background image

Security information

1

Siemens provides products and solutions with industrial security functions that support the 
secure operation of plants, systems, machines and networks.

In order to protect plants, systems, machines and networks against cyber threats, it is necessary 
to implement – and continuously maintain – a holistic, state-of-the-art industrial security 
concept. Siemens’ products and solutions constitute one element of such a concept.

Customers are responsible for preventing unauthorized access to their plants, systems, 
machines and networks. Such systems, machines and components should only be connected to 
an enterprise network or the internet if and to the extent such a connection is necessary and only 
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.

For additional information on industrial security measures that may be implemented, please 
visit 
https://www.siemens.com/industrialsecurity. 

Siemens’ products and solutions undergo continuous development to make them more secure. 
Siemens strongly recommends that product updates are applied as soon as they are available 
and that the latest product versions are used. Use of product versions that are no longer 
supported, and failure to apply the latest updates may increase customer’s exposure to cyber 
threats.

To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed 
under 
https://www.siemens.com/industrialsecurity. 

DI 8x24...125VDC HA
Equipment Manual, 10/2021, A5E39288633-AD

5

Summary of Contents for SIMATIC 6DL1131-6DF00-0EK0

Page 1: ...DF00 0PK0 6DL1131 6DF00 0EK0 10 2021 A5E39288633 AD Security information 1 Preface 2 2D Matrix code QR code EAN code 3 Product overview 4 Terminal 5 Parameters 6 Displays and interrupts 7 Technical specifications 8 Parameters diagnostics messages and address space A ...

Page 2: ...nnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufacturers are...

Page 3: ...le channel parameters 20 6 4 1 Channel activated 20 6 4 2 Diagnostics Missing supply voltage L 21 6 4 3 Diagnostics Wire break 21 6 4 4 Wire break check 21 6 4 5 Input delay 21 6 4 6 Hardware interrupts positive edge 21 6 4 7 Hardware interrupts negative edge 21 6 4 8 Potential group 22 7 Displays and interrupts 23 7 1 Status and error displays 23 7 2 LEDs 24 7 2 1 DIAG LED 24 7 2 2 MT LED 24 7 2 ...

Page 4: ...ts 38 A 5 Hardware interrupts 39 A 6 Address space 40 A 7 Address space of the time stamping accuracy 1 ms 40 Tables Table 5 1 Terminal assignment of the DI 8 24 125VDC HA 16 Figures Figure A 1 Structure byte x to x 1 for the channels 0 to 7 37 Table of contents DI 8x24 125VDC HA 4 Equipment Manual 10 2021 A5E39288633 AD ...

Page 5: ...nd to the extent such a connection is necessary and only when appropriate security measures e g firewalls and or network segmentation are in place For additional information on industrial security measures that may be implemented please visit https www siemens com industrialsecurity Siemens products and solutions undergo continuous development to make them more secure Siemens strongly recommends t...

Page 6: ...Security information DI 8x24 125VDC HA 6 Equipment Manual 10 2021 A5E39288633 AD ...

Page 7: ...0SP HA distributed I O system Functions that generally relate to the system are described in this manual The information in this device manual and the system function manuals help you to commission the ET 200SP HA Conventions Please also observe notes marked as follows Note A note contains important information on the product described in the documentation on the handling of the product and on the...

Page 8: ...Preface DI 8x24 125VDC HA 8 Equipment Manual 10 2021 A5E39288633 AD ...

Page 9: ...x code SIEMENS offers an app for mobile use Information about the app and the download can be found on the Internet Mobile use via app https support industry siemens com cs ww en sc 2067 The app provides direct access to the technical forum and product related posts such as FAQs Application examples Manuals Certificates Product notices DI 8x24 125VDC HA Equipment Manual 10 2021 A5E39288633 AD 9 ...

Page 10: ...2D Matrix code QR code EAN code DI 8x24 125VDC HA 10 Equipment Manual 10 2021 A5E39288633 AD ...

Page 11: ...u configure the I O module DI 8x24 125VDC HA using HW Config In addition to the technical specifications this module has the following properties Parameter reassignment in RUN Value status DI 8x24 125VDC HA Equipment Manual 10 2021 A5E39288633 AD 11 ...

Page 12: ...Module type color coding LED for diagnostics Product version LED for maintenance Function status and firmware ver sion 2D matrix code Color code for selection of the col or coded labels Wiring diagram Serial number LEDs for channel status channel fault Article number 4 2 Accessories Definition Accessories for the I O module must be ordered separately Description The following accessories are avail...

Page 13: ...re available for the I O module Article No Color Description 6DL1193 6TP00 0DK0 Lit for single operation and new load group 6DL1193 6TP00 0BK0 Dark for single operation Note Terminal blocks are not included in the scope of delivery of the I O module and must be ordered separately You can find additional information on the configuration in the system manual Product overview 4 3 Terminal blocks DI 8...

Page 14: ...Product overview 4 3 Terminal blocks DI 8x24 125VDC HA 14 Equipment Manual 10 2021 A5E39288633 AD ...

Page 15: ...minal assignment Definition The pin assignment provides you with information on the arrangement and marking of the connections when wiring a plug in connector DI 8x24 125VDC HA Equipment Manual 10 2021 A5E39288633 AD 15 ...

Page 16: ...1 12 13 14 2M 3 DI2 4 DI3 5 DI4 6 DI5 7 DI6 8 DI7 9 2M 10 2M 11 2M 12 2M 13 2M 14 2M 15 2M 16 2M 1P1 L 1P2 M 2P1 L 2P2 M Notice Note differences in potential The load voltage supply and the signal voltage of the I O module are electrically isolated The connection of the load supply voltage and the signal voltage is only permissible when no compensating currents are flowing as a result of a differe...

Page 17: ...re sensor Example 0 1 Q 5 3 Schematic circuit diagram Definition A block diagram contains the schematic representation of individual function blocks Terminal 5 3 Schematic circuit diagram DI 8x24 125VDC HA Equipment Manual 10 2021 A5E39288633 AD 17 ...

Page 18: ...7 Voltage monitoring Status DI0 DI7 3 3 V A resistor must be connected to the encoder contacts in order to perform wire break detection The resistor used is dependent on the nominal input voltage of the module LQ 5V Nominal input voltage Resistor Rs 24 V DC 43 kΩ 48 V DC 100 kΩ 125 V DC 300 kΩ Terminal 5 3 Schematic circuit diagram DI 8x24 125VDC HA 18 Equipment Manual 10 2021 A5E39288633 AD ...

Page 19: ... channels Deactivate unused channels in the configuration to improve the cycle time of the module A deactivated channel always returns the output value 0 mA Parameter Value range Default Parameter re assignment in RUN Efficiency range Channel activated Page 20 Activated Deactivated Activated Yes Channel Diagnostics No supply volt age L Page 21 Activated Deactivated Activated Yes Module Diagnostics...

Page 20: ...you need to connect a resistor in parallel to enable a wire break check to be performed when the contacts are open The resistor used depends on the nominal input voltage of the module 3 When time stamping with an accuracy of 1 ms is enabled the input delay on all channels is switched off and the pulse stretching and hardware interrupt for positive negative edge is disabled on all channels not adju...

Page 21: ...ak if wire break is activated 6 4 5 Input delay Definition This parameter can be used to avoid signal faults Changes to the signal are only detected if they are constantly pending longer than the set input delay time 6 4 6 Hardware interrupts positive edge Definition Specifies if a hardware interrupt should be generated for a rising edge 6 4 7 Hardware interrupts negative edge Definition Specifies...

Page 22: ...tential group is fed in The potential group is continued to the right with dark gray terminal blocks and ends when a new potential group is built up next to it The potential group also ends if there is a black terminal block next to it Black terminal blocks are fed individually and cannot be included in potential groups You can find additional information on the configuration of the potential grou...

Page 23: ... The following figure identifies the LED displays of the I O module DIAG MT DI HA 8x24 125VDC 7 DI 6 8 1 DI 0 2 3 DI 2 4 5 DI 4 6 1P1 L 24VDC M 1P2 2P1 L 24VDC M 2P2 MAX 10 A 0 1 V 1 0 0 CC42 PWR 6DL1131 6DF00 0PK0 X 2 3 4 DI 7 DI 1 DI 3 DI 5 DI 15 16 9 10 11 12 13 14 F0 F1 2 3 F2 F3 4 5 F4 F5 6 7 F6 F7 2M DIAG LED Page 24 green red MT LED Page 24 yellow Channel status fault LEDs Page 25 green Cha...

Page 24: ...rameters are assigned No diagnostic message is pending flashes Module parameters are assigned At least one diagnostic message is pending 7 2 2 MT LED Definition The MT LED provides maintenance information Description The MT LED indicates the following maintenance status MT LED Meaning Off No maintenance is required On Maintenance is required At least one maintenance event has occurred Displays and...

Page 25: ...nding Off On Channel enabled and channel diagnostics module diagnostics pending 7 2 4 PWR LED Definition The PWR LED provides you status information about supply voltage L Description The PWR LED indicates the following status PWR LED Meaning Off Supply voltage L missing On Supply voltage L present 7 3 Interrupts Definition A diagnostic interrupt reports activated events of a device status to the ...

Page 26: ...component temporarily unavailable Hardware interrupt lost Parameter assignment error Retentive memory in carrier module defective Retentive memory in the terminal block defective Note A pending Module is defective or Overtemperature diagnostic is not deleted from the module without a restart Displays and interrupts 7 3 Interrupts DI 8x24 125VDC HA 26 Equipment Manual 10 2021 A5E39288633 AD ...

Page 27: ...figurable integrated from version V9 0 PROFINET from GSD version GSD revision GSDML V2 3 Operating mode DI Yes Redundancy Redundancy capability No Supply voltage Rated value DC 24 V permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Input current Current consumption rated value 16 mA Current consumption max 20 mA Power loss Power loss ty...

Page 28: ...w LED Monitoring of the supply voltage PWR LED Yes green PWR LED Channel status display Yes green LED for channel diagnostics Yes red LED for module diagnostics Yes green red DIAG LED Potential separation Potential separation channels between the channels No between the channels and backplane bus Yes Permissible potential difference between different circuits 250 V AC 300 V DC Isolation Isolation ...

Page 29: ...Article number 6DL1131 6DF00 0PK0 Weights Weight approx 165 g Technical specifications DI 8x24 125VDC HA Equipment Manual 10 2021 A5E39288633 AD 29 ...

Page 30: ...Power loss Power loss typ 3 75 W Address area Address space per module Address space per module max 14 byte Without SOE PII 1 byte 1 byte for QI information 1 byte of PROFINET status data PIO 1 byte of PROFINET status data with SOE PII 1 byte 1 byte for QI information 10 bytes for SOE 1 bytes of PROFINET status data PIO 1 byte PRO FINET status data Digital inputs Input characteristic curve in acco...

Page 31: ...tential separation channels between the channels No between the channels and backplane bus Yes Permissible potential difference between different circuits 250 V AC 300 V DC Ambient conditions Ambient temperature during operation horizontal installation min 40 C horizontal installation max 70 C vertical installation min 40 C vertical installation max 60 C Dimensions Height 115 mm Depth 138 mm Cycle...

Page 32: ...d by the I O module the signal status must be active for at least for the time period of the minimum pulse length The minimum pulse length is greater than the input delay and greater than the cycle time Technical specifications DI 8x24 125VDC HA 32 Equipment Manual 10 2021 A5E39288633 AD ...

Page 33: ...n_Num general error code Byte2 Error_Decode location of the error code Byte3 Error_Code_1 error code Byte4 Error_Code_2 manufacturer specific extension of the error code Module specific errors are displayed via Error_Decode 0x80 and Error_Code_1 Error_Code_2 Error_ Code_ 1 Error_ Code_ 2 Cause Solution 0xB0 0x00 Number of the data record unknown Enter valid number for data record 0xB1 0x01 Length ...

Page 34: ... are not listed are rejected by the module Every parameter data record is checked by the module If an incorrect parameter is detected the entire data record is rejected and the parameters of the module remain unchanged A 2 Parameter assignment and structure of the module channel parameters Structure of data record 128 Data record 128 is 28 bytes long It contains module parameters as well as all ch...

Page 35: ...VWLFV KDQQHO VHWWLQJV LDJQRVWLFV KDQQHO VHWWLQJV LDJQRVWLFV KDQQHO VHWWLQJV WH WH WH WH WH HDGHU LQIRUPDWLRQ PRGXOH WH HDGHU LQIRUPDWLRQ FKDQQHO WH 0RGXOH SDUDPHWHU WH Parameters diagnostics messages and address space A 2 Parameter assignment and structure of the module channel parameters DI 8x24 125VDC HA Equipment Manual 10 2021 A5E39288633 AD 35 ...

Page 36: ...HG WH UHVHUYHG WH 1XPEHU RI IROORZLQJ FKDQQHO SDUDPHWHU EORFNV WH HQJWK RI D FKDQQHO SDUDPHWHU EORFN WH Channel parameters Every channel parameter block contains the channel parameters for the digital input 2 bytes The following figure shows the configuration of the channel parameters for channels 0 to 7 x 12 channel number 2 with channel number 0 7 Parameters diagnostics messages and address spac...

Page 37: ... the channels 0 to 7 A 3 Diagnostics alarms Diagnostics messages A diagnostics message is generated for every fault identified The DIAG LED on the module flashes There is additionally a channel specific display of the diagnostics through the corresponding channel fault LEDs The diagnostic messages can for example be read from the diagnostic buffer of the CPU Diagnostic messages are either assigned...

Page 38: ...uring this time Restart firmware update Wait for firmware update Hardware inter rupt lost 16H Module Error is reported because the events occur faster than they can be pro cessed in the system Module is faulty 100H Module Internal module error has occurred Replace I O module Retentive memo ry in carrier mod ule defective 154H Module A memory block fault on the support module was detected during st...

Page 39: ...ditional interrupt information Evaluate hardware interrupts of digital inputs On occurrence of the following events the DI 8x24 125VDC HA generates a hardware interrupt for digital input signals At positive edge change of signal from 0 to 1 At negative edge change of signal from 1 to 0 The module digital input channel that has triggered the hardware interrupt is entered in variable OB40_POINT_ADDR...

Page 40: ...alue Value status 1 Process value okay good Value status 0 Process value not okay bad Basically the value status is set to good if the digital value can be detected without error The value status is set to bad in the following cases The process value cannot be recorded due to an error The digital channel is deactivated Note The value status is not set to bad when there is a wire break on the chann...

Page 41: ...put address space Irrespective of the diagnostics enables each value status each QI bit provides information on the validity of the corresponding process value Value status 1 Process value okay good Value status 0 Process value not okay bad Basically the value status is set to good if the digital value can be detected without error The value status is set to bad in the following cases The process ...

Page 42: ...Parameters diagnostics messages and address space A 7 Address space of the time stamping accuracy 1 ms DI 8x24 125VDC HA 42 Equipment Manual 10 2021 A5E39288633 AD ...