background image

7-1

ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b

Fault Diagnostics with the IM 308-B

This chapter contains information on diagnosing faults on the ET 200C dis-
tributed I/O station.

This chapter describes fault detection:

via LEDs on the front panel of the module (see Section 7.1)

with COM ET 200 V4.x and the programmer (see Section 7.2)

via STEP 5 (see Section 7.3)

Fault detection via STEP 5 (station diagnostics) is included here for situa-
tions where the ”diagnostics” master of the ET 200C is an IM 308-B.

In this Chapter

7

Summary of Contents for SIMATIC ET 200C

Page 1: ...ith COM ET 200 6 Fault Diagnostics with the IM 308 B 7 Fault Diagnostics with the IM 308 C 8 Connection of the ET 200 Handheld 9 General Technical Specifications 10 Digital Modules 11 Analog Modules 12 Other ET 200C Components 13 Pin Assignments of the ET 200C Modules A Type files B Safety Related Guidelines C Glossary Index EWA 4NEB 812 6119 02b Edition 03 ET 200C Distributed I O Station Manual S...

Page 2: ... operated in conjunction with this manual Note the following Warning This device and its components may only be used for the applications described in the cata log or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens This product can only function correctly and safely if it is transported stored s...

Page 3: ...3 Chap 4 Chap 6 Chap 7 8 What is ET 200C Chap 1 How do I set the address and parameters with COM ET 200 Chap 5 How do I connect the ET 200 handheld Chap 9 Chap 10 11 12 13 Pin assignment type files Appendix A B This manual covers all the ET 200C modules that can be addressed with the DP standard bus protocol Each of these ET 200C modules has an order number beginning with 6ES7 See Chapter 10 1 Thi...

Page 4: ...require At the start of the manual you will find a general table of contents plus a list of all the illustrations and a list of all the tables in the manual On each page throughout the manual the bold face headings on the left summarize the contents of the individual passages The Appendices are followed by a Glossary containing definitions of the important terms used in this manual The manual clos...

Page 5: ... 3 1 3 1 Digital Input Module ET 200C DI 8 DC 24V 6ES7 141 0BF00 0XB0 3 2 3 2 Digital Output Module ET 200C DO 8 DC 24V 0 5A 6ES7 142 0BF00 0XB0 3 4 3 3 Digital Output Module ET 200C DO 8 DC 24V 2A 6ES7 142 0BF10 0XB0 3 6 3 4 Digital Input Output Module ET 200C DI 16 DO 16 DC 24V 6ES 143 0BL00 0XB0 and 6ES7 143 0BL10 0XB0 3 8 3 5 Analog Input Module ET 200C AI 4 8 12 Bit 6ES7 144 0KH00 0XB0 3 11 3...

Page 6: ...nalog Modules of ET 200C 4 43 4 4 1 Setting the Station Number of Analog Modules by Means of DIL Switch Block S1 4 44 4 4 2 Setting the Measurement Type for Analog Module ET 200C AI 4 8 12 Bit 4 46 4 4 3 Setting Measurement Type for Analog Module ET 200C AI 4 12 Bit 4 50 4 4 4 Setting Connection Mode for Analog Module ET 200C AO 4 12 Bit 4 52 5 Address Assignment and Parameterization with COM ET 2...

Page 7: ... 10 2 General Technical Specifications 10 3 11 Digital Modules 11 1 11 1 Digital Input Module ET 200C DI 8 DC 24V 6ES7 141 0BF00 0BX0 11 2 11 2 Digital Output Module ET 200C DO 8 DC 24V 0 5A 6ES7 142 0BF00 0XB0 11 6 11 3 Digital Output Module ET 200C DO 8 DC 24V 2A 6ES7 142 0BF10 0XB0 11 11 11 4 Digital Input Output Module ET 200C DI 16 DO 16 DC 24V 2A 6ES7 143 0BL00 0XB0 and 6ES7 143 0BL10 0XB0 1...

Page 8: ...200 V4 x C 8DO DP B 4 B 1 3 Type File SN8012TD 200 COM ET 200 V4 x C 8DO 2A DP B 5 B 1 4 Type File SN8013TD 200 COM ET 200 V4 x C 16DI 16DO 2A DP B 6 B 2 Type Files of ET 200C Analog Modules for COM ET 200 Windows B 7 B 2 1 Type File SI800FAD 200 COM ET 200 Windows C 4 8AI DP B 8 B 2 2 Type File SI800EAD 200 COM ET 200 Windows C 4AI DP B 13 B 2 3 Type File SI800DAD 200 COM ET 200 Windows C 4AO DP ...

Page 9: ...dule ET 200C DI 16 DO 16 DC 24V with Circular Connector 6ES7 143 0BL00 0XB0 3 9 3 5 Digital I O Module ET 200C DI 16 DO 16 DC 24 V with Conduit Thread Glands 6ES7 143 0BL10 0XB0 3 10 3 6 Analog Input Module ET 200C AI 4 8 12 Bit 6ES7 144 0KH00 0XB0 3 12 3 7 Analog Input Module ET 200C AI 4 12 Bit 6ES7 144 0HF00 0XB0 3 14 3 8 Analog Output Module ET 200C AO 4 12 Bit 6ES7 145 0HF00 0XB0 3 16 3 9 T C...

Page 10: ...Cable 4 35 4 24 Arrangement of Screw Terminals and DIL Switches in ET 200C AO 4 12 Bit 4 37 4 25 Connection of Loads to ET 200C AO 4 12 Bit 4 Wire Circuit for Voltage Output 4 38 4 26 Connection of Loads to ET 200C AO 4 12 Bit 2 Wire Circuit for Voltage Output 4 39 4 27 Connection of Loads to ET 200C AO 4 12 Bit 2 Wire Circuit for Current Output 4 40 4 28 DIL Switch Block in Default Position As De...

Page 11: ...Modules 8 24 8 8 Structure of Diagnostics Word Header Device related Diagnostics DW n 4 for Analog ET 200C Modules 8 25 8 9 Structure of Diagnostics Word Device related Diagnostics Diagnostics Alarm DW n 5 for Analog ET 200C Modules 8 25 8 10 Structure of Diagnostics Word Device related Diagnostics Diagnostics Alarm DW n 6 for Analog ET 200C Modules 8 26 8 11 Structure of Diagnostics Word Device r...

Page 12: ... Digital Input Output Module ET 200C DI 16 DO 16 DC 24 V 2A 6ES7 143 0BL00 0XB0 Dimension Drawing 11 20 11 12 Digital Input Output Module ET 200C DI 16 DO 16 DC 24 V 2A 6ES7 143 0BL10 0XB0 Dimension Drawing 11 21 11 13 Digital Input Output Module ET 200C DI 16 DO 16 DC 24 V 2A 6ES7 143 0BL00 0XB0 Dimension Drawing with T Connector and Plug Connectors with Pin Socket Inserts 11 22 11 14 Digital Inp...

Page 13: ...t Module AO 4 12 Bit Dimensional Drawing with T connector 12 43 13 1 Power Supply Connector Dimension Drawing with Plug Connectors with Pin Socket Insert 13 3 13 2 Power Supply Connector Dimension Drawing 13 4 13 3 Programmer Connector Dimension Drawing with Plug Connectors with Pin Socket Insert 13 5 13 4 Programmer Connector Dimension Drawing 13 6 Contents ...

Page 14: ...nection where only the Power Supply is Connected 4 12 4 5 Pin Assignment of the Bus Connection if SINEC L2 DP and Power Supply are Connected 4 12 4 6 Pin Assignment of the Inputs of ET 200C DI 8 DC 24V 6ES7 141 0BF00 0XB0 4 13 4 7 Pin Assignments of the Outputs of ET 200C DO 8 DC 24V 0 5A 6ES7 142 0BF00 0XB0 and ET 200C DO 8 DC 24V 2A 6ES7 142 0BF10 0XB0 4 15 4 8 Pin Assignments of the Inputs of E...

Page 15: ...8 6 Structure of Station Diagnostics for Digital ET 200C Modules 8 7 8 7 Structure of Station Diagnostics for ET 200C AI 4 8 12 Bit 8 8 8 8 Structure of Station Diagnostics for ET 200C AI 4 12 Bit 8 9 8 9 Structure of Station Diagnostics for ET 200C AO 4 12 Bit 8 10 8 10 Position of the Diagnostics Data in the Data Block 8 14 8 11 Position of Diagnostics Data in Data Block for ET 200C digital ET 2...

Page 16: ...Digitized Measured Values for ET 200C AI 4 8 12 Bit for Type E Thermocouple 12 17 12 17 Parameters for ET 200C Analog Input Module AI 4 12 Bit 12 22 12 18 Presentation of an Analog Input Value as Bit Pattern for ET 200C AI 4 12 Bit 12 24 12 19 Description of bits for ET 200C AI 4 12 Bit 12 24 12 20 Digitized Measured Values for ET 200C AI 4 12 Bit Measuring Ranges 1 25 V 2 5 V 5 V 10 V 12 25 12 21...

Page 17: ...C 24V 2A 6ES7 143 0BL00 0BX0 A 3 A 5 Pin Assignment Outputs of ET 200C DO 8 DC 24V 0 5A ET 200C DO 8 DC 24V 2A and ET 200C DI16 DO16 DC 24V 2A 6ES7 143 0BL00 0XB0 A 3 A 6 Pin Assignment Inputs and Outputs of ET 200C DI 16 DO 16 DC 24V 2A 6ES7 143 0BL10 0XB0 A 3 A 7 Pin Assignment for Load Voltage Supply ET 200C Modules with Outputs A 4 A 8 Pin Assignment External Power Supply at PSU Feed A 4 A 9 P...

Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...

Page 19: ...ion EWA 4NEB 812 6119 02b Configuration This chapter Configuration provides you with information on the position of the ET 200C distributed I O station in the distributed I O system and the components of the ET 200C In this Chapter 1 ...

Page 20: ...riant of SINEC L2 called SINEC L2 DP This version is designed for communication with the distributed I O at extremely short response times The distributed I O system comprises active and passive stations the SINEC L2 DP field bus and the SINEC L2 network components The distributed I O station is a slave station Other field devices SINEC L2 DP Field Bus 2 wire or Fiber Optic Cable ET 200C ET 200B E...

Page 21: ...s each form a slave station 8DO 8DI 8DO 2A 16DI 16DO Digital Input Module DI 8 DC 24V Digital Output Module DO 8 DC 24V 0 5A Digital Output Module DO 8 DC 24V 2A Digital Input Output Module DI 16 DO 16 DC 24V 2A 4 8AI 4AI 4AO Analog Input Module AI 4 8 12 Bit Analog Input Module AI 4 12 Bit Analog Output Module AO 4 12 Bit Figure 1 2 ET 200C Digital and Analog Modules Range of Modules Configuratio...

Page 22: ...e Adapter Cable 2 core 5 core 3 core PG Terminating Resistor Figure 1 3 Other ET 200C Components All ET 200C components can be addressed under the DP standard bus proto col Note ET 200C can be operated with the following master interface modules and versions of COM ET 200 IM 308 B revision level 5 or higher and COM ET 200 V4 0 or later see Chapters 5 and 6 only in conjunction with ET 200C digital ...

Page 23: ...l modules only 2 wire and 3 wire proximity switches can be connected Electrical isolation between the SINEC L2 DP field bus and the process side of the ET 200C modules Direct connection of programmer or ET 200 handheld possible with adapter cable and programmer with programmer interface module CP5410 S5DOS ST For setting the station number digital modules require ET 200 handheld analog modules by ...

Page 24: ...M 308 C master interface and ten ET 200C DI 16 DO 16 DC 24V 2A distributed I O stations each with 2 byte inputs outputs The baud rate is 12 Mbaud The reaction time for a complete data cycle is thus 0 45 ms The reaction time tDP for a data cycle is calculated as follows tDP A B number of I O bytes Tbyte slave 1 B number of I O bytes Tbyte slave 2 B number of I O bytes Tbyte slave n A B Tbyte master...

Page 25: ...C L2 bus cable in accordance with the baud rate on the bus when configuring the ET 200C Table 1 2 Length of the SINEC L2 Bus Cable in Accordance with the Baud Rate on the SINEC L2 DP Bus Baud rate Max length of bus cable 500 kbaud 500 m segment 500 kbaud 400 m segment 1500 kbaud 200 m segment 1500 kbaud 100 m segment Configuration ...

Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...

Page 27: ...2 1 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options This chapter describes the configuration options offered to you by ET 200C In this Chapter 2 ...

Page 28: ...hout T connector Section 2 1 1 connector Configuration with power supply connector and with T connector Section 2 1 2 Configuration with several power supply connectors the level of expansion with one power supply connector is limited Section 2 1 3 Configuration with programmer connector Section 2 1 5 Configuration without power supply connector Configuration without power supply connector Section...

Page 29: ...e Bus Cable incl PS Cable Adapter Cable 2 core 5 core 3 core see note PG Terminating Resistor conn Figure 2 1 Legend Note You will require a 3 core cable for the load voltage supply and the separate power supply connectors of the digital modules You can however also use the prefabricated 5 core cable from Siemens for the load voltage Two of the conductors will then not be used in this case see Sec...

Page 30: ... is required for the slave station If a slave station is disconnected from the bus the Bus traffic is interrupted for slave stations located further down the line Since there is then no terminating resistor available bus traffic might be dis turbed for slave stations still connected to the bus The level of expansion using one power supply connector is limited see Section 2 1 3 Different types of c...

Page 31: ...Power Supply SINEC L2 DP PS conn 16DI 16DO Load Voltage Supply Looped On Load Voltage Supply for Channel Group Q0 Load Voltage Supply for Channel Group Q1 1 No separate load voltage supply is necessary for analog output modules External Load Voltage Supply Figure 2 2 SINEC L2 DP Field Bus and Power Supply Looped Through at ET 200C Slave Station Configuration ET 200C Configuration Options ...

Page 32: ...DO 8 DC 24V 2A Ambient temperature 25 25 C max 10 A 26 40 C max 8 A 41 60 C max 4 A ET 200C DI 16 DO 16 DC 24V 2A outputs in groups of 4 Ambient temperature 25 25 C max 3 5 A per group of 4 26 40 C max 2 5 A per group of 4 41 60 C max 1 5 A per group of 4 Note An external load voltage supply can only be looped via the digital output module DO 8 DC 24V 0 5A until the maximum current of 4 A is reach...

Page 33: ...n can be disconnected at any time from the bus without inter rupting the Bus traffic for the remaining slave stations The power supply is fed over the bus cable i e no external power supply is required for the slave stations The level of expansion with one power supply connector is limited see Section 2 1 3 Different types of cable can be used for the various configurations Read Section 3 11 if yo...

Page 34: ... Fig 2 3 8DO 4AO1 4AI SV External Power Supply SINEC L2 DP PS conn 8DO 16DI 16DO Load Voltage Supply Looped On Load Voltage Supply for Chan nel Group Q0 Load Voltage Supply for Channel Group Q1 1 No separate load voltage supply is necessary for analog output modules External Load Voltage Supply Figure 2 3 SINEC L2 DP Field Bus and Power Supply Looped Through with T Connectors Configuration ET 200C...

Page 35: ... 40 C max 2 5 A per group of 4 41 60 C max 1 5 A per group of 4 Note An external load voltage supply can only be looped via the digital output module DO 8 DC 24V 0 5A until the maximum current of 4 A is reached The maximum current load of 4 A is not protected by means of a fuse in the module Spur lines are not permitted on the ET 200C except for the programmer or the ET 200 handheld This means tha...

Page 36: ...upply connector The current consumption of the digital modules limits the number of digital modules that can be connected Table 2 5 Current Consumption of the Digital Modules of ET 200C Digital module Current consumption comprises Current consumption ET 200C DI 8 DC 24V Power supply for internal logic and Sensor supply typ 135 mA application specific see Section 4 3 2 ET 200C DO 8 DC 24V 0 5A Powe...

Page 37: ...n be seen in Fig 2 5 8DO 8DI 8DI SV 8DO External Load Voltage Supply External Power Supply SINEC L2 DP PS SV External Power Supply SINEC L2 DP1 PS 1 In this case you can use a 2 or 5 core cable The 2 left connections for External power supply and SINEC L2 DP are not jumpered conn conn Figure 2 5 Configuration using Several Power Supply Connectors Remedy ET 200C Configuration Options ...

Page 38: ...ore cable A slave station can be disconnected at any time from the bus without the Bus traffic being interrupted for slave stations further down the line since the field bus is looped via the T connectors Different types of cable can be used for the various configurations Read Section 3 11 if you wish to use prefabricated cables from Siemens Read Section 4 3 if you wish to prepare the cables yours...

Page 39: ...xternal Load Voltage Supply for Channel Group Q0 Load Voltage Supply for Channel Group Q1 1 No separate load voltage supply is necessary for analog output modules External Power Supply Two wire Cable External Power Supply External Power Supply External Power Supply Figure 2 6 SINEC L2 DP Field Bus Looped Through with T Connectors Individual External Power Supply to Each Slave Station Configuration...

Page 40: ...max 3 5 A per group of 4 26 40 C max 2 5 A per group of 4 41 60 C max 1 5 A per group of 4 Note An external load voltage supply can only be looped via the digital output module DO 8 DC 24V 0 5A until the maximum current of 4 A is reached The maximum current load of 4 A is not protected by means of a fuse in the module Spur lines are not permitted on the ET 200C except for the programmer or the ET ...

Page 41: ... 200C modules This could cause the gradual destruction of the ET 200C modules If you connect an external power supply to an ET 200C module it is imperative to use only the 2 core bus cable for connecting the SINEC L2 DP 8DI External Power Supply SINEC L2 DP 8DI External Power Supply SINEC L2 DP with Power Supply 8DI External Power Supply SINEC L2 DP with Power Supply SINEC L2 DP 8DI External Power...

Page 42: ...grammer connector It can only be plugged into the bus connection of a slave station via the adapter cable Connection of the ET 200 handheld is described in detail in Chapter 9 1 A possible configuration with a programmer connector can be seen in Fig 2 9 8DO 8DO 2A 8DI SV External Power Supply SINEC L2 DP PS conn Adapter Cable Programmer Connecting Cable External Load Voltage Supply for Channel Gro...

Page 43: ...us You can however only connect one programmer to one of the programmer connectors on the bus since the programmer is a station with the number 0 The following values apply for the length of the spur line in accordance with the baud rate on the SINEC L2 DP bus when connecting a programmer Table 2 7 Length of the Spur Line of the Programmer Connection in Accordance with the Baud Rate on the SINEC L...

Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...

Page 45: ... 1 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components All components of the ET 200C with their performance data and characteris tics are described in this chapter In this Chapter 3 ...

Page 46: ...odule is operated with the IM 308 C see Section 1 2 Channel by channel diagnostics of the inputs for wire breaks and short circuit overload of the sensor supply can be switched off with COM ET 200 see Section 5 1 4 The diagnostics can be output via the IM 308 B master interface module In addition each diagnostic message causes the LED DIA or the respective individual diagnostics LED to light up LE...

Page 47: ...onnection 2 bus connections 12 pin socket The 12 pin sockets can be used for several purposes To connect the SINEC L2 DP field bus To connect the power supply To connect the field bus and incorporated power supply The bus connections are interconnected internally Figure 3 1 Digital Input Module ET 200C DI 8 DC 24V 6ES7 141 0BF00 0XB0 Connections ET 200C Components ...

Page 48: ...e is operated with the IM 308 C see Section 1 2 Channel by channel diagnostics of the outputs for wire break and short circuit overload and load voltage of the outputs can be switched off with COM ET 200 see Section 5 1 4 The diagnostics can be output via the IM 308 B master interface module In addition each diagnostic message causes the LED DIA or the respective individual diagnostics LED to ligh...

Page 49: ...connect the field bus and incorporated power supply The bus connections are interconnected internally 2 connections for external load voltage supply 6 pin male connector for feeding load voltage supply 6 pin socket for looping the load voltage supply The load voltage connections are interconnected internally i e the load voltage supply can be looped via the digital output module provided a total c...

Page 50: ...s operated with the IM 308 C see Section 1 2 Channel by channel diagnostics of the outputs for wire break and short circuit overload and load voltage of the outputs can be switched off with COM ET 200 see Section 5 1 4 The diagnostics can be output via the IM 308 B master interface module In addition each diagnostic message causes the LED DIA or the respective individual diagnostics LED to light u...

Page 51: ...d for several purposes to connect the SINEC L2 DP field bus to connect the power supply to connect the field bus and incorporated power supply The bus connections are interconnected internally 1 connection for external load voltage supply 6 pin male connector The load voltage supply cannot be looped if the ET 200C DO 8 DC 24V 2A is used Figure 3 3 Digital Output Module ET 200C DO 8 DC 24V 2A 6ES7 ...

Page 52: ...perated with the IM 308 C see Section 1 2 Diagnostics for 4 outputs of a channel group for wire break short circuit overload and load voltage of the outputs LED DIA for output x 0 to x 3 LED DIA for output x 4 to x 7 x 0 1 Diagnostics for 4 inputs of a channel group for wire break short circuit overload of the sensor supply LED DIA for input x 0 to x 3 LED DIA for input x 4 to x 7 x 0 1 The diagno...

Page 53: ...onnect the field bus and incorporated power supply The bus connections are interconnected internally 2 connections for external load voltage supply 6 pin male connector There is a separate load voltage connection for each channel group Q0 Q1 The load voltage cannot be looped via the digital input output module Male Connector for Feeding the Load Voltage Supply for Q1 Male Connector for Feeding the...

Page 54: ...143 0BL00 0XB0 and 6ES7 143 0BL10 0XB0 Continued Male Connector for the Load Voltage Supply Input for Q1 Male Connector for the Load Voltage Supply Input for Q0 Sockets for Connecting SINEC L2 DP Figure 3 5 Digital I O Module ET 200C DI 16 DO 16 DC 24 V with Conduit Thread Glands 6ES7 143 0BL10 0XB0 ET 200C Components ...

Page 55: ... J L E Resistance thermometers Pt100 Ni100 The analog input module ET 200C AI 4 8 12 bit is suitable for either two wire or four wire connection This means that the measuring range can be set only on the basis of channel groups Channel diagnostics of inputs for wire break range overshoot common mode voltage overshoot short circuit and parameterization error can be switched off with COM ET 200 see ...

Page 56: ...nnels for thermocouples and voltage sensors 2 wire or 4 input channels 4 wire 2 bus connectors 12 pin socket The 12 pin sockets can be used for connecting to the SINEC L2 DP field bus connecting to the power supply connecting to the combined field bus and power supply cable The bus connectors are linked internally Figure 3 6 Analog Input Module ET 200C AI 4 8 12 Bit 6ES7 144 0KH00 0XB0 Connections...

Page 57: ...ncryption successive approximation Measuring range selectable separately for each channel group 1 25 V 2 5 V 5V 10 V 20 mA 0 20 mA 4 20 mA Channel diagnostics of inputs for range overshoot and parameterization error can be switched off with COM ET 200 see Section 5 1 4 Channel diagnostics can be evaluated only via the IM 308 C master interface Each diagnostics message causes the DIA LED to light u...

Page 58: ...llowing connec tions 4 input channels 2 wire 2 bus connectors 12 pin socket The 12 pin sockets can be used for connecting to the SINEC L2 DP field bus connecting to the power supply connecting to the combined field bus and power supply cable The bus connectors are linked internally Figure 3 7 Analog Input Module ET 200C AI 4 12 Bit 6ES7 144 0HF00 0XB0 Connections ET 200C Components ...

Page 59: ...e separately for each channel group 10 V 0 10 V 20 mA 0 20 mA 4 20 mA Channel diagnostics of outputs for wire break range overshoot common mode voltage overshoot short circuit and parameterization error can be switched off with COM ET 200 see Section 5 1 4 Channel diagnostics can be evaluated only via the IM 308 C master interface Each diagnostics message causes the DIA LED to light up LEDs for RU...

Page 60: ... following con nections 4 output channels 2 bus connectors 12 pin socket The 12 pin sockets can be used for connecting to the SINEC L2 DP field bus connecting to the power supply connecting to the combined field bus and power supply cable The bus connectors are linked internally Figure 3 8 Analog Output Module ET 200C AO 4 12 Bit 6ES7 145 0HF00 0XB0 Connections ET 200C Components ...

Page 61: ...ics Degree of protection IP 66 IP 67 see Installation rules Section 4 1 Choice of following baud rates 9 6 19 2 93 75 187 5 500 1500 3000 6000 or 12000 kbaud The baud rates 3000 6000 and 12000 kbaud are only possible when the module is operated with the IM 308 C see Section 1 2 A T connector has 3 bus connections Two 12 pin sockets One 12 pin male connector The T connector is attached to the bus c...

Page 62: ...8 C and the digital modules see Section 1 2 Loadable with a maximum of 4 A input current This limits the number of digital input modules that can be connected see Section 2 1 3 Does not represent a bus node with station number Attachment without opening the cover drill hole template at the back of the manual The power supply connector has the following connections Connection for Incoming SINEC L2 ...

Page 63: ...tal modules see Section 1 2 Can be placed anywhere on the bus exception the programmer connector may not be attached to the ends of the bus cable since there is then no space for the terminating resistor Does not represent a bus node with station number Attachment without opening the cover drill hole template at the back of the manual A programmer connector has three bus connections Connection for...

Page 64: ...cables are available precut and terminated at both ends one end or not at all with 12 pin male connector for SINEC L2 DP bus connection and or power supply and or with 6 pin connection for load voltage supply You can however also prepare the cables yourself The necessary informa tion can be found in Section 4 3 Note All prefabricated cables have a core cross sectional area of 0 75 mm2 for a maximu...

Page 65: ...r feeding the power supply separately as bus cable is connected may cause interference on the bus If you require cables of a different length you can order these using Z num bers Specify the order number and the desired length e g 6ES5 717 1AA01 Z 3 50 m Table 3 3 Order Numbers for Standard Cable Lengths Core Cross Sectional Area 0 75 mm2 Max Current Load 4 A Description Cable standard sheath Cabl...

Page 66: ...g resis tor On the ET 200C the terminating resistor is screwed onto a 12 pin socket The terminating resistor can be screwed onto the bus connection of Digital and analog modules or T connector The terminating resistor has Degree of protection IP 66 IP 67 see Installation rules Section 4 1 Figure 3 12 Terminating Resistor Application Characteristics ET 200C Components ...

Page 67: ...has the following characteristics Degree of protection IP 66 IP 67 see Installation rules Section 4 1 only at the end with the IP 66 IP 67 bus connector Choice of following baud rates 9 6 19 2 93 75 187 5 500 1500 3000 6000 or 12000 kbaud The baud rates 3000 6000 and 12000 kbaud are only possible when operating with the IM 308 C and digital modules see Section 1 2 The adapter cable has the followi...

Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...

Page 69: ...4 1 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Mechanical and Electrical Installation This chapter describes the mechanical and electrical installation of the ET 200C In this Chapter 4 ...

Page 70: ...ity of all metal and plastic seals on the ET 200C distributed I O station The ET 200C modules can be installed in any position and inclined at any angle Note the minimum distances between ET 200C modules and cable ducts Table 4 1 Distances between ET 200C Modules and Cable Ducts Between ET 200C module and cable duct Distance no T connector is installed 10 cm a T connector is installed 5 cm Captive...

Page 71: ...llowing two sections include a circuit example for Grounded configuration and Ungrounded configuration The text contains code numbers which are references to the respective dia gram Note We recommend the grounded configuration for analog modules This configuration provides additional protection against electromagnetic interference Introduction Mechanical and Electrical Installation ...

Page 72: ...back up capacitor with a rating of 200 F per 1 A load current 3 You should provide in secondary circuit a connection 4 to the protective conductor on the load power supply terminal M You need a main power fuse to protect the supply voltage 5 For both grounded and ungrounded configurations use a low resistance conductor to connect the protective ground PE terminal of the ET 200C modules digital and...

Page 73: ...low L1 L2 L3 N PE 1 2 3 4 5 M L Connection for Grounded Configuration M L M L PE M L PE M L PE M L PE 6 I O Sensor Actuator I O Sensor Actuator PS Conn PE PE ET 200C ET 200C Figure 4 1 Grounded Configuration for ET 200C with 24 V DC Current Load Voltage Supply Configuration Mechanical and Electrical Installation ...

Page 74: ...tional extra low voltage with protective separation in accordance with VDE 0106 Part 101 If you use a switched mode power supply you will need a back up capacitor with a rating of 200 F per 1 A load current 3 You need a main power fuse to protect the supply voltage 5 For both grounded and ungrounded configurations use a low resistance conductor to connect the protective ground PE terminal of the E...

Page 75: ... configuration for the ET 200C is shown below L1 L2 L3 N PE 1 2 3 5 M L M L M L PE M L PE M L PE M L PE 6 I O Sensor Actuator I O Sensor Actuator PS Conn 7 U ET 200C ET 200C Figure 4 2 Ungrounded Configuration for ET 200C Configuration Mechanical and Electrical Installation ...

Page 76: ... instructions if you wish to prepare the cables yourself You will require 6 pin and 12 pin circular connectors sockets for connecting the bus power supply and the load voltage supply The following table contains the order numbers for 6 pin and 12 pin circular connectors Table 4 2 Order Numbers for Circular Connectors Round connector socket Order number 6 pin connector with a socket insert not pref...

Page 77: ...AI 4 8 12 bit 6ES7 144 0KH00 0XB0 ET 200C AI 4 12 bit 6ES7 144 0HF00 0XB0 ET 200C AO 4 12 bit 6ES7 145 0HF00 0XB0 are connected by means of cable glands which carry the cable through the housing and into the module Connect the cables as indicated by the labels on the terminals see Section 4 3 4 The inputs outputs have conduit threads in order to secure the signal lines and to ensure that the appro...

Page 78: ...or 2 bus connections a 3rd bus connection is screwed directly onto the ET 200C module Power supply connector 2 bus connections 1 SINEC L2 DP 1 power supply and SINEC L2 DP together Programmer connector 3 bus connections SV PS Conn 8DO 8DI 8DO 2A 16DI 16DO PG 4AI 4 8AI 4AO Figure 4 3 Bus Connections of the ET 200C Modules All ET 200C modules have a socket as bus connection i e a plug connector must...

Page 79: ...cond bus connection It is only permissible to connect the 2 core SINEC L2 bus cable where a T connector is used If you only wish to connect the SINEC L2 DP bus you will require 12 pin circular connectors SINEC L2 2 core cable Connect the circular connectors in accordance with the following table Table 4 3 Pin Assignment of the Bus Connection where only the SINEC L2 DP is Connected Pin Assignment P...

Page 80: ...ved 10 reserved 5 reserved 11 reserved 6 reserved 12 reserved If you combine the SINEC L2 DP bus and the power supply in a single cable you will require 12 pin circular plugs 5 core cable with a diameter of 6 to 10 mm Table 4 5 Pin Assignment of the Bus Connection if SINEC L2 DP and Power Supply are Connected Pin Assignment Pin Assignment 1 reserved 7 P 24 V 2 A green 8 M 24 V 3 reserved 9 PE 4 B ...

Page 81: ... the pin assignment in the following table Table 4 6 Pin Assignment of the Inputs of ET 200C DI 8 DC 24V 6ES7 141 0BF00 0XB0 Pin Input View 1 24 V DC1 1 2 2 Free 1 2 5 3 Ground 3 4 5 4 Signal View Mating Side 3 4 5 PE View Mating Side 1 The module supplies this 24 V DC at pin 1 as the voltage supply for the connected sensors Inputs which are not required must be sealed using the enclosed twist cap...

Page 82: ...must be connected to ground at the input for wire break recognition Output Input 2 4 kW Wire Break Recognition with 2 4 kW Resistor Figure 4 4 Sensor Supply Returned to Input without Load If a load is connected only a wire break on the connection to the load will be recognized The connection between the sensor supply and the input cannot be monitored for wire breaks Output Input Load Wire Break Re...

Page 83: ...0 75 mm2 Connect the outputs in accordance with the pin assignments in the table below Table 4 7 Pin Assignments of the Outputs of ET 200C DO 8 DC 24V 0 5A 6ES7 142 0BF00 0XB0 and ET 200C DO 8 DC 24V 2A 6ES7 142 0BF10 0XB0 Pin Output View 1 Free 1 2 2 Free 1 2 5 3 Ground 3 4 5 4 Signal View Mating Side 3 4 5 PE View Mating Side Outputs which are not required must be sealed using the enclosed twist...

Page 84: ...nnected in the COM ET 200 see section 5 1 4 or a resistor 2 4 kW must be connected to ground at the input for wire break recognition Output Input 2 4 kW Wire Break Recognition with 2 4 kW Resistor Figure 4 6 Output Returned to Input without Load If a load is connected a wire break is only recognized on the connection to the load The output input connection can not be monitored for wire break Outpu...

Page 85: ... Pin Input View 1 24 V DC1 1 2 2 Free 1 2 5 3 Ground 3 4 5 4 Signal View Mating Side 3 4 5 PE View Mating Side 1 The module supplies this 24 V DC at pin 1 as the voltage supply for the connected sensors Connect the outputs in accordance with the pin assignments in the following table Table 4 9 Pin Assignments of the Outputs of ET 200C DI 16 DO 16 DC 24V 2A 6ES7 143 0BL00 0XB0 Pin Input View 1 Free...

Page 86: ... 200 see section 5 1 4 or a resistor 2 4 kW must be connected to ground at the input for wire break recognition Output Input 2 4 kW Wire Break Recognition with 2 4 kW Resistor Figure 4 8 Output Returned to Input without Load If a load is connected a wire break is only recognized on the connection to the load The output input connection can not be monitored for wire break Output Input Load Wire Bre...

Page 87: ...tighten the conduit thread 6 Fill in the labelling strips on the front of the module 7 Close the module using a screwdriver Connect the signal lines in accordance with the terminal assignments in the following table Table 4 10 Connection Assignments of ET 200C DI 16 DO 16 DC 24V 2A 6ES7 143 0BL10 0XB0 Terminal Assignment I0 0 I0 7 I0 Input 0 7 I1 0 I1 7 I1 Input 0 7 Q0 0 Q0 7 Q0 Output 0 7 Q1 0 Q1...

Page 88: ...1 4 0V PE 24V I1 8 0V PE 24V I0 1 0V PE 24V I0 3 0V PE 24V I0 5 0V PE 24V I0 7 0V PE 24V I1 1 0V PE 24V I1 3 0V PE 24V I1 5 0V PE 24V I1 7 0V PE Q0 1 M1 PE Q0 3 M1 PE Q0 5 M1 PE Q0 7 M1 PE Q1 1 M2 PE Q1 3 M2 PE Q1 5 M2 PE Q1 7 M2 PE Q0 0 M1 PE Q0 2 M1 PE Q0 4 M1 PE Q0 6 M1 PE Q1 0 M2 PE Q1 2 M2 PE Q1 4 M2 PE Q1 6 M2 PE 1 1 1 1 1 1 1 1 1 1 Screw terminals pre wired Figure 4 10 Arrangement of Screw ...

Page 89: ... braided shield flush with the outer edge of the sleeve 7 Pull the ends of the signal cables though the glands with the foil and cut off the foil 8 Strip the ends of the signal lines and crimp the conductors with wire ferrules 9 Connect the lines to the corresponding terminals 10 Pull the lines taut and tighten the gland 11 Repeat steps 2 through 10 with other signal lines or close the module usin...

Page 90: ...easuring line Measuring line 8 Measuring line Measuring line Measuring line 9 Constant current line IC CH3 Measuring line Measuring line 10 Constant current line IC Measuring line Measuring line 11 CH2 Measuring line CH4 Measuring line Measuring line 12 Measuring line Measuring line Measuring line 13 Constant current line IC CH5 Measuring line Measuring line 14 Constant current line IC Measuring l...

Page 91: ...ors Figure 4 12 Arrangement of Screw Terminals and DIL Switches in ET 200C AI 4 8 12 Bit Table 4 12 DIL Switch Blocks in the ET 200C AI 4 8 12 Bit DIL switch block Function Described in S1 Manually set the station number Section 4 4 1 S2 Select 2 wire or 4 wire con nection for Pt100 resistance thermometers Section 4 4 2 S3 Select external internal and floating non floating com pensation for thermo...

Page 92: ...ment and external floating compensation MANA 1 2 OFF 1 2 3 4 5 6 7 8 ON ON 1 2 3 4 5 6 7 8 ON ON S3 S2 S4 Compensator Shield Thermal Coupling CH0 COMP CH1 CH2 CH3 CH4 CH5 CH6 CH7 Figure 4 13 Connection to ET 200C AI 4 8 12 Bit of Thermocouples for Floating Measurement and External Floating Compensation Thermocouple Floating Measurement and Floating External Compensation Mechanical and Electrical I...

Page 93: ...ion MANA 1 2 OFF 1 2 3 4 5 6 7 8 ON ON 1 2 3 4 5 6 7 8 ON ON Thermal Coupling CH0 COMP CH1 CH2 CH3 CH4 CH5 CH6 CH7 S3 S2 S4 Compensation Shield Figure 4 14 Connection to ET 200C AI 4 8 12 Bit of Thermocouples for Non Floating Measurement and External Non Floating Compensation Thermocouple Non Floating Measurement and Non Floating External Compensation Mechanical and Electrical Installation ...

Page 94: ...d for non floating measurement and internal compensation MANA 1 2 OFF 1 2 3 4 5 6 7 8 ON ON 1 2 3 4 5 6 7 8 ON ON CH0 COMP CH1 CH2 CH3 CH4 CH5 CH6 CH7 S3 S2 S4 Schirm Figure 4 15 Connection to ET 200C AI 4 8 12 Bit of Thermocouples for Non Floating Measurement and Internal Compensation Thermocouple Non Floating Measurement and Internal Compensation Mechanical and Electrical Installation ...

Page 95: ...ing see Section 4 4 2 Note If a resistance thermometer Pt100 is used for floating measurement the maximum permissible common mode voltage is UCM v 1V and must not be overshot relative to MANA at any differential input The illustration below shows how resistance thermometers Pt100 are con nected to channel 0 and channel 2 in a 2 wire circuit for floating measure ment MANA 1 2 OFF 1 2 3 4 5 6 7 8 ON...

Page 96: ...ng inputs are high ohmic so the voltage drop on the measuring lines is negligible Note If a resistance thermometer Pt100 is used for floating measurement the maximum permissible common mode voltage is UCM v 1V and must not be overshot relative to MANA at any differential input The illustration below shows how resistance thermometers Pt 100 are con nected in a 4 wire circuit for floating measuremen...

Page 97: ...ment the maximum permissible common mode voltage is UCM v 1V and must not be overshot relative to MANA at any differential input The illustration below shows how voltage sensors are connected in a 2 wire circuit for non floating measurement MANA 1 2 OFF 1 2 3 4 5 6 7 8 ON ON 1 2 3 4 5 6 7 8 ON ON CH0 COMP CH1 CH2 CH3 CH4 CH5 CH6 CH7 U U S3 S2 S4 Shield Figure 4 18 Connection to ET 200C AI 4 8 12 B...

Page 98: ...aided shield flush with the outer edge of the sleeve 7 Pull the ends of the signal cables though the glands with the foil and cut off the foil 8 Strip the ends of the signal lines and crimp the conductors with wire ferrules 9 Connect the lines to the corresponding terminals 10 Pull the lines taut and tighten the gland 11 Repeat steps 2 through 10 with other signal lines or close the module using a...

Page 99: ...44 0HF00 0KB0 Channel Terminal Assignment CH0 1 Measuring line 2 Measuring line CH1 3 Measuring line 4 Measuring line CH2 5 Measuring line 6 Measuring line CH3 7 Measuring line 8 Measuring line 9 Analog ground MANA 10 Analog ground MANA Seal all unused inputs with the screw caps supplied module is supplied with all inputs sealed Terminal Assignment Sealing of Unused Inputs Mechanical and Electrica...

Page 100: ...H2 CH3 MANA S1 S5 A V A V A V A V Figure 4 20 Arrangement of Screw Terminals and DIL Switches in ET 200C AI 4 12 Bit Table 4 14 DIL Switch Blocks in ET 200C AI 4 12 Bit DIL switch block Function Described in S1 Manually set the station number Section 4 4 1 S5 Select voltage or current measurement Section 4 4 3 Select floating non floating measurement Arrangement of Screw Terminals and DIL Switches...

Page 101: ...sensor is used for floating measurement the maximum permissible common mode voltage is UCM v 1 V and must not be overshot relative to MANA at any differential input The illustration below shows how voltage sensors are connected in a 2 wire circuit for floating measurement Shield U U 1 2 3 4 5 6 7 8 ON ON S5 CH0 CH1 CH2 CH3 MANA Figure 4 21 Connection to ET 200C AI 4 12 Bit of Voltage Sensors in 2 ...

Page 102: ... mea surement is floating or non floating see Section 4 4 1 Note If a current sensor is used for floating measurement the maximum permissible common mode voltage is UCM v 1 V and must not be overshot relative to MANA at any differential input The illustration below shows how current sensors are connected in a 2 wire circuit for floating measurement mA 1 2 3 4 5 6 7 8 ON ON mA CH0 CH1 CH2 CH3 MANA ...

Page 103: ...braided shield flush with the outer edge of the sleeve 7 Pull the ends of the signal cables though the glands with the foil and cut off the foil 8 Strip the ends of the signal lines and crimp the conductors with wire ferrules 9 Connect the lines to the corresponding terminals 10 Pull the lines taut and tighten the gland 11 Repeat steps 2 through 10 with other signal lines or close the module using...

Page 104: ... 7 Analog output Voltage Analog output Current or Voltage 8 Analog output Voltage Analog output Current or Voltage 9 Sensor line S not used 10 Sensor line S not used CH2 11 Analog output Voltage Analog output Current or Voltage 12 Analog output Voltage Analog output Current or Voltage 13 Sensor line S not used 14 Sensor line S not used CH3 15 Analog output Voltage Analog output Current or Voltage ...

Page 105: ...s in ET 200C AO 4 12 Bit Table 4 16 DIL Switch Blocks in ET 200C AO 4 12 Bit DIL switch block Function Described S1 Manually set the station number Section 4 4 1 S2 Select 2 wire or 4 wire con nection Section 4 4 4 You have two options for connecting loads to the ET 200C AO 4 12 Bit Connect load in 4 wire circuit Connect load in 2 wire circuit Arrangement of Screw Terminals and DIL Switches Connec...

Page 106: ...ssible to correct voltage drops of up to 3 V per line It is important to ensure that the sensor lines are connected directly to the load The illustration below shows how to connect loads in a 4 wire circuit for voltage output 1 2 3 4 5 6 7 8 ON ON S2 CH0 CH1 CH2 CH3 RL RL S S S S Shield Figure 4 25 Connection of Loads to ET 200C AO 4 12 Bit 4 Wire Circuit for Voltage Output Load in 4 Wire Circuit ...

Page 107: ... a precise output voltage in the 2 wire circuit This creates a low ohmic link between the sensor input and the associated output thus preventing a circuit related error due to the output voltage feedback The illustration below shows how to connect loads in a 2 wire circuit for voltage output 1 2 3 4 5 6 7 8 ON ON CH0 CH1 CH2 CH3 RL RL S2 Shield Figure 4 26 Connection of Loads to ET 200C AO 4 12 Bi...

Page 108: ...inued The illustration below shows how to connect loads in a 2 wire circuit for cur rent output 1 2 3 4 5 6 7 8 ON ON CH0 CH1 CH2 CH3 RL RL S2 Shield Figure 4 27 Connection of Loads to ET 200C AO 4 12 Bit 2 Wire Circuit for Current Output Load in 2 Wire Circuit Current Output Mechanical and Electrical Installation ...

Page 109: ... you will require 6 pin circular socket for incoming load voltage or 6 pin circular connector for outgoing load voltage only with ET 200C DO 8 DC 24V 0 5A Flexible 3 core Cu cables for ET 200C DO 8 DC 24V 0 5A with a minimum core cross sectional area of 0 75 mm2 AWG 18 and a diameter of between 6 and 10 mm for ET 200C DO 8 DC 24V 2A and ET 200C DI 16 DO 16 DC 24V 2A with a minimum core cross secti...

Page 110: ...3 core Cu cables with a minimum core cross section of 0 75 mm2 AWG 18 and a diameter of 6 to 10 mm Connect the circular socket in accordance with the following pin assignment Table 4 18 Pin Assignment of the External Power Supply Pin Power supply 1 PE 2 P 24 V 3 M 24 V 4 free 5 free 6 free Connections which are not required must be sealed using the enclosed metal caps Introduction Connecting Exter...

Page 111: ...number of the ET 200C module optional the measurement type for the input modules and the wiring configuration 2 wire or 4 wire for the output module Every analog module has a DIL switch block for setting the station number block S1 The other DIL switch blocks are module specific Note The settings performed electronically with COM ET 200 Windows as described in the manual ET 200 Distributed I O Sys...

Page 112: ...igure 4 28 64 32 16 8 4 2 1 S1 M DIL Switch Block S1 in Default Position As Delivered E 1 0 Electronic Param eterization via Bus Manual Setting by Means of DIL Switches Figure 4 28 DIL Switch Block in Default Position As Delivered If you leave the switches in their default positions all you have to do is set the station number when parameterizing via the bus see Chapter 5 If you set the single DIL...

Page 113: ... COM ET 200 Example You want to assign station number 6 to an analog module 6 2 4 DIL switch block S1 set to station number 6 64 32 16 8 4 2 1 S1 M E 1 0 Figure 4 29 Example of How to Set a Station Number at DIL Switch Block S1 To set a station number by means of the DIL switches in DIL switch block S1 proceed as follows 1 Open the analog module 2 On the lower printed circuit board set the single ...

Page 114: ... measurement type for the analog module ET 200C AI 4 8 12 Bit by means of the DIL switches are as follows High precision measurement with Pt 100 resistance thermometers is ensured only if you use 4 wire connection The usual setting for thermocouple measurements is internal with non floating compensation Use external compensation only if the reference point has to be outside the analog module ET 20...

Page 115: ...nnection for Pt 100 4 OFF Channels CH 2 and 3 measuring line nega tive connected to constant current line nega tive 2 wire connection for Pt 100 5 OFF Channels CH 4 and 5 measuring line positive connected to constant current line positive 2 wire connection for Pt 100 6 OFF Channels CH 4 and 5 measuring line nega tive connected to constant current line nega tive 2 wire connection for Pt 100 7 OFF C...

Page 116: ...ck S2 is ON DIL switch block S3 on the AI 4 8 module enables you to select external in ternal and floating non floating compensation for thermocouples Set DIL switch block S3 as follows Table 4 21 DIL Switches in DIL Switch Block S3 DIL switch block S3 Default Switch ON 1 ON Negative input connected to ground non floating compensation 2 ON External compensation inputs short circuited necessary for...

Page 117: ...nd non floating measurement 4 OFF Channel CH 3 measuring line negative connected to analog ground non floating measurement 5 OFF Channel CH 4 measuring line negative connected to analog ground non floating measurement 6 OFF Channel CH 5 measuring line negative connected to analog ground non floating measurement 7 OFF Channel CH 6 measuring line negative connected to analog ground non floating meas...

Page 118: ...t a shunt resistor 125 ohms parallel to the input is activated Caution Make sure that this shunt resistor is not in circuit for voltage measurements as otherwise the sensor would be overloaded The rules for setting the measurement type for the analog module ET 200C AI 4 12 bit by means of the DIL switches are as follows The shunt resistor parallel to the input of the channel in question must be ac...

Page 119: ...Channel CH 1 shunt resistor activated voltage measurement 4 OFF Channel CH 1 measuring line negative connected to analog ground floating measurement 5 OFF Channel CH 2 shunt resistor activated voltage measurement 6 OFF Channel CH 2 measuring line negative connected to analog ground floating measurement 7 OFF Channel CH 3 shunt resistor activated voltage measurement 8 OFF Channel CH 3 measuring lin...

Page 120: ...for 2 wire connection mode as otherwise an error of 2 would occur at the output The rules for setting the connection mode for the analog module ET 200C AO 4 12 Bit by means of the DIL switches are as follows The analog module ET 200C AO 4 12 Bit is intended primarily for high end control functions with 4 wire configurations You should use the 2 wire option only in exceptional cases If you have to ...

Page 121: ...2 wire connection 3 OFF Channel CH 1 output line positive connected to sensor line positive 2 wire connection 4 OFF Channel CH 1 output line negative connected to sensor line negative 2 wire connection 5 OFF Channel CH 2 output line positive connected to sensor line positive 2 wire connection 6 OFF Channel CH 2 output line negative connected to sensor line negative 2 wire connection 7 OFF Channel ...

Page 122: ...4 54 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Mechanical and Electrical Installation ...

Page 123: ...he address area and the station type of the station see Section 5 1 2 The addresses of the inputs and outputs see Section 5 1 3 and The inputs and outputs that will generate a diagnostics signal in the event of a fault see Section 5 1 4 You can skip this chapter if you use ET 200C with COM ET 200 Windows COM ET 200 Windows supports standardized simple configuration and parameterization for all ET ...

Page 124: ...00 0XB0 6ES7 143 0BL10 0XB0 SI8013TD 200 The type files of the ET 200C modules are part of COM ET 200 as of Ver sion 4 1 If you are currently working with COM ET 200 V4 0 you can ob tain Version 4 1 of COM ET 200 free of charge from your contact at Siemens Alternatively you can download the appropriate type file from the interface centre via modem under the following mailbox number Tel 49 911 73 7...

Page 125: ...sary correct the station number that appears on the screen Entry options Possible station numbers for ET 200C 3 to 124 Help Press F7 HELP A window appears with all previously assigned station numbers and station types You can select a station and display its configuration If no station number has been assigned the message No stations configured appears 3 Confirm the entry with F6 ENTER If the stat...

Page 126: ...d In our example the station is being assigned the station number 3 ENTER HELP EXIT F2 F3 F4 F5 F6 F7 F8 F1 Station number 3 Program file selected TEST ET 200 SIMATIC S5 COM ET 200 CONFIGURING Figure 5 1 CONFIGURING Screen 1 Example Address Assignment and Parameterization with COM ET 200 ...

Page 127: ... you entered N for the ET 200 system parameter Dual port RAM ADDR you must select one of the permissible areas for linear addressing P or Q Note The ET 200 Distributed I O System manual describes the basic principles of address assignment for ET 200 linear addressing or dual port RAM addressing 2 Enter the corresponding name for your ET 200C station in the Station type entry field see Table 5 1 He...

Page 128: ...BF00 0XB0 is to be con figured The inputs of the module are addressed linearly in the P peripheral area ENTER HELP EXIT F2 F3 F4 F5 F6 F7 F8 F1 Station number 3 Program file selected TEST ET 200 SIMATIC S5 COM ET 200 CONFIGURING Area P Station type C 8DI DP Figure 5 2 CONFIGURING Screen 2 Example Address Assignment and Parameterization with COM ET 200 ...

Page 129: ...s of the inputs outputs of the ET 200C station are defined as follows 1 If required enter in the Next free address entry fields another free address that you wish to use for the inputs or outputs of the ET 200C station Entry options For linear addressing 0 to 255 For Q dual port RAM addressing 0 to 254 For P dual port RAM addressing 192 to 254 2 Enter the address identifiers of the ET 200C in the ...

Page 130: ...r address identifier The following address identifiers are used for ET 200C Table 5 2 Address Identifiers for ET 200C DP Standard Module Order number Address identifier Consis tency Address range Address area Slot 0 Slot 1 tency range byte area ET 200C DI 8 DC 24V 6ES7 141 0BF00 0XB0 000 016 Byte 1 digital ET 200C DO 8 DC 24V 0 5A 6ES7 142 0BF00 0XB0 032 000 Byte 1 digital ET 200C DO 8 DC 24V 2A 6...

Page 131: ...tion Module address Shift F6 DP slave parameterization frame I Q 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Station number 5 Program file selected TEST ET 200 SIMATIC S5 COM ET 200 CONFIGURING Area P Station type C 16DI 16DO 2A DP Station name Press control Next available address DI 2 DQ 2 AI 0 AQ 0 033 STATION DELETE STATION NEW STATION ADRESS ASSIGN ENT...

Page 132: ...ll then appear DP IDENTIFIER I Q Length Format Consistency Help I Q I Input Q Output X Input Output Length 1 16 Format B Byte W Word Consistency 0 Byte Word 1 Total depending on format 3 Make the appropriate entries in the 4 fields with the aid of the legend Example DP IDENTIFIER for the 16 inputs of the ET 200C 16DI 16DO slot 1 DP IDENTIFIER I Q I Length 2 Format B Consistency 0 Help I Q I Input ...

Page 133: ... NAK yes in COM ET 200 The CPU is reset to RUN after a STOP RUN transition although 8DI 1 and 8DI 2 or 8DO 1 and 8DO 2 are not entered in the process image 8DO 2 behaves in the same way as in case 1 Assumption failure occurs in 8DI 2 Since the above mentioned CPUs read the process image one word at a time they recognize that a failure has occurred in 8DI 2 The CPU is set to STOP with NAK if NAK ye...

Page 134: ...of the ET 200C 1 Press shift F6 DP slave parameterization frame The DP slave parameterization frame window for the ET 200C station will then appear 5 bytes of the parameterization frame are preassigned with 00H the first time this is selected DP SLAVE PARAMETERIZATION FRAME Byte entry in format KH 0 00 00 00 00 00 10 20 2 Then enter the diagnostic behavior of the ET 200C station in the format KH N...

Page 135: ... the ET 200C modules DI 8 DC 24V DO 8 DC 24V 0 5A and DO 8 DC 24V 2A is defined in byte 1 of the parameterization frame Structure of the Parameterization Frame Byte 1 7 6 5 4 3 2 1 0 Byte 1 1 Diagnostics for input output 0 switched off 1 Diagnostics for input output 1 switched off 1 Diagnostics for input output 2 switched off 1 Diagnostics for input output 3 switched off 1 Diagnostics for input ou...

Page 136: ...5 14 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Address Assignment and Parameterization with COM ET 200 ...

Page 137: ...T 200 V4 x You will learn in this chapter how to Connect the programmer and the rules you need to observe to do this see Section 6 1 Select the station and transfer the configuration data to the station see Section 6 2 Test the station see Section 6 3 You can skip this chapter if you use ET 200C with COM ET 200 Windows COM ET 200 Windows supports standardized simple startup for all ET 200 slaves I...

Page 138: ...s to connect the programmer to the ET 200C module An adapter cable see Section 3 13 and The programmer connecting cable Order No 6XV1 830 1AH Please observe the following rules when connecting the programmer to ET 200C modules The programmer is plugged into the bus connection of the digital modules via the adapter cable and the programmer connecting cable The digital module is run over an external...

Page 139: ...nnecting cable Caution If you start up an ET 200C station while the bus is in operation using the programmer connected to the bus you must note the following The station cannot be controlled by the master station while the programmer has access to the station 8DO 8DO 2A 8DI SV External Power Supply SINEC L2 DP PS Adapter Cable Programmer Connecting Cable External Load Voltage Supply External Load ...

Page 140: ...T 200 V 4x software package press F5 in the FUNCTION SELECTION form 3 Enter the station number of the ET 200C station 4 Confirm the entry with F6 ENTER Result COM ET 200 V4 x now tries to establish a connection to the station After the connection has been established the station is assigned the con figuration data The station should now be coded with the current station number The station number c...

Page 141: ...ion is to be assigned the station number 3 SYSTEM START UP TEST STATION SELECTED Program file selected TEST ET 200 SIMATIC S5 COM ET 200 ENTER HELP EXIT F2 F3 F4 F5 F6 F7 F8 F1 Station number 3 Figure 6 3 SYSTEM START UP TEST STATION SELECTED Screen Example Startup and Test with COM ET 200 ...

Page 142: ...d with a The slot will be deselected if F5 SELECT is pressed again 3 Confirm the selection with F6 ENTER The SYSTEM START UP TEST STATUS CONTROL screen for the se lected station appears with the following contents Diagnostics messages for the entire station appear in plain text in the output field Station status The digital inputs outputs are displayed in KH format in two tables Note on changing t...

Page 143: ...F5 F6 F7 F8 F1 Station number 6 Program file selected TEST ET 200 SIMATIC S5 COM ET 200 START UP TEST STATUS CONTROL Station type C 8DO DP Station name PRESS Station status Force Outputs KH 13 Status Inputs Status of outputs is retained Slot 0 Identifier 032 Figure 6 4 SYSTEM START UP TEST STATUS CONTROL Screen Example Startup and Test with COM ET 200 ...

Page 144: ...tion key assignments on the screen change 3 Press F6 STOP to freeze the screen i e to stop the output fields in the line Inputs from being updated Outputs are tested as follows 1 Enter the output signals in the line Outputs 2 Press F6 ENTER Result The output data is transferred cyclically to the selected module The function key assignments on the screen change 3 Press F6 STOP to freeze the screen ...

Page 145: ...C dis tributed I O station This chapter describes fault detection via LEDs on the front panel of the module see Section 7 1 with COM ET 200 V4 x and the programmer see Section 7 2 via STEP 5 see Section 7 3 Fault detection via STEP 5 station diagnostics is included here for situa tions where the diagnostics master of the ET 200C is an IM 308 B In this Chapter 7 ...

Page 146: ...apsed without the ET 200C DI 8 DC 24V being addressed because the connection to the IM 308 B is lost or IM 308 B is set to STOP or The ET 200C DI 8 DC 24V was not parameterized during startup or a restart DIA Lit red Group diagnostics of the inputs Wire breakage short circuit overload at the sensor supply 0 1 2 3 4 5 6 7 Lit green Input active Status LEDs of the inputs Flashing red Short circuit a...

Page 147: ... DO 8 DC 24V 0 5A or ET 200C DO 8 DC 24V 2A was not parameterized during startup or a restart DIA Lit red Group diagnostics of the outputs Wire break short circuit1 overload or undervoltage at the outputs 0 1 2 3 4 5 6 7 Lit green Output active Status LEDs of the outputs Flashes red Short circuit at the output Lit red Wire break at the output 4 LEDs lit red 2 Internal blowing of fuse3 8 LEDs lit r...

Page 148: ...connection to the IM 308 B is lost or IM 308 B is in STOP mode or ET 200C DI 16 DO 16 DC 24V 2A was not parameterized during startup or a restart DIA Lit red Group diagnostics for groups of 4 inputs or 4 out puts Inputs wire break short circuit1 overload of the sensor supply Outputs wire break short circuit2 overload or undervoltage at the outputs 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Lit green In...

Page 149: ...on for which diagnostics data is available are listed under Station number in the screen 2 Press F1 INDIVIDUAL DIAGNOSTICS Result COM ET 200 asks for a Station number 3 In the Station number entry field enter the number of the faulty station that you want to investigate further 4 Press F6 ENTER to be able to evaluate the diagnostics messages of this station After F6 ENTER is pressed COM ET 200 bra...

Page 150: ...tics have a length of 7 bytes incl header F2 F3 F4 F5 F6 F7 F8 HELP EXIT F1 Program file selected TEST ET 200 SIMATIC S5 COM ET 200 INDIVIDUAL DIAGNOSTICS Station number 3 Area P Station type C 8DI DP Station name Press control Active Device related diagnostics KH 00 00 BE 00 00 00 Identifier specific diagnostics Slot Station status Device related diagnostics Byte 0 Byte 5 Figure 7 1 INDIVIDUAL DI...

Page 151: ...ine which stations have diagnostics data pending Diagnostics for Parameter assignment and adressibility Enables you to determine which stations have been parameterized and which stations can be contacted Station diagnostics Provides messages on the status of the slave station and locates the defective input or output The Diagnostics Overview and Parameter Assignment and Addressabil ity each requir...

Page 152: ...dress 1 Table 7 5 Structure of the Station Diagnostics for ET 200C Code Diagnostics address Diagnostics address 1 0 Station status 1 Station status 2 1 Station status 3 Master address 2 Manufacturer ID 3 Header device related diagnostics Device related diagnostics byte 0 16DI 16DO group diagnostics 8DI 8DO 8DO 2A free 4 Reserved byte 1 Device related diagnostics byte 2 16DI 16DO free 8DI 8DO 8DO 2...

Page 153: ...e addressing you must select the dual port RAM page A typical STEP 5 station diagnostics listing is given below STL Explanation L KY basic dual port RAM page number T PY 255 L KY station number code T PW 252 L PW 252 L KH hex code no fault F BEB SFB FBx Page selection Basic dual port RAM page number nx16 n 0 1 Load diagnostics station number 3 124 code see Table 7 5 and transfer to the diagnostics...

Page 154: ...2 L KH 0000 F BEB SPB FBx Store the value 127 code for diagnostics Overview request in the diagnostics address byte store the code for the numbers of the stations from which the diagnostics Overview is to be requested in the diagnostics address 1 byte the diagnostics Overview ranges from station n 16 station n 16 15 Load diagnostics word No station with faults Evaluate fault in FBx Introduction Re...

Page 155: ...gn address 1 1 Station n 16 15 has sent diagnostics message 1 Station n 16 9 has sent diagnostics message 1 Station n 16 has sent diagnostics message 1 Station n 16 1 has sent diagnostics message 1 Station n 16 7 has sent diagnostics message n 0 1 2 7 1 Station n 16 8 has sent diagnostics message Figure 7 2 Structure of the Diagnostics Word after Requesting the Diagnostics Overview Structure Diagn...

Page 156: ...126 code for diagnostics for Parameter assignment and addressability request in the diagnostics address byte store the code for the numbers of the stations from which the diagnostics Parameter assignment and addressability are to be requested in the diagnostics address 1 byte the diagnostics range from station n 16 station n 16 15 Load diagnostics word all stations n 16 n 16 15 parameterized with ...

Page 157: ...d addressable n 0 1 2 7 Figure 7 3 Structure of the Diagnostics Word after Requesting the Diagnostics for Parameter Assignment and Addressability The following diagnostics messages can be formed by combining the diagno stics Overview and diagnostics Parameter assignment and addressability Table 7 6 Combination of the Diagnostics Overview and Diagnostics for Parameter Assignment and Addressability ...

Page 158: ...am is programmed as follows STL Explanation L KY n 0 T PW 252 L PW 252 L KH 000C F BEB SPB FBx Store the number of the slave station n slave station of which the station status is to be requested in the Diagnostics address byte store the code for Station status 1 and station status 2 code 0 in the Diagnostics address 1 byte Load diagnostics word Monitoring is activated No fault Evaluate fault in F...

Page 159: ...e station is in SYNC mode 1 Slave station is in FREEZE mode 1 Monitoring is activated 1 Bit is always 1 1 An implausible response has been received from the addressed slave station 1 Parameterizing error 1 Slave station has been parameterized by another master 1 Slave station cannot continue to operate as long as fault has not been eliminated 1 Slave station must be parameterized again Indication ...

Page 160: ...tation number of the master 1 No fault Evaluate fault in FBx Following request of station status 3 and the master address code 1 the diagnostics word has the following structure Diagnostics word Station status 3 and master address code 1 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Irrelevant Address of the master which parameterized the slave station Diagnostics address Station status 3 Diagnostics address 1 ...

Page 161: ...uest of the manufacturer identification code 2 the diagnos tics word has the following structure Diagnostics Word Manufacturer Identification Code 2 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 x x x x x x x x x x x x x x x x 8010H ET 200C DI 8 DC 24V 6ES7 141 0BF00 0XB0 8011H ET 200C DO 8 DC 24V 0 5A 6ES7 142 0BF00 0XB0 8012H ET 200C DO 8 DC 24V 2A 6ES7 142 0BF10 0XB0 8013H ET 200C DI 16 DO 16 DC 24V 2A 6ES7 ...

Page 162: ...ws STL Explanation L KY n 3 T PW 252 L PW 252 L KH 0700 F BEB SPB FBx Store the number of the slave station n station number for which the device related diagnostics are to be requested in the Diagnostics address byte store the code for header or device related diagnostics group diagnostics for 16 DI 16 DO code 3 in the Diagnostics address 1 byte Load diagnostics word Fault Evaluate fault in FBx I...

Page 163: ...ess 1 Device related diagnostics Code for I O diagnos tics Length of the individual diagnostics incl header length 7 bytes 0 0 0 0 0 1 1 1 Output 0 3 defective Output 4 7 defective Output 8 11 defective Output 12 15 defective Input 0 3 defective Input 4 7 defective Input 8 11 defective Input 12 15 defective Figure 7 7 Structure of the Diagnostics Word after Requesting the Header and the Device rel...

Page 164: ...t in FBx The structure of the diagnostics word is as follows after requesting the de vice related diagnostics of ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5A and ET 200C DO 8 DC 24V 2A code 4 Diagnostics Word Device Related Diagnostics Code 4 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Diagnostics address Diagnostics address 1 Device related diagnostics Reserved 1 Input output 7 defective 1 Input output 0 def...

Page 165: ... the ET 200C dis tributed I O station This chapter describes fault detection via LEDs on the front panel of the module see Section 8 1 via STEP 5 see Section 8 2 Fault detection with STEP 5 station diagnostics is included here for situa tions where the diagnostics master of the ET 200C is an IM 308 C and an analog module is connected In this Chapter 8 ...

Page 166: ...apsed without the ET 200C DI 8 DC 24V being addressed because the connection to the IM 308 B is lost or IM 308 B is set to STOP or The ET 200C DI 8 DC 24V was not parameterized during startup or a restart DIA Lit red Group diagnostics of the inputs Wire breakage short circuit overload at the sensor supply 0 1 2 3 4 5 6 7 Lit green Input active Status LEDs of the inputs Flashing red Short circuit a...

Page 167: ... DO 8 DC 24V 0 5A or ET 200C DO 8 DC 24V 2A was not parameterized during startup or a restart DIA Lit red Group diagnostics of the outputs Wire break short circuit1 overload or undervoltage at the outputs 0 1 2 3 4 5 6 7 Lit green Output active Status LEDs of the outputs Flashes red Short circuit at the output Lit red Wire break at the output 4 LEDs lit red 2 Internal blowing of fuse3 8 LEDs lit r...

Page 168: ...connection to the IM 308 B is lost or IM 308 B is in STOP mode or ET 200C DI 16 DO 16 DC 24V 2A was not parameterized during startup or a restart DIA Lit red Group diagnostics for groups of 4 inputs or 4 out puts Inputs wire break short circuit1 overload of the sensor supply Outputs wire break short circuit2 overload or undervoltage at the outputs 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Lit green In...

Page 169: ...interruption or memory module was reimported with COM ET 200 Windows V1 01 DIA Flashes red Hardware fault if BF is also lit2 Lit red Fault at inputs outputs of the analog modules Configuration parameterization error 4 8 AI 4AI 4AO Common mode error 4 8 AI Sh i i d 4 8 AI 4 AO Short circuit to ground 4 8 AI 4 AO Wire breakage 4 8 AI 4 AI 4 AO Measuring range undershot 4 8 AI 4 AI Measuring range ov...

Page 170: ...ding Registers all slaves with which data trans fer has taken place within a certain time window Provides information on the operating mode of the DP master Station diagnostics Provides information on status of the slave and outputs diagnostics for channel groups modules with diagnostics capability only Master diagnostics with IM 308 C is dependent on the station type of the slaves It is described...

Page 171: ... DP standard Diagnostics byte 2 Station status 3 PROFIBUS DP standard Diagnostics byte 3 Master station number PROFIBUS DP standard Diagnostics byte 4 Manufacturer identification high PROFIBUS DP standard Diagnostics byte 5 Manufacturer identification low PROFIBUS DP standard Diagnostics byte 6 Header device related diagnostics Diagnostics byte 7 Device related diagnostics 16 DI 16DO group diagnos...

Page 172: ...ntification related diagnostics Diagnostics byte 7 Module fault vector Diagnostics byte 8 Header device related diagnostics Diagnostics byte 9 S7 header S7 alarm limit value alarm 02H diagnostics alarm 01H Diagnostics byte 10 Slot number Diagnostics byte 11 Reserved Diagnostics alarm Limit value alarm Diagnostics byte 12 System specific diagnostics Limit value overshoot Diagnostics byte 13 System ...

Page 173: ...iagnostics byte 7 Module fault vector Diagnostics byte 8 Header device related diagnostics Diagnostics byte 9 S7 header S7 alarm limit value alarm 02H diagnostics alarm 01H Diagnostics byte 10 Slot number Diagnostics byte 11 Reserved Diagnostics alarm Limit value alarm Diagnostics byte 12 System specific diagnostics Limit value overshoot Diagnostics byte 13 System specific diagnostics Limit value ...

Page 174: ...FIBUS DP standard Diagnostics byte 6 Header identification related diagnostics Diagnostics byte 7 Module fault vector Diagnostics byte 8 Header device related diagnostics Diagnostics byte 9 S7 header S7 alarm diagnostics alarm 01H Diagnostics byte 10 Slot number Diagnostics byte 11 Reserved Diagnostics alarm Diagnostics byte 12 System specific diagnostics Diagnostics byte 13 System specific diagno...

Page 175: ...4AO Length 4 Bytes FB IM308C Maximum Length 20 Bytes 1 Slave Diagnostics Station Diagnostics 1 Figure 8 1 Diagram Illustrating How Station Diagnostics is Requested with FB IM308C FB IM308C and its use relate to general access to diagnostics data of the IM 308 C and are described in detail in the manual ET 200 Distributed I O System Order No 6ES5 998 3ES12 The example below illustrates how to call ...

Page 176: ...STAD KF 0 LENG KF 1 ERR MW 134 L DR 4 L KB 2 F SPB FB 60 Name LIMITA48 L DR 4 L KB 1 F SPB FB 61 Name DIA AL48 BE Call the FB IM308C DP window F800 Number of IM 308 C 0 station number of the slave 3 SD read slave diagnostics irrelevant Memory area 0 block DB 10 No of first data word DW0 Bytes to be transferred 1 joker length fault word MW 134 Check Limit value alarm Store limit value alarm Check D...

Page 177: ...n Name DIA AL48 A DB 10 L DW 6 T DW 62 L DW 7 T DW 63 L DW 8 T DW 64 L DW 9 T DW 65 L DW 10 T DW 66 L DW 11 T DW 67 L DW 12 T DW 68 L DW 13 T DW 69 BE Move information for diagnostics alarm to prevent overwriting by subsequent diagnostics alarms Fault Diagnostics with the IM 308 C ...

Page 178: ...ics of an ET 200C module has been requested by the CPU and is stored in a data block DB starting at data word DW n The table below shows the position of the diagnostics data in a data block Table 8 10 Position of the Diagnostics Data in the Data Block Data word DL DR DW n Station status 1 Station status 2 DW n 1 Station status 3 Master station number DW n 2 Manufacturer identification n starting w...

Page 179: ...station is not yet ready for data exchange 1 Configuration data sent by the master to the slave station do not match the configuration of the slave 1 Individual diagnostics selected 1 Requested function is not supported by the slave station 1 Slave station is in SYNC mode 1 Slave station is in FREEZE mode 1 Response monitoring is activated 1 Bit is always 1 1 An implausible response has been recei...

Page 180: ... diagnostics word for station status 3 and master station number in our example DW 1 is as follows Diagnostics Word Station Status 3 and Master Station Number 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Irrelevant Station number of the master which parameterized the slave station DL n 1 Station Status 3 DR n 1 Master Station Number Figure 8 3 Structure of the Diagnostics Word Station Status 3 and Master Stati...

Page 181: ...word for manufacturer identification in our example DW 2 is as follows 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 x x x x x x x x x x x x x x x x DL n 2 DR n 2 Diagnostics Word Manufacturer Identification 8010H ET 200C DI 8 DC 24V 6ES7 141 0BF00 0XB0 8011H ET 200C DO 8 DC 24V 0 5A 6ES7 142 0BF00 0XB0 8012H ET 200C DO 8 DC 24V 2A 6ES7 142 0BF10 0XB0 8013H ET 200C DI 16 DO 16 DC 24V 6ES7 143 0BL00 0XB0 8013H E...

Page 182: ...n a data block DB 10 starting at data word DW 0 The length of this device related diagnostics data is 7 bytes The table below shows the position of the diagnostics data in the data block Table 8 11 Position of Diagnostics Data in the Data Block for ET 200C Data word DL DR DW 0 Station status 1 Station status 2 DW 1 Station status 3 Master station nummer DW 2 Manufacturer identification DW 3 Header...

Page 183: ... and Device related Diagnostics for Digital ET 200C Modules 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 DL n 3 Header DR n 3 Dev rel Diagnostics Bits are always 0 Length of device related diagnostics including header length 7 bytes 0 0 0 0 0 1 1 1 Output 0 3 defective Output 4 7 defective Output 8 11 defective Output 12 15 defective Input 0 3 de fective Input 4 7 de fective Input 8 11 defective Input 12 15 de...

Page 184: ...T 200C DO 8 DC 24V 2A is as follows Diagnostics Word Device related Diagnostics 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 DL n 4 DR n 4 Dev rel Diagnostics Reserved 1 Input output 7 defective 1 Input output 0 defective Figure 8 6 Structure of the Diagnostics Word for Device related Diagnostics for ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5A and ET 200C DO 8 DC 24V 2A Structure Device related Diagnostics fo...

Page 185: ...ter stations number DW n 2 Manufacturer identification DW n 3 Header identification related diagnostics Module fault vector DW n 4 Header device related diagnostics S7 Header Diagnosealarm limit value alarm 02H diagnostics alarm 01H DW n 5 Slotnummer Reserved Diagnostics alarm Limit value alarm Diagnostics alarm Limit value alarm DW n 6 System specific diagnostics Limit value overs hoot System spe...

Page 186: ... header diagnostics alarm limit value alarm 02H diagnostics alarm 01H DW n 5 Slot number Reserved Diagnostics alarm Limit value alarm Diagnostics alarm Limit value alarm DW n 6 System specific diagnostics Limit value overs hoot System specific diagnostics Limit value un dershoot DW n 7 Free Free System specific diagnostics Free DW n 8 Channel type AI 4 8 AI 4 AO 4 Length of diagno stics per channe...

Page 187: ...e related diagnostics S7 Header diagnostics alarm diagnostics alarm 01H DW n 5 Slot number Reserved Diagnostics alarm Diagnostics alarm DW n 6 System specific diagnostics System specific diagnostics DW n 7 Free System specific diagnostics DW n 8 Channel type AI 4 8 AI 4 AO 4 Length of diagnostics per channel DW n 9 Number of channels Channel fault vector one bit per channel DW n 10 to n 11 Channel...

Page 188: ...ag DR n 3 ID Diagnostics 04H for AI 4 8 AI 4 AO 4 0 0 0 0 0 1 0 0 Figure 8 7 Structure of Diagnostics Word for Identification related Diagnostics DW n 3 for Analog ET 200C Modules The STEP 5 program is programmed as follows AWL Explanation A DB 10 L DL 4 L KH 0008 F BEB SPA FBx Call data block here DB 10 Load diagnostics word device re lated diagnostics DW n 4 No fault Evaluate fault in FBx Call o...

Page 189: ...iagnostics alarm 02H limit value alarm 01H diagnostics alarm 0 0 0 0 0 0 1 0 Figure 8 8 Structure of Diagnostics Word Header Device related Diagnostics DW n 4 for Analog ET 200C Modules The structure of diagnostics word DW n 5 for analog ET 200C modules is as follows DL n 5 Dev rel Diag Byte 1 Diagnostics Word Device related Diagnostics for Analog ET 200C Modules 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 0 ...

Page 190: ...Structure of Diagnostics Word Device related Diagnostics Diagnostics Alarm DW n 6 for Analog ET 200C Modules The structure of diagnostics word DW n 7 for analog ET 200C modules is as follows 1 Internal fault EEPROM fault 4AI only DL n 7 Dev rel Diag Diagnostics Word Device related Diagnostics for Analog ET 200C Modules 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 DR n 7 Dev rel Diag 0 0 0 0 0 0 0 0 0 0 0 0 0 1...

Page 191: ...n 9 Dev rel Diag Diagnostics Word Device related Diagnostics for Analog ET 200C Modules 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 0 0 0 0 1 0 0 0 DR n 9 Dev rel Diag Number of channels 04H 4AI 4AO 08H 4 8AI 1 Channel 0 defective 4 8AI 4AI 4AO 1 Channel 1 defective 4 8AI 4AI 4AO 1 Channel 2 defective 4 8AI 4AI 4AO 1 Channel 3 defective 4 8AI 4AI 4AO 1 Channel 4 defective 4 8AI 1 Channel 5 defective 4 8AI 1 C...

Page 192: ... Measuring range undershoot 4 8AI 4AI 1 Measuring range overshoot 4 8AI 4AI 0 Bit is always 0 1 Wire break feed current monitoring measuring transducer Pt 100 4 8AI 4AO 1 Short circuit to ground 4AO 0 Bit is always 0 1 Common mode error 4 8AI 1 Configuration parameterization error 4 8AI 4AI 4AO Channel specific diagnostics for channel 1 Channel specific diagnostics for channel 0 Figure 8 14 Struct...

Page 193: ...pecific diagnostics for channel 4 1 Wire break feed current monitoring measuring transducer Pt 100 4 8AI 1 Bit is always 0 1 Bit is always 0 0 Bit is always 0 1 Short circuit to ground 4 8AI 0 Bit is always 0 0 Bit is always 0 1 Configuration parameterization error 4 8AI Figure 8 15 Structure of Diagnostics Word Header and Device related Diagnostics Diagnostics Alarm DW n 12 for Analog ET 200C Mod...

Page 194: ...it value overshoot channel 2 4 8AI 4AI 1 Limit value overshoot channel 3 4 8AI 4AI 1 Limit value overshoot channel 4 4 8AI 1 Limit value undershoot channel 5 4 8AI 1 Limit value undershoot channel 4 4 8AI 4AI 1 Limit value undershoot channel 3 4 8AI 4AI 1 Limit value undershoot channel 2 4 8AI 4AI 1 Limit value overshoot channel 5 4 8AI 1 Limit value overshoot channel 6 4 8AI 1 Limit value oversho...

Page 195: ...on of the ET 200 handheld for startup and testing of the ET 200C distributed I O station In this chapter you will learn which connections are possible for the ET 200 handheld and which rules must be observed Startup and testing of the ET 200C with the ET 200 handheld are described in the ET 200 Handheld manual In this Chapter 9 ...

Page 196: ...st be removed from the ET 200C station and the ET 200 handheld is then plugged onto this bus connector Note The ET 200 handheld must always be connected in such a way that the power supply for the digital module is not interrupted The ET 200 handheld must not be plugged onto the programmer connector Connection of the ET 200 handheld automatically disconnects the ET 200C distributed I O station fro...

Page 197: ...d without T connector 8DI 8DI SV PS Adapter Cable External Power Supply SINEC L2 DP conn Figure 9 1 Connection of ET 200 Handheld for Configuration with Power Supply Connector and without T Connector Configuration with external power supply 8DI 8DI External Power Supply SINEC L2 DP External Power Supply Adapter Cable Figure 9 2 Connection of ET 200 Handheld for Configuration with External Power Su...

Page 198: ...V PS External power supply SINEC L2 DP conn Adapter Cable Figure 9 3 Connection of the Handheld to the Unassigned Bus Connection of the ET 200C Station for Configuration with Power Supply Connector and T Connector or Connect the ET 200 handheld to the T connector 8DI 8DI SV PS External power supply SINEC L2 DP conn Adapter Cable Figure 9 4 Connection of the Handheld to the T Connector for Configur...

Page 199: ...Specifications This chapter contains the general technical data The general technical data comprises a list of all ET 200C modules the standards and specified values which are satisfied by all modules of ET 200C and the criteria applied in testing the modules In this Chapter 10 ...

Page 200: ...16 DC 24V 6ES7 143 0BL00 0XB0 16 inputs with circular socket connectors 16 outputs with circular socket connectors ET 200C DI 16 DO 16 DC 24V 6ES7 143 0BL10 0XB0 16 inputs with cable glands and conduit threads 16 outputs with cable glands and conduit threads Analog modules ET 200C AI 4 8 12 Bit 6ES7 144 0KH00 0XB0 8 inputs with cable glands and conduit threads measuring principle integrating ET 20...

Page 201: ...intensity Direction of shock Half sine 30 g peak value 18 ms duration 6 shocks in each of the 3 axes vertical to each other Bump test to IEC 68 2 29 Type of shock Shock intensity Direction of shock Half sine 25 g peak value 6 ms duration 1000 shocks in each of the 3 axes vertical to each other Drop and topple to IEC 68 2 31 Tested with Height of fall 100 mm Electromagnetic Compatibility EMC Noise ...

Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...

Page 203: ...11 1 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules This chapter contains technical details of the digital ET 200C modules In this Chapter 11 ...

Page 204: ...ED for status of inputs 1 This baud rate is only relevant in conjunction with the IM 308 C Supply Voltage for Inputs Sensor Supply and Internal Logic Nominal value L 24 V DC Permissible range incl ripple max 3 6V 20 to 30 V Value at t 0 5 s 35 V Short circuit capability Yes Current consumption Logic Sensor typ 35 mA application specific Short circuit current max 4 A Inputs Number of inputs 8 Conne...

Page 205: ...s parameters for the ET 200C DI 8 DC 24 V Table 11 1 Parameters for Digital Input Module ET 200C DI 8 DC 24 V Byte1 Bit Parameter Explanation Value range 1 0 Enable diagnostics for channel 0 Enable diagnostics messages channel by channel bl disable 1 Enable diagnostics for channel 1 channel by channel enable 2 Enable diagnostics for channel 2 3 Enable diagnostics for channel 3 4 Enable diagnostics...

Page 206: ...0C DI 8 DC 24V 6ES7 141 0BF00 0XB0 Continued Dimension drawing for digital input module ET 200C DI 8 DC 24 V 12 pin socket connector 12 pin socket connector 5 pin circular connector Figure 11 2 Digital Input Module ET 200C DI 8 DC 24 V Dimension Drawing Dimension Drawing Digital Modules ...

Page 207: ...00C DI 8 DC 24V with T connector and plug connectors with pin socket inserts 1 Observe the bending radii of the cable when installing the module Figure 11 3 Digital Input Module ET 200C DI 8 DC 24 V Dimension Drawing with T Connector and Plug Connectors with Pin Socket Inserts Dimension Drawing Digital Modules ...

Page 208: ...UL supply of outputs 1 This baud rate is only relevant in conjunction with the IM 308 C Supply Voltage for Outputs Load Voltage Supply and Internal Logic Nominal value L 24 V DC Permissible range incl ripple max 3 6 V 20 to 30 V Value at t 0 5 s 35 V Short circuit capability Yes Current consumption Logic Load typ 90 mA typ 80 mA Short circuit current max 4 A Outputs Number of outputs 8 Connection ...

Page 209: ... of the digital output module ET 200C DO 8 DC 24V 0 5A L M PE A B SINEC Logic 24 V 5 V L M PE A B L1 M PE L2 DP SINEC L2 DP PE L1 M PE L1 M PE 6 pin connection load voltage 12 pin bus connection Output Figure 11 4 Digital Output Module ET 200C DO 8 DC 24V 0 5A Block Diagram Block Diagram Digital Modules ...

Page 210: ...t Module ET 200C DO 8 DC 24 V 0 5A Byte1 Bit Parameter Explanation Value range 1 0 Enable diagnostics for channel 0 Enable diagnostics messages channel by channel bl disable 1 Enable diagnostics for channel 1 channel by channel enable 2 Enable diagnostics for channel 2 3 Enable diagnostics for channel 3 4 Enable diagnostics for channel 4 5 Enable diagnostics for channel 5 6 Enable diagnostics for ...

Page 211: ...for digital output module ET 200C DO 8 DC 24 V 0 5A 12 pin socket connector 12 pin socket connector 5 pin circular connector 6 pin plug connector 6 pin plug connector Figure 11 5 Digital Output Module ET 200C DO 8 DC 24 V 0 5A Dimension Drawing Dimension Drawing Digital Modules ...

Page 212: ...for the digital output module ET 200C DO 8 DC 24V 0 5A with T connectors and plug connectors with pin socket inserts 1 Observe the bending radii of the cable when installing the module Figure 11 6 Digital Output Module ET 200C DO 8 DC 24 V 0 5A Dimension Drawing with T Connector and Plug Connectors with Pin Socket Inserts Dimension Drawing Digital Modules ...

Page 213: ...le max 3 6V Value at t 0 5 s 24 V DC 20 30 V 35 V Short circuit capability Yes Current consumption S Logic S Load Short circuit current typ 90 mA typ 80 mA max 4 A Outputs Number of outputs 8 Connection via 5 pin circular connector 3 wire connection per channel Electrical isolation between internal logic and outputs Yes 500 V Load voltage supply S Nominal value L1 S Permissible range incl ripple m...

Page 214: ...fied representation of the potentials of the digital output module ET 200C DO 8 DC 24V 2A L M PE A B SINEC Logic 24 V 5 V L M PE A B L1 M PE L2 DP SINEC L2 DP PE L1 M PE L1 M PE 6 pin load connection load voltage 12 pin bus connection Output Figure 11 7 Digital Output Module ET 200C DO 8 DC 24V 2A Block Diagram Block Diagram Digital Modules ...

Page 215: ...Bit Parameter Explanation Value range 1 0 Enable diagnostics for channel 0 Enable diagnostics messages channel by channel bl disable 1 Enable diagnostics for channel 1 channel by channel enable 2 Enable diagnostics for channel 2 3 Enable diagnostics for channel 3 4 Enable diagnostics for channel 4 5 Enable diagnostics for channel 5 6 Enable diagnostics for channel 6 7 Enable diagnostics for channe...

Page 216: ...2A 6ES7 142 0BF10 0XB0 Continued Dimension drawingfor digital output module ET 200C DO 8 DC 24 V 2A 12 pin socket connector 12 pin socket connector 5 pin circular connector 6 pin plug connector Figure 11 8 Digital Output Module ET 200C DO 8 DC 24 V 2A Dimension Drawing Dimension Drawing Digital Modules ...

Page 217: ... DO 8 DC 24V 2A with T connectors and plug connectors with pin socket inserts 1 Observe the bending radii of the cable when installing the module Figure 11 9 Digital Output Module ET 200C DO 8 DC 24 V 2A Dimension Drawing with T Connector and Plug Connectors with Pin Socket Inserts Dimension Drawing Digital Modules ...

Page 218: ...ity Yes Current consumption Logic Load Short circuit current typ 90 mA typ 40 mA max 6 3 A 1 This baud rate is only relevant in conjunction with the IM 308 C 2 If a short circuit occurs in the sensor supply of an input the sensor supply for all of the inputs in the group of 4 will be interrupted Inputs Number of inputs 16 Connection 6ES7 143 0BL00 0XB0 via 5 pin circular connec tor 4 wire connecti...

Page 219: ...0 mA 2 A per channel max 5 W Permissible total current Ambient temperature 25 25 _C 26 40 _C 41 60 _C max 3 5 A per group of 4 max 2 5 A per group of 4 max 1 5 A per group of 4 Residual current for 0 signal max 0 5 mA Wire break recognition No wire break recognition typ I v 1 mA typ I w 20 mA Short circuit diagnostics signal typ 3 5 A per channel Switching frequency S at resistive load S at induct...

Page 220: ...sentation of the potentials of the digital input output module ET 200C DI 16 DO 16 DC 24V 2A L M PE A B SINEC Logic 24 V 5 V L M PE A B M PE L2 DP SINEC L2 DP PE L1 M PE L1 M PE Logic L1 M PE M PE 12 pin bus connection 6 pin load connection voltage Output Q0 Output Q1 Input Figure 11 10 Digital Input Output Module ET 200C DI 16 DO 16 DC 24V 2A Block Diagram Block Diagram Digital Modules ...

Page 221: ...tics parameters for the ET 200C DI 16 DO 16 DC 24 V 2A Table 11 4 Parameters for Digital Input Output Module ET 200C DI 16 DO 16 DC 24 V 2A Byte1 Parameter Explanation Value range 0 Enable group diagnostics for DI 16 DO 16 Enable diagnostics messages for entire module enable disable Default setting in parameterization telegram 1 Byte address in parameterization telegram of slave Parameterization D...

Page 222: ...24V 2A 6ES7 143 0BL00 0XB0 UL2 I 0 I 1 I 2 I 3 I 4 I 5 I 6 I 7 I 0 I 1 I 2 I 3 I 4 I 5 I 6 I 7 ET 200C DI 16 DO 16 RUN BF UL1 UL2 DIA DIA SINEC L2 DP SV UL1 Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 ET 200C DC 24 V 12 pin socket connector 6 pin plug connector 5 pin circular connector Figure 11 11 Digital Input Output Module ET 200C DI 16 DO 16 DC 24 V 2A 6ES7 143 0BL00 0XB0 D...

Page 223: ...I 5 I 6 I 7 I 0 I 1 I 2 I 3 I 4 I 5 I 6 I 7 ET 200C DI 16 DO 16 RUN BF UL1 UL2 DIA DIA SINEC L2 DP SV UL1 Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 ET 200C DC 24 V 12 pin socket connector 6 pin plug connector Conduit thread Figure 11 12 Digital Input Output Module ET 200C DI 16 DO 16 DC 24 V 2A 6ES7 143 0BL10 0XB0 Dimension Drawing Dimension Drawing Digital Modules ...

Page 224: ...2 I 0 I 1 I 2 I 3 I 4 I 5 I 6 I 7 I 0 I 1 I 2 I 3 I 4 I 5 I 6 I 7 ET 200C DI 16 DO 16 RUN BF UL1 UL2 DIA DIA SINEC L2 DP SV UL1 ET 200C DC 24 V Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 1 Observe the bending radii of the cable when installing the module Figure 11 13 Digital Input Output Module ET 200C DI 16 DO 16 DC 24 V 2A 6ES7 143 0BL00 0XB0 Dimension Drawing with T Connect...

Page 225: ...5 I 6 I 7 ET 200C DI 16 DO 16 RUN BF UL1 UL2 DIA DIA SINEC L2 DP SV UL1 ET 200C DC 24 V Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 Q 0 Q 1 Q 2 Q 3 Q 4 Q 5 Q 6 Q 7 1 Observe the bending radii of the cable when installing the module Figure 11 14 Digital Input Output Module ET 200C DI16 DO 16 DC 24 V 2A 6ES7 143 0BL10 0XB0 Dimension Drawing with T Connector and Plug Connectors with Pin Socket Inserts Dimension ...

Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...

Page 227: ...19 02b Analog Modules This chapter contains technical data for the analog modules of ET 200C In addition to the technical data this chapter also describes the measurement types and the measured value presentation of the analog modules In this Chapter 12 ...

Page 228: ...8 voltage inputs or 4 inputs forPT100 or 8 inputs for thermocouples Galvanic isolation between voltage supply and internal logic yes Test voltage 500 V DC Measured value ranges Voltage sensor 80 mV 250 mV 500mV 1000mV Resistance sensor 0 400 W Permissible input voltage for voltage input max 32 V Inputs Continued Characteristic linearization for the following thermocouples Types N K T U J E to IEC ...

Page 229: ... UCM max 1 V S MA to PE or M max 75V DC 60V AC Error message for S Range overshoot yes S Wire break on sensor line yes for Pt 100 80 mV thermocouples types N K T U J L E parameterizable with COM ET 200 Interference voltage suppression for f n f1 1 f1 interference frequency S Common mode interference Upp t2 5 V 70 dB S Series mode interference peak interference nominal value of input range 40 dB Cr...

Page 230: ...V Galvanic isolation Channel activation L M Control logic Figure 12 1 ET200C Analog Input Module AI 4 8 12 Bit Block Diagram Fig 12 2 shows the screw terminals and their assignments in the ET 200C AI 4 8 12 Bit COMP V V V V V V V V CH1 CH2 CH3 CH0 CH0 CH1 CH2 CH3 CH4 CH5 CH6 CH7 Screw terminals labels for resistance thermometer Screw terminals labels for thermocouples and voltage sensors M ANA M A...

Page 231: ...er Explanation Range of values 08 0 Enable diagnostics CH 0 1 Enable diagnostics messages by channel groups bl disable 1 Enable diagnostics CH 2 3 channel groups enable 2 Enable diagnostics CH 4 5 3 Enable diagnostics CH 6 7 09 0 Enable wire breakage message CH 0 1 Enable wire breakage detect by channel groups enable disable 1 Enable wire breakage message CH 2 3 2 Enable wire breakage message CH 4...

Page 232: ...Lower limit value CH 0 Set lower limit value for channel 0 0 32768 32767 23 0 7 Upper limit value CH 2 Set upper limit value for channel 2 0 32768 32767 24 0 7 Lower limit value CH 2 Set lower limit value for channel 2 0 32768 32767 34 2 Measured value presentation Present measured value for master system S5 or S7 S5 S7 Default setting in parameterization telegram 1 Byte address in parameterizatio...

Page 233: ...tion and linearization Measurement type th cpl type T int lin Thermocouple measurement type T with internal compensation and linearization Measurement type th cpl type K int lin Thermocouple measurement type K with internal compensation and linearization Measurement type th cpl type U int lin Thermocouple measurement type U with internal compensation and linearization Measurement type th cpl type ...

Page 234: ...210 29 28 27 26 25 24 23 22 21 20 X F O Bits 0 2 and 15 are without significance for the amount of the measured value These bits are described in detail in Table 12 4 Bits 0 2 and 15 in the bit pattern of the analog input value have the follow ing significance Table 12 4 Description of Bits for ET 200C AI 4 8 12 Bit Bit Significance Signal state Significance of the signal state O Overflow bit 1 Ra...

Page 235: ...rload Overload range 2049 80 04 250 12 500 24 1000 48 0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0 range 2048 80 00 250 0 500 0 1000 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1024 40 00 125 00 250 00 500 00 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 039 0 12 0 24 0 48 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 Nominal range 0 0 00 0 00 0 00 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 range 1 0 039 0 12 0 24 0 48 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 ...

Page 236: ...1700 390 26 850 0 0 1 1 0 1 0 1 0 0 1 0 0 0 0 0 1400 345 13 700 0 0 1 0 1 0 1 1 1 1 0 0 0 0 0 0 1000 280 90 500 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0 600 212 02 300 0 0 0 1 0 0 1 0 1 1 0 0 0 0 0 0 300 157 31 150 0 0 0 0 1 0 0 1 0 1 1 0 0 0 0 0 200 138 50 100 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 0 Nominal range 2 100 39 1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 100 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 40 92 16 20 1 1...

Page 237: ...0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0 500 20 640 500 0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 150 6 137 150 0 0 0 0 0 1 0 0 1 0 1 1 0 0 0 0 Nominal range 100 4 095 100 0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 1 0 039 1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 039 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 100 3 553 100 1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 101 3 584 101 1 1 1 1 1 1 0 0 1 1 0 1 1 0 0 0...

Page 238: ...000 57 942 1000 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0 500 27 388 500 0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 100 5 268 100 0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 1 0 05 1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 Nominal range 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 05 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 100 4 632 100 1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 150 6 499 150 1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0 199 7 868 199 1 1 1 1 1 0 0 1 1 1...

Page 239: ...1 0 0 0 0 0 250 13 75 250 0 0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 100 5 37 100 0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 1 0 05 1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 Nominal range 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 05 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 100 4 75 100 1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 150 6 60 150 1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0 190 7 86 190 1 1 1 1 1 0 1 0 0 0 0 1 0 0 0 0 199 8 12 199 1 1 1 1 1 0 0 1...

Page 240: ...the ET 200C AI 4 8 12 for the measuring ranges 80 mV 250 mV 500 mV and 1000 mV Table 12 11 Digitized Measured Values for ET 200C AI 4 8 12 Bit Measuring Ranges 80 mV 250 mV 500 mV and 1000 mV Measuring range Measuring range Measuring range Measuring range Units range 80 mV range 250 mV range 500 mV range 1 V decimal hexa decimal Range w 94 074 w 293 98 w 587 96 w 1 176 32767 7FFFH Overflow 94 071 ...

Page 241: ... 2430 F82FH F682H Underdrive range v 243 1 32768 8000H Underrun The four tables below show the digitized measured values for thermocouples of types K N J and E Table 12 13 Digitized Measured Values for ET 200C AI 4 8 12 Bit for Type K Thermocouple Temperature range in C Type K Decimal Hexadecimal Range w1623 32767 7FFFH Overflow 1622 1373 16220 13730 3FSCH 35A2H Overload range 1372 270 13720 2700 ...

Page 242: ...range If wiring is incorrect or an error occurs in the sensor in the negative the analog input module reports underrun if F0C5H is undershot and outputs 8000H Table 12 15 Digitized Measured Values for ET 200C AI 4 8 12 Bit for Type J Thermocouple Temperature range in C Type J Decimal Hexadecimal Range w1451 32767 7FFFH Overflow 1450 1201 14500 12010 38A4H 2EEAH Overload range 1200 210 0 12000 2100...

Page 243: ...ge in C Type E Decimal Hexadecimal Range w1201 32767 7FFFH Overflow 1200 1001 12000 10010 2EE0H 271AH Overload range 1000 270 10000 2700 2710H F574H Nominal range v 271 2710 F573H Underdrive range If wiring is incorrect or an error occurs in the sensor in the negative the analog input module reports underrun if F0C5H is undershot and outputs 8000H Analog Modules ...

Page 244: ...ule AI 4 8 12 Bit 6ES7 144 0KH00 0XB0 Continued Dimensional drawing for ET 200C analog input module AI 4 8 12 Bit 12 pin socket connector 12 pin socket connector Conduit thread Figure 12 3 ET 200C Analog Input Module AI 4 8 12 Bit Dimensional Drawing Dimensional Drawing Analog Modules ...

Page 245: ...drawing for ET 200C analog input module AI 4 8 12 Bit with T connector 1 The bending radii of the cable must be taken into account for installation Figure 12 4 ET 200C Analog Input Module AI 4 8 12 Bit Dimensional Drawing with T connector Dimensional Drawing Analog Modules ...

Page 246: ...20 mA 4 20 mA Signal generator connection two wire Input resistance Voltage sensor 1 MW Current sensor 125 W Measured value presentation 12 Bit sign Measuring principle momentary value encryption successive approximation Encryption time 250 ms per input Cycle time of the module approx 2 ms without system reaction time Inputs Continued Permissible potential differential Input to input max 10 V Inpu...

Page 247: ...Control logic CH 0 CH 1 CH 3 CH 2 Galvanic isolation Channel activation 24 V L M Figure 12 5 ET200C Analog Input Module AI 4 12 Bit Block Diagram Fig 12 6 shows the screw terminals and their assignments in the ET 200C AI 4 12 Bit CH0 CH1 CH2 CH3 A V A V A V A V M ANA Figure 12 6 Screw Terminals with Assignments in the ET 200C AI 4 12 Bit Block Diagram Screw Terminals Analog Modules ...

Page 248: ...ups enable 2 Enable diagnostics CH 2 3 Enable diagnostics CH 3 09 6 Enable diagnostics alarm Enable diagnostics alarm of module disable enable 7 Enable limit value alarm Enable limit value alarm of module 17 0 7 Measurement type measuring range CH 0 Set measurement type and measuring range for channel CH 0 Channel not activated Measurement type 1 25 V Measurement type 2 5 V M t t 5 V 18 0 7 Measur...

Page 249: ...meter Bit 25 0 7 Upper limit value CH 2 Set upper limit value for channel CH 2 0 32768 32767 27 0 7 Lower limit value CH 2 Set lower limit value for channel CH 2 0 32768 32767 34 2 Measured value presentation Present measured value for master system S5 or S7 S5 S7 Default setting in parameterization telegram 1 Byte address in parameterization telegram of slave Analog Modules ...

Page 250: ...7 26 25 24 23 22 21 20 X F O Bits 0 2 and 15 are without significance for the amount of the measured value These bits are described in detail in Table 12 19 Bits 0 2 and 15 in the bit pattern of the analog input value have the follow ing significance Table 12 19 Description of bits for ET 200C AI 4 12 Bit Bit Significance Signal state Significance of the signal state O Overflow bit 1 Range oversho...

Page 251: ... 5000 5 0000 10 0000 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2047 1 2494 2 4988 4 9976 9 9951 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0 2046 1 2488 2 4975 4 9951 9 9902 0 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0 1 0 0006 0 0012 0 0024 0 0049 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 Nominal range 0 0 0000 0 0000 0 0000 0 0000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 range 1 0 0006 0 0012 0 0024 0 0049 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 2047 1 2494...

Page 252: ...measured value X F O Range 20 mA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 O l d Overload range 2048 20 0000 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 range 2047 19 9902 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 1 2046 19 9804 0 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0 1 0 00976 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 Nominal range 0 0 0000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 range 1 0 00976 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 2047 19 9902 1 1 0 0 0...

Page 253: ...easured value in mA Digitized measured value1 X F O Range 4 20 mA 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 3009 23 500 1 Overflow 3008 23 462 0 Overload range 0 range 2561 20 008 0 1 0 1 0 0 0 0 0 0 0 0 1 0 0 0 2560 20 000 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 Nominal range 2048 16 000 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 range 512 4 000 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 511 3 992 0 0 0 0 1 1 1 1 1 1 1 1 1 0 0 0 ...

Page 254: ...igitized measured values of the ET 200C AI 4 12 for the measuring ranges 1 25 V 2 5 V 5 V and 10 V Table 12 25 Digitized Measured Values for ET 200C AI 4 12 bit Measuring Ranges 1 25 V 2 5 V 5 V and 10 V Measuring range Measuring range Measuring range Measuring range Units range 1 25 V range 2 5 V range 5 V range 10 V decimal hexa decimal Range w 1 4699 w 2 9398 w 5 8796 w 11 759 32767 7FFFH Overf...

Page 255: ... 200C AI 4 12 Bit Measuring Range 20 mA Measuring range 20 mA Units Range range 20 mA decimal hexadecimal Range w 23 516 32767 7FFFH Overflow 23 515 32511 7EFFH Overload range 20 0007 27649 6C01H 20 000 27648 6C00H 14 998 20736 5100H Nominal range 14 998 20736 AF00H 20 000 27648 9400H 20 0007 27649 93FFH Underdrive range 23 516 32512 8100H v 23 517 32768 8000H Underrun Table of Measured Values Ana...

Page 256: ...AI 4 12 Bit Measuring Ranges 0 to 20 mA and 4 to 20 mA Measuring range f Measuring range f Units Range from 0 to 20 mA from 4 to 20 mA decimal hexadecimal Range w 23 516 w 22 815 32767 7FFFH Overflow 23 515 22 810 32511 7EFFH Overload range 20 0007 20 0005 27649 6C01H 20 000 20 000 27648 6C00H 14 998 16 000 20736 5100H Nominal range Nominal range 0 000 4 000 0 0H 0 0007 3 9995 1 FFFFH Underdrive r...

Page 257: ... 812 6119 02b Dimensional drawing for ET 200C analog input module AI 4 12 Bit 12 pin socket connector 12 pin socket connector Conduit thread Figure 12 7 ET 200C Analog Input Module AI 4 12 Bit Dimensional Drawing Dimensional Drawing Analog Modules ...

Page 258: ...144 0HF00 0XB0 Continued Dimensional drawing for ET 200C analog input module AI 4 12 Bit with T connector 1 The bending radii of the cable must be taken into account for installation Figure 12 8 ET 200C Analog Input Module AI 4 12 Bit Dimensional Drawing with T connector Dimensional Drawing Analog Modules ...

Page 259: ...oltage output max 500 W Capacitive load max 1 mF Inductive load max 1 mH Measured value presentation 12 bit sign Overload range approx 17 5 Conversion time S5 max 2 ms per output Outputs Continued Conversion time S7 max 1 ms per output Settling time for ohmic load 0 15 ms for capacitive load 2 5 ms for inductive load 0 2 ms Permissible potential differential MA to PE or M max 75V DC 60V AC Crossta...

Page 260: ...put module AO 4 12 Bit Internal supply A D SINEC L2 DP 24 V Galvanic isolation L M CH 0 CH 1 CH 2 CH 3 Control logic Figure 12 9 ET 200C Analog Output Module AO 4 12 Bit Block Diagram Fig 12 10 shows the screw terminals and their assignments in the ET 200C AO 4 12 Bit CH1 CH2 CH3 CH0 Figure 12 10 Screw Terminals with Assignments in the ET 200C AO 4 12 Bit Block Diagram Screw Terminals Analog Modul...

Page 261: ... value CH 0 Channel by channel definition of substitute value output on Substitute value l t l 1 Type of substitute value CH 1 of substitute value output on error last value 2 Type of substitute value CH 2 error 3 Type of substitute value CH 3 17 0 7 Output type output range CH 0 Channel by channel selection of output range Output range 10 V O 0 10 V 18 0 7 Output type output range CH 1 output ran...

Page 262: ...le Substitute value last value POWER OFF at controller CPU and DP master CV å SV CV å LV CV å SV CV å LV CPU stopped CV å SV CV å LV CV å SV CV å LV DP master stopped CV å SV CV å LV CV å SV CV å LV Interruption on bus CV å SV CV å LV CV å LV CV å LV Response of 4AO output module to end of interruption in communication Response monitoring active Response monitoring not active Substitute value conf...

Page 263: ...4 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Analog value presentation DT 211 210 29 28 27 26 25 24 23 22 21 20 X X X Bits 0 3 and 15 are without significance for the amount of the measured value These bits are described in detail in Table 12 31 Bits 0 2 and 15 in the bit pattern of the analog input value have the follow ing significance Table 12 31 Description of bits for ET 200C AO 4 12 Bit Bit Significanc...

Page 264: ...0 2 10 0098 5 004 10 0098 0 1 0 0 0 0 0 0 0 0 0 1 0 range 1024 20 0 20 0 20 0 10 00 5 0 10 00 0 1 0 0 0 0 0 0 0 0 0 0 0 1023 19 98 19 98 19 98 9 99 4 995 9 990 0 0 1 1 1 1 1 1 1 1 1 1 1 512 10 0 12 0 10 0 5 00 3 5 000 0 0 1 0 0 0 0 0 0 0 0 0 0 256 5 0 8 00 5 0 2 50 2 2 500 0 0 0 1 0 0 0 0 0 0 0 0 0 1 0 0195 4 015 0 02 0 0098 1 00375 0 0098 0 0 0 0 0 0 0 0 0 0 0 0 1 Nom range 0 0 0 4 0 0 0 0 0 1 0 ...

Page 265: ...0C AO 4 12 Bit Table 12 33 Presentation of an Analog Input Value as Bit Pattern for SIMATIC S7 with ET 200C AO 4 12 Bit High byte Low byte Bit number 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Analog value presentation DT 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 Bit 15 is without significance for the amount of the measured value It merely represents the sign Analog Value Presentation SIMATIC S...

Page 266: ... Bit Output Ranges 20 mA 0 to 20 mA and 4 to 20 mA Output range Output range Output range Units Range range 20 mA range 0 to 20 mA range 4 to 20 mA decimal hexa decimal 0 0 0 w32512 w7F00H Overflow 23 515 23 515 22 81 32511 7EFFH Overload range 20 0007 20 0007 20 005 27649 6C01H 20 000 20 000 20 000 27648 6C00H 0 0 4 000 0 0H 0 Nominal range 0 6912 E500H Nominal range 0 6913 E4FFH 20 000 27648 940...

Page 267: ...Ranges 0 to 10 V and 10 V Output range 0 to 10 V Output range 10 V Units 0 to 10 V 10 V decimal hexa decimal Range 0 0 w32512 w7F00H Overflow 11 7589 11 7589 32511 7EFFH Overload range 10 0004 10 0004 27649 6C01H 10 0000 10 0000 27648 6C00H 0 0 0 0H 0 Nominal range 6912 E500H Nominal range 6913 E4FFH 10 0000 27648 9400H 10 0004 27649 93FFH Underdrive range 11 7589 32512 8100H 0 v 32513 v80FFH Unde...

Page 268: ...odule AO 4 12 Bit 6ES7 144 0HF00 0XB0 Continued Dimensional drawing for ET 200C analog output module AO 4 12 Bit 12 pin socket connector 12 pin socket connector Conduit thread Figure 12 11 ET 200C Analog Output Module AO 4 12 Bit Dimensional Drawing Dimensional Drawing Analog Modules ...

Page 269: ... drawing for ET 200C analog output module AO 4 12 Bit with T connector 1 The bending radii of the cable must be taken into account for installation Figure 12 12 ET 200C Analog Output Module AO 4 12 Bit Dimensional Drawing with T connector Dimensional Drawing Analog Modules ...

Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...

Page 271: ...n EWA 4NEB 812 6119 02b Other ET 200C Components This chapter contains technical data on the following ET 200C components T connector Power supply connector Programmer connector Cable Terminating resistor Adapter cable In this Chapter 13 ...

Page 272: ...ed I O Station EWA 4NEB 812 6119 02b 13 1 T Connector 6ES5 762 2CT11 Technical Specifications Connections 2 12 pin socket connector 1 12 pin connector Weight approx 160 g Dimensions W H L 46 26 70 mm Other ET 200C Components ...

Page 273: ...rotection No Electrical isolation No Insulation rating to VDE 0160 Internal resistance RI typ 10 mW Connections 2 12 pin socket connector 1 6 pin plug Earthing screw Weight Dimensions W H L approx 500 g 80 57 125 mm Dimension drawing for the power supply connector with plug connectors with pin socket insert 1 1 Observe the bending radii of the cable when installing the connector Figure 13 1 Power ...

Page 274: ...pply Connector 6ES5 762 2CS11 Continued Dimension drawing for power supply connector 6 pin plug connector 12 pin socket connector M4 earth connection 12 pin socket connector Figure 13 2 Power Supply Connector Dimension Drawing Dimension Drawing Other ET 200C Components ...

Page 275: ...t with metal cap 1 12 pin male connector Weight Dimensions W H L approx 220 g 55 30 63 mm Dimension drawing for programmer connector with plug connectors with pin socket insert 1 Observe the bending radii of the cable when installing the module 1 1 Figure 13 3 Programmer Connector Dimension Drawing with Plug Connectors with Pin Socket Insert Dimension Drawing Other ET 200C Components ...

Page 276: ...or 6ES5 762 2CA12 Continued Dimension drawing for Programmer Connector 12 pin socket connector 12 pin socket connector 12 pin socket connector Chain length approx 80 mm Coding position Figure 13 4 Programmer Connector Dimension Drawing Dimension Drawing Other ET 200C Components ...

Page 277: ...r diameter of the 5 core bus cable 8 mm Version Single pair bus cable and 3 supply lines with common screen 1 Youcanalsousethiscableforfeedingthepowersupply to the power supply connector or for feeding the external load voltage Cables for SINEC L2 DP 2 core Surge impedance approx 135 to 160 W f 3 to 20 MHz Loop impedance v 115 W km Effective capacity 30 nF km Attenuation 0 9 dB 100 m f 200 kHz Per...

Page 278: ...buted I O Station EWA 4NEB 812 6119 02b 13 5 Terminating Resistor 6ES5 755 2CA11 Technical Specifications Connection 1 12 pin socket in metal cap Weight Dimensions diameter H approx 70 g 26 40 mm Other ET 200C Components ...

Page 279: ...EB 812 6119 02b 13 6 Adapter Cable 6ES5 755 8CA11 Technical Specifications Connections 1 9 pin D sub connector 1 12 pin connector Cable length without plug in connector 20 cm Smallest permissible bending radius 7 5 DMax Other ET 200C Components ...

Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...

Page 281: ...A 1 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Pin Assignments of the ET 200C Modules This chapter describes the pin assignments of the analog and digital modules in ET 200C In this Chapter A ...

Page 282: ...served 5 reserved 11 reserved 6 reserved 12 reserved Table A 2 Pin Assignment of Bus Connector for ET 200C Digital Modules only Separate Power Supply Connected Pin Assignment Pin Assignment 1 reserved 7 P 24 V 2 reserved 8 M 24 V 3 reserved 9 PE 4 reserved 10 reserved 5 reserved 11 reserved 6 reserved 12 reserved Table A 3 Pin Assignment of Bus Connector for ET 200C Digital Modules SINEC L2 DP and...

Page 283: ...Pin Assignment Outputs of ET 200C DO 8 DC 24V 0 5A ET 200C DO 8 DC 24V 2A and ET 200C DI16 DO16 DC 24V 2A 6ES7 143 0BL00 0XB0 Pin Output View 1 not used 1 2 2 not used 1 2 5 3 Ground 3 4 5 4 Signal View mating side 3 4 5 PE View mating side Table A 6 Pin Assignment Inputs and Outputs of ET 200C DI 16 DO 16 DC 24V 2A 6ES7 143 0BL10 0XB0 Terminal Assignment I0 0 I0 7 I0 input 0 7 I1 0 I1 7 I1 input ...

Page 284: ...7 Pin Assignment for Load Voltage Supply ET 200C Modules with Outputs Pin Load voltage supply 1 PE 2 P 24 V 3 M 24 V 4 not used 5 not used 6 not used Table A 8 Pin Assignment External Power Supply at PSU Feed Pin Power supply 1 PE 2 P 24 V 3 M 24 V 4 not used 5 not used 6 not used Pin Assignments of the ET 200C Modules ...

Page 285: ...0 reserved 5 reserved 11 reserved 6 reserved 12 reserved Table A 10 Pin Assignment of Bus Connector for ET 200C Analog Modules only Separate Power Supply Connected Pin Assignment Pin Assignment 1 reserved 7 P 24 V 2 reserved 8 M 24 V 3 reserved 9 PE 4 reserved 10 reserved 5 reserved 11 reserved 6 reserved 12 reserved Table A 11 Pin Assignment of Bus Connector for ET 200C Analog Modules SINEC L2 DP...

Page 286: ...asuring line CH2 Measuring line Measuring line 8 Measuring line Measuring line Measuring line 9 Constant current line IC CH3 Measuring line Measuring line 10 Constant current line IC Measuring line Measuring line 11 CH2 Measuring line CH4 Measuring line Measuring line 12 Measuring line Measuring line Measuring line 13 Constant current line IC CH5 Measuring line Measuring line 14 Constant current l...

Page 287: ...200C AI 4 12 Bit 6ES7 144 0HF00 0XB0 Channel Terminal Assignment CH0 1 Measuring line 2 Measuring line CH1 3 Measuring line 4 Measuring line CH2 5 Measuring line 6 Measuring line CH3 7 Measuring line 8 Measuring line 9 Analog ground MANA 10 Analog ground MANA Pin Assignments of the ET 200C Modules ...

Page 288: ... Sensor line S not used CH1 7 Analog output Voltage Analog output Current or Voltage 8 Analog output Voltage Analog output Current or Voltage 9 Sensor line S not used 10 Sensor line S not used CH2 11 Analog output Voltage Analog output Current or Voltage 12 Analog output Voltage Analog output Current or Voltage 13 Sensor line S not used 14 Sensor line S not used CH3 15 Analog output Voltage Analog...

Page 289: ...ely you can fetch the device master data by modem from the Inter face Center by dialing the following mailbox number Phone 49 for Germany 911 73 7972 This chapter contains the listings of all type files for configuring your system with COM ET 200 V4 x ET 200C digital modules and COM ET 200 Win dows ET 200C analog modules If the need arises you can use these list ings to generate a missing type fil...

Page 290: ... directory of COM ET 200 V4 x The designations of the type files for ET 200C digital modules with COM ET 200 V4 x are as follows Table B 1 Designations of Type Files for ET 200C Digital Modules Station type Order number Type file C 8DI DP 6ES7 141 0BF00 0XB0 SN8010TD 200 C 8DO DP 6ES7 142 0BF00 0XB0 SN8011TD 200 C 8DO 2A DP 6ES7 142 0BF10 0XB0 SI8012TD 200 C 16DI 16DO 2A DP 6ES7 143 0BL00 0XB0 6ES...

Page 291: ...DP SIEMENS SIMATIC_S7 ET200 ET200C 24V DP 32784 Y Y Y Y Y Y N N N N N N N N 00000 1111011111 032 032 032 015 012 PV005 00 00 00 00 00 PSL000 KV000 SY DKM000 69 char 5 char 18 char 11 char 11 char 11 char 16 char 6 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 6 char 11 char 4 char 4 char 4 char 4 char 4 char 6 char 3 char 3 char 3 char 3 cha...

Page 292: ...DO DP SIEMENS SIMATIC_S7 ET200 ET200C 24V DP 32785 Y Y Y Y Y Y N N N N N N N N 00000 1111011111 032 032 032 015 012 PV005 00 00 00 00 00 PSL000 KV000 SY DKM000 76 char 5 char 18 char 11 char 11 char 11 char 16 char 6 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 6 char 11 char 4 char 4 char 4 char 4 char 4 char 6 char 3 char 3 char 3 char 3 ...

Page 293: ...DO 2A DP SIEMENS SIMATIC_S7 ET200 ET200C 24V DP 32786 Y Y Y Y Y Y N N N N N N N N 00000 1111011111 032 032 032 015 012 PV005 00 00 00 00 00 PSL000 KV000 SY DKM000 74 char 5 char 18 char 11 char 11 char 11 char 16 char 6 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 6 char 11 char 4 char 4 char 4 char 4 char 4 char 6 char 3 char 3 char 3 char...

Page 294: ...16DI 16DO 2A DP SIEMENS SIMATIC_S7 ET200 ET200C 24V DP 32787 Y Y Y Y Y Y N N N N N N N N 00000 1111011111 032 032 032 015 012 PV005 00 00 00 00 00 PSL000 KV000 SY DKM000 73 char 5 char 18 char 11 char 11 char 11 char 16 char 6 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 6 char 11 char 4 char 4 char 4 char 4 char 4 char 6 char 3 char 3 char...

Page 295: ...the ET 200C module is installed in the direc tory of COM ET 200 Windows The designations of the type files for ET 200C analog modules with COM ET 200 Windows are as follows Table B 2 Designations of Type Files for ET 200C Analog Modules Station type Order number Type file C 4 8AI DP 6ES7 144 0KH00 0XB0 SI800FAD 200 C 4AI DP 6ES7 144 0HF00 0XB0 SI800EAD 200 C 4AO DP 6ES7 145 0HF00 0XB0 SI800DAD 200...

Page 296: ... Y N N N N N N N N N 00030 0001011111 016 000 004 028 043 PV036 00 00 00 07 81 04 00 00 00 00 13 81 04 01 00 00 00 00 00 00 00 00 71 char 5 char 18 char 11 char 11 char 11 char 16 char 6 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 6 char 11 char 4 char 4 char 4 char 4 char 4 char 6 char 3 char 3 char 3 char 3 char 3 char 3 char 3 char 3 ch...

Page 297: ...0 0 231 HI003 PS026 Measurement type measuring range CH4 5 BYTE 0 0 231 HI003 PS027 Measurement type measuring range CH6 7 BYTE 0 0 231 HI003 PS028 Upper limit value CH 0 INT 0 32768 32767 HI000 PS030 Lower limit value CH 0 INT 0 32768 32767 HI000 PS032 Upper limit value CH 2 INT 0 32768 32767 HI000 PS034 Lower limit value CH 2 INT 0 32768 32767 HI000 PS041 Measured value presentation BIT2 0 0 1 H...

Page 298: ...00178 Measurement type th cpl type J ext 00181 Measurement type th cpl type L ext 00182 Measurement type th cpl type T ext 00183 Measurement type th cpl type K ext 00184 Measurement type th cpl type U ext 00185 Measurement type th cpl type N ext lin 00225 Measurement type th cpl type E ext lin 00226 Measurement type th cpl type J ext lin 00229 Measurement type th cpl type L ext lin 00230 Measureme...

Page 299: ...ge overshot CH3 1 DBO016 0 Parameterization error CH 4 1 DBO016 1 Common mode error CH 4 1 DBO016 3 Short circuit to M CH 4 1 DBO016 4 Wire break CH 4 1 DBO016 6 Measuring range undershot CH4 1 DBO016 7 Measuring range overshot CH4 1 DBO017 0 Parameterization error CH 5 1 DBO017 1 Common mode error CH 5 1 DBO017 3 Short circuit to M CH 5 1 DBO017 4 Wire break CH 5 1 DBO017 6 Measuring range unders...

Page 300: ...00C Distributed I O Station EWA 4NEB 812 6119 02b Type file SI800FAD 200 COM ET 200 Windows C 4 8AI DP char SO000 016 MLFB000 LSK000 000 SPT000 HTT000 6 char 4 char 8 char 7 char 4 char 7 char 7 char Type Files ...

Page 301: ...N N N N N N N N N 00020 0001011111 008 000 004 028 043 PV036 00 00 00 07 81 04 00 00 00 00 13 81 04 01 00 00 00 00 00 00 00 00 70 char 5 char 18 char 11 char 11 char 11 char 16 char 6 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 6 char 11 char 4 char 4 char 4 char 4 char 4 char 6 char 3 char 3 char 3 char 3 char 3 char 3 char 3 char 3 char ...

Page 302: ...CH 2 INT 0 32768 32767 HI000 PS034 Lower limit value CH 2 INT 0 32768 32767 HI000 PS041 Measured value presentation BIT2 0 0 1 HI003 HTT005 HI001 L2 disable 00000 enable enable diag alarm 00001 HI002 L8 Channel not activated 00000 Measurement type 1 25 V 00020 Measurement type 2 5 V 00021 Measurement type 5 0 V 00022 Measurement type 10 V 00025 Measurement type 20 mA 00036 Measurement type 0 20 mA...

Page 303: ...1 DBO012 7 Measuring range overshot CH0 1 DBO013 0 Parameterization error CH 1 1 DBO013 6 Measuring range undershot CH1 1 DBO013 7 Measuring range overshot CH1 1 DBO014 0 Parameterization error CH 2 1 DBO014 6 Measuring range undershot CH2 1 DBO014 7 Measuring range overshot CH2 1 DBO015 0 Parameterization error CH 3 1 DBO015 6 Measuring range undershot CH3 1 DBO015 7 Measuring range overshot CH3 ...

Page 304: ... N N N N N N N N 00020 0001011111 000 008 004 028 043 PV036 00 00 00 07 81 04 00 00 00 00 13 81 04 01 00 00 00 25 25 25 25 00 69 char 5 char 18 char 11 char 11 char 11 char 16 char 6 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 2 char 6 char 11 char 4 char 4 char 4 char 4 char 4 char 6 char 3 char 3 char 3 char 3 char 3 char 3 char 3 char 3 char 3...

Page 305: ...0 Substitute value CH 1 INT 0 32768 32767 HI000 PS032 Substitute value CH 2 INT 0 32768 32767 HI000 PS034 Substitute value CH 3 INT 0 32768 32767 HI000 PS041 Measured value presentation BIT2 0 0 1 HI004 HTT005 HI001 L2 disable 00000 enable 00001 HI002 L2 Substitute value parameterizable 00000 Substitute value last value 00001 HI003 L6 Output range 1 5 V 00023 Output range 0 10 V 00024 Output range...

Page 306: ... CH 1 1 DBO013 3 Short circuit to M CH 1 1 DBO013 4 Wire break CH 1 1 DBO013 6 No load voltage CH 1 1 DBO014 0 Parameterization error CH 2 1 DBO014 1 Common mode error CH 2 1 DBO014 2 Short circuit to P CH 2 1 DBO014 3 Short circuit to M CH 2 1 DBO014 4 Wire break CH 2 1 DBO014 6 No load voltage CH 2 1 DBO015 0 Parameterization error CH 3 1 DBO015 1 Common mode error CH 3 1 DBO015 2 Short circuit ...

Page 307: ...uted I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines The following guidelines are intended to ensure personal safety as well as to protect the products and equipment connected against damage In this Chapter C ...

Page 308: ...he product supplied Warning In all cases where a fault in automation equipment can result in severe personal injury or substantial property damage i e where a dangerous fault can occur additional external measures must be taken or equipment provided to ensure or force safe operating conditions even in the event of a fault e g by means of independent limit monitors mechanical interlocks etc If you ...

Page 309: ...41 VDE 0100 Part 410 Fluctuations or deviations of the supply voltage from the rated value may not exceed the tolerance limit specified in the technical specifications If they do functional failures or dangerous conditions can occur in the electronic modules or equipment Take suitable measures to make sure that programs that are interrupted by a voltage dip or power failure resume proper operation...

Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...

Page 311: ...he binary file is formatted in such a way that it can be read by different ver sions of COM ET 200 Common transmission path for all nodes connected with defined termination points All ET 200C modules have a bus connection 12 pin socket This bus con nection has several functions Connection to the SINEC L2 DP field bus Connection to the power supply Connection to the field bus and power supply at a ...

Page 312: ...of the slave specific diagnostics The device related diagnostics refer to the entire slave Detection location classification display additional evaluation of errors faults and messages Diagnostics includes monitoring functions that are automatically executed during normal operation Application Increasing the availability of a system plant by cutting start up and idle times Comprises the input outp...

Page 313: ...other adequate master The ET 200 is characterized by fast response times as only small volumes of data bytes are transferred ET 200 is based on the PROFIBUS standard DIN 19245 part 1 and the draft standard PROFIBUS DP DIN 19245 part 3 ET 200 operates in accordance with the master slave principle The IM 308 B or any host incorporating the CP 5480 DP can be master The distributed I O stations ET 200...

Page 314: ...master system Affiliation of a bus station with a group H A host is a system or device which incorporates at least one DP master e g The programmable controller with the CPU is the host and the IM 308 C the DP master The PC is the host and the CP 5480 the DP master I Degree of protection to DIN 40050 full protection against contact with live or moving parts contamination dust and the harmful ingre...

Page 315: ...f the control and load circuits are electrically interconnected O indicates the slave station for which a diagnostics message is present P They may exchange data with an active node only after being requested to do so by the active node slave station This is the master which is authorized to parameterize a slave station PROcess FIeld BUS German process and field bus standard defined in the PROFIBU...

Page 316: ...ng resistors constitutes a segment A seg ment includes 0 to 32 nodes Segments can be linked via repeaters Caused by a fault it conductively connects conductors that are energized in normal operation if no resistance is inserted in the faulty circuit LAN that interfaces PROFIBUS compatible programmable controllers and field devices both at the cell and field levels SINEC L2 LAN with DP protocol DP ...

Page 317: ... of an ET 200C module or onto a T connector File which is required by the COM ET 200 in order to configure a slave sta tion The type file contains slave specific characteristics such as number of inputs and outputs number of diagnostics bytes SYNC capability etc are defined One type file which is generated by Siemens and is part of COM ET 200 from version 4 1 is available for each ET 200C station ...

Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...

Page 319: ... module DO 8 x DC 24V 2A 3 7 programmer connector 3 19 T connector 3 17 wiring 4 10 Bus node Glossary 1 Bus segment Glossary 1 C Cables 1 4 3 20 made up by the customer 4 8 prefabricated 4 8 technical specifications 13 7 Characteristics of ET 200C 1 4 1 5 1 6 Circular connectors rules for connection 4 9 COM ET 200 5 1 Components ET 200C 3 1 Conduit thread gland 1 4 Configuration grounded 4 3 4 4 u...

Page 320: ...3 8 connections 3 8 technical specifications 11 16 wiring 4 13 4 15 4 17 4 19 Digital output module DO 8 x DC 24V 0 5A 1 3 3 4 connections 3 4 technical specifications 11 6 wiring 4 15 Digital output module DO 8 x DC 24V 2A 1 3 3 6 connections 3 6 technical specifications 11 11 wiring 4 15 DIL switches 4 23 4 32 4 43 DIN 19245 1 2 Distributed I O Glossary 2 DP master Glossary 2 DP Siemens Glossary...

Page 321: ...nect for 6ES7 143 0BL10 0XB0 4 17 4 19 connecting 4 15 4 35 Overview of digital and analog modules for the ET 200C 10 2 Overview diagnostics Glossary 5 P Parameterization master Glossary 5 Passive nodes Glossary 5 Pin assignment for inputs 4 21 4 30 for inputs and outputs for 6ES7 143 0BL10 0XB0 4 17 4 19 for outputs 4 35 inputs of ET 200C AI 4 x 12 Bit 4 31 A 7 inputs outputs of ET 200C DI 16 DO ...

Page 322: ...grammer 6 2 for connecting the programmer connector 2 17 for current connection 2 15 for grounded configuration 4 4 for installation 4 2 for the external load voltage supply 2 6 2 9 2 14 for the T connector 2 9 2 14 for ungrounded configuration 4 6 S Screen CONFIGURING 1 5 3 5 4 CONFIGURING 2 5 5 5 6 CONFIGURING 3 5 7 5 9 DIAGNOSTICS OVERVIEW 7 5 INDIVIDUAL DIAGNOSTICS 7 5 STARTUP TEST STATION SEL...

Page 323: ...cal specifications 13 8 Test with ET 200 handheld 6 1 9 1 with programmer and COM ET 200 6 1 6 6 Test and startup 3 23 6 1 Thermocouple 4 24 4 25 4 26 Twist caps for sealing unused connections 4 17 4 19 4 22 4 31 for sealing unused outputs 4 15 for unused inputs 4 13 Type file B 1 Glossary 7 U UNFREEZE Glossary 7 Ungrounded configuration 4 6 rules 4 6 UNSYNC Glossary 7 V Voltage sensors 4 29 4 33 ...

Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...

Page 325: ...our Name Your Title Company Name Street City Zip Code Country Phone Please check any industry that applies to you Automotive Chemical Electrical Machinery Food Instrument and Control Nonelectrical Machinery Petrochemical Pharmaceutical Plastic Pulp and Paper Textiles Transportation Other ...

Page 326: ...anual Order No of Your Manual Release Please give each of the following questions your own personal mark within the range from 1 very good to 5 poor 1 Do the contents meet your requirements 2 Is the information you need easy to find 3 Is the text easy to understand 4 Does the level of technical detail meet your requirements 5 Please rate the quality of the graphics tables Please do not forget to s...

Page 327: ...24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit ET 200C AO 4 12 Bit Drill holes M4 thread ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit ET 200C AO 4 12 Bit Drill holes M4 thread ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit...

Page 328: ...24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit ET 200C AO 4 12 Bit Drill holes M4 thread ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit ET 200C AO 4 12 Bit Drill holes M4 thread ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit...

Page 329: ...24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C DI 8 DC 24V ET 200C DO 8 DC 24V 0 5 A ET 200C DO 8 DC 24V 2A ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit ET 200C AO 4 12 Bit Drill holes M4 thread ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit ET 200C AO 4 12 Bit Drill holes M4 thread ET 200C AI 4 8 12 Bit ET 200C AI 4 12 Bit...

Page 330: ...ET 200C Distributed I O Station EWA 4NEB 812 6119 02b 240 mm 110 mm Drill hole template Drill holes M4 thread ET 200C DI 16 DO 16 DC 24V 2A ...

Page 331: ...ET 200C Distributed I O Station EWA 4NEB 812 6119 02b 240 mm 110 mm Drill hole template Drill holes M4 thread ET 200C DI 16 DO 16 DC 24V 2A ...

Page 332: ...ctor Drill holes M4 thread 63 mm 2 48 inches 52 mm 2 05 inches Drill hole template Power supply connector Drill holes M4 thread 63 mm 2 48 inches 52 mm 2 05 inches Drill hole template Power supply connector Drill holes M4 thread 63 mm 2 48 inches 52 mm 2 05 inches Drill hole template Power supply connector Drill holes M4 thread 63 mm 2 48 inches 52 mm 2 05 inches Drill hole template Power supply c...

Page 333: ...ET 200C Distributed I O Station EWA 4NEB 812 6119 02b 14 mm 0 55 inch 14 mm 0 55 inch 14 mm 0 55 inch 14 mm 0 55 inch 14 mm 0 55 inch 14 mm 0 55 inch ...

Reviews: