Error_
Code_
1
Error_
Code_
2
Cause
Solution
0xE1
0x01
Reserved bit set
Check and correct the parameters
0xE1
0x02
Invalid diagnostics enable bit set for operating mode
0xE1
0x03
Invalid hardware interrupt enable bit set for operating
mode
0xE1
0x07
Invalid coding for input delay
0xE1
0x0E
Invalid redundancy parameter assignment
Valid parameters
Only the values specified in the following are permitted. Values that are not listed are rejected
by the module.
Every parameter data record is checked by the module. If an incorrect parameter is detected, the
entire data record is rejected and the parameters of the module remain unchanged.
A.2
Parameter assignment and structure of the module/channel
parameters
Structure of data record 128
Data record 128 is 28 bytes long.
It contains module parameters as well as all channel parameters of the 8 channels.
Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters
DI 8x24...125VDC HA
34
Equipment Manual, 10/2021, A5E39288633-AD