Mounting
4.2 Mounting the enclosure
Wall-mount enclosure 6DL2804-0xxxx
16
Hardware Installation Manual, 08/2009, A5E00378691N-02
4.2
Mounting the enclosure
The enclosure is intended for wall mounting and should be secured with the wall supports
supplied with it. Use the following template for the drilling.
%
$
%
%
%
B = 950 mm for 6DL2804-xxDxx
B = 650 mm for 6DL2804-xxExx
Figure 4-1
Drilling template for securing the device
NOTICE
Reduction of the degree of protection
If the device is not installed horizontally, this may lead to a reduction in the degree of
protection. Furthermore, the operating ambient temperature is 30°C lower with vertical
installation than with horizontal installation. The temperature information on the type plate
always applies to horizontal installation. Therefore, always install the device horizontal, in
such a way that the cable entries face downward.
NOTICE
•
Remember the maximum thermal load on the cables and wiring. The degree of
protection is only ensured when suitable cables and wires are used and correctly
installed.
•
Note that it is only permitted to connect and disconnect the cables to the power supply
module if the module has been powered down.