12-9
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
The table below shows the relationship between analog and digitized
measured values for the measuring ranges:
"
80 mV,
"
250 mV,
"
500 mV
and
"
1000 mV.
Table 12-5
Digitized Measured Values for ET 200C; AI 4/8
12 Bit (Measuring Ranges:
"
80 mV,
"
250 mV,
"
500 mV and
"
1000 mV)
Units
Measured value in mV
Digitized measured value
X F O
Range
"
80
"
250
"
500
"
1000
"
80
mV
"
250
mV
"
500
mV
"
1000
mV
15 14 13 12 11 10 9 8 7 6 5 4 3
2 1 0
> 2409
94.10
294.07
588.13
1176.26
0 1 0 0 1 0 1 1 0 1 0 0 1 0 0 1
Overflow
2408
94.06
293.95
587.89
1175.78
0 1 0 0 1 0 1 1 0 1 0 0 0 0 0 0
Overload
:
:
:
:
:
:
Overload
range
2049
80.04
250.12
500.24
1000.48
0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
range
2048
80.00
250.0
500.0
1000.0
0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
1024
40.00
125.00
250.00
500.00
0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
1
0.039
0.12
0.24
0.48
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
Nominal
range
0
0.00
0.00
0.00
0.00
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
range
–1
–0.039
–0.12
–0.24
–0.48
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–1024
–40.00
–125.00
–250.00
–500.00
1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0
–2048
–80.00
–250.0
–500.0
–1000.0
1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–2049
–80.04
–250.12
–500.24
–1000.48 1 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
Overload
:
:
:
:
:
:
Overload
range
–2408
–94.06
–293.95
587.89
–1175.78 1 0 1 1 0 1 0 0 1 1 0 0 0 0 0 0
range
< –2409
–94.10
–294.07
–588.13
–1176.26 1 0 1 1 0 1 0 0 1 0 1 1 1 0 0 1
Overflow
Table of Measured
Values
Analog Modules
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...