Analog electronic modules
4.2 Analog value representation
ET 200S
4-12
Manual, Edition 10/2005, A5E00514527-01
Measuring range for thermocouple type N
Table 4-20 SIMATIC S7 format: Measuring range Type N in °C and °F
Units
Units
Type N in °C
Decimal Hexadecima
l
Type N in °F
Decimal
Hexadeci
mal
Range
> 1550.0
32767
7FFF
H
> 2822.0
32767
7FFF
H
Overflow
1550.0
:
1300.1
15500
:
13001
3C8C
H
:
32C9
H
2822.0
:
2372.1
28220
:
23721
6E3C
H
:
5CA9
H
Overshoot range
1300.0
:
-270.0
13000
:
-2700
32C8
H
:
F574
H
2372.0
:
-454.0
23720
:
-4540
5CA8
H
:
EE44
H
Rated range
< -270.0
-32768
8000
H
-32768
8000
H
<EE44
H
Underflow
Measuring range for thermocouple types R, S
Table 4-21 SIMATIC S7 format: Measuring range Type R, S in °C and °F
Units
Units
Type R, S in °C
Decimal Hexadecima
l
Type R, S in °F
Decimal
Hexadeci
mal
Range
> 2019.0
32767
7FFF
H
> 3276.6
32767
7FFF
H
Overflow
2019.0
:
1769.1
20190
:
17691
4EDE
H
:
451B
H
3276.6
:
3216.3
32766
:
32163
7FFE
H
:
7DA3
H
Overshoot range
1769.0
:
-50.0
17690
:
-500
451A
H
:
FE0C
H
3216.2
:
-58.0
32162
:
-580
7DA2
H
:
FDBC
H
Rated range
-50.1
:
-170.0
-510
:
-1700
FE0B
H
:
F95C
H
-58.1
:
-274.0
-581
:
-2740
FDBB
H
:
F54C
H
Undershoot
range
< -170.0
-32768
8000
H
< -274.0
-32768
8000
H
Underflow