Technical specifications
7
Table 7-1
Technical specifications 6DL2804-xxDxx / xxExx / xxFxx / xxGxx (not for mining)
6DL2804-
xxDxx
xxExx
xxFxx
xxGxx
Wall-mounted enclosure
Type 6DL2804-0xxxx, DMT 02 ATEX E 249 U
Ex marking
see below - section Ex marking
Degree of protection
1)
IP54 to IP66
Dimensions: W x H x D
650 x 450 x 230
950 x 450 x 230
650 x 450 x 350
950 x 450 x 350
Material
Stainless steel: DIN 1.4404, plate thickness 1.5 mm
Weight [kg]
30
43
31
43
Cover seal
Silicone rubber
Cable entries for
Voltage (cable-Ø in mm)
2 M32 Ex e (13 to 21)
Bus (cable-Ø in mm)
4 M20 Ex e (6 to 13)
Signals (cable-Ø in mm)
M16 (4 to 9)
M16 (4 to 9)
M20 (6 to 13)
M20 (6 to 13)
3 rows (xxx3x)
39
66
36
57
5 rows (xxx5x)
65
110
60
95
Equipotential bonding rail
3 x 10 mm Cu
Bonding terminals
0.75 to 35 mm² Ex e for equipotential bonding cable, 4 mm² for shield connection
Protective conductor connector
M6 screw, at least 16 mm²
Rated voltage/current
2)
These values depend on the installed components.
Operating temperature range
6DL2804-1xxxx with installation of
ET200iSP
-20 °C to +xx °C
3)
6DL2804-1xxx1 with installation and
heater
-40 °C to +xx °C
3) 4)
6DL2804-2xxxx
with installation of ET200iSP and elec‐
tro-pneumatic system AirLine Ex Typ
8650
0 °C to +xx °C
3)
Permissible humidity
Max. 95%
1)
The degree of protection of the enclosure depends on that of the installed parts and the enclosure size.
2)
The actual electrical values depend on the electrical equipment installed. The manufacturer specifies the final values within
the framework of these limits.
3)
The specified permissible operating temperature range is only valid if the enclosure is installed horizontally. A vertical
installation can reduce the maximum permissible temperature (for information on this refer also to the ET200iSP manual).
The max. operating temperature is defined depending on the dissipated heat of the installed components, and specified
on the nameplate.
Note that the operating temperature of the complete setup must be checked again if further components are subsequently
fitted.
4)
The temperature range of -40 °C only applies to the enclosure types 6DL2804-1xxx1 (metal cable entries). Installation of
a heater is required for this.
Distributed I/O device 6DL2804-1xxxx & 6DL2804-2xxxx
Hardware Installation Manual, 07/2017, A5E42025214-AA
29