A.4
Mounting rules
A.4.1
Minimum clearances in the control cabinet
Install the mounting rail so that sufficient space remains for the installation and heat removal of
the Compact Field Unit remains.
Observe the following points if you plan to install the Compact Field Unit:
● Ensure that the space in the control cabinet or components in the surrounding area is
sufficient for the heat to be removed.
See the following table
● When mounting on a mounting rail, pay attention to the distance between the fixing points:
maximum distance 500 mm - measured between the first and the last fixing point
● Leave sufficient space for the wiring and the communication cable connections.
● Route the cables away from the CFU as follows:
– Horizontal installation (see figure below):
Route cables downwards.
– Vertical installation (interface dome at bottom; rotated 90° counterclockwise compared
to the figure below):
Route cables to the right.
Table A-9
Minimum clearances in the control cabinet
Top
20 mm
Left
10 mm
Right
10 mm
Bottom
20 mm
Appendix
A.4 Mounting rules
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
185
Summary of Contents for Simatic CFU
Page 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Page 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...