Communication using function blocks
6.3 Using the function blocks for connecting to a communications processor
PtP coupling and configuration of CP 340
Manual, 04/2011, A5E00369892-03
111
P_RCV (FB 2) parameters
The table below lists the parameters of P_RCV (FB 2).
Table 6- 3
P_RCV (FB 2) parameters
Name
Type
Data type
Comment
Permitted values, comment
EN_R
INPUT
BOOL
Enables data read
R
INPUT
BOOL
Cancels request
Current request is aborted. Receiving
locked
LADDR
INPUT
INT
Basic address of CP 340
The start address is taken from STEP
7.
DB_NO
INPUT
INT
Data block number
Receive DB No.:
CPU-specific, zero is not permitted
DBB_NO
INPUT
INT
Data byte number
0 ≤ DBB_NO ≤ 8190 Received data as
of data byte
NDR
1)
OUTPUT
BOOL
Request completed without
errors, data accepted
STATUS parameter == 16#00;
ERROR
1)
OUTPUT
BOOL
Request completed with
errors
Error information is written to the
STATUS parameter.
LEN
1)
OUTPUT
INT
Length of message frame
received
1 ≤ LEN ≤ 1024, specified in number
of bytes
STATUS
1)
OUTPUT
WORD
Specification of error
If ERROR == 1, the STATUS
parameter contains the error
information.
1)
The parameter is available for a single CPU cycle after the send request has been completed correctly.
Summary of Contents for SIMATIC CP 340
Page 6: ...Preface PtP coupling and configuration of CP 340 6 Manual 04 2011 A5E00369892 03 ...
Page 10: ...Table of contents PtP coupling and configuration of CP 340 10 Manual 04 2011 A5E00369892 03 ...
Page 200: ...Index PtP coupling and configuration of CP 340 200 Manual 04 2011 A5E00369892 03 ...