12 Monitored lines
12.6.5 Parameter sets for alarm devices
The following sounds can be configured:
970Hz, continuous tone
BS 5839 'evacuate'
950Hz, 1 s intermittent
BS 5839 'alert'
Sweep down
DIN33404-3
Slow whoop
NEN2575
500Hz, pulsing
SS 031711 'imminent danger'
500Hz, intermittent
SS 031711 'important message'
500Hz, 30s
SS 031711 'all clear'
560/440Hz, alternating
NF S32-001
420Hz, intermittent
AS 2220 ‘Alert’
Slow whoop
AS 2220 ‘Action’
Intermittent
ISO 8201
Customized / Download 1
Customized / Download 2
Table35: Parameter sets for alarm devices
= Default setting in PLAN D100
FDSB291 signal base
The signal base is installed in place of the standard base and adds 2 horn output components
to the FDOxxx smoke detector. The detector can then be used to activate a warning or
evacuation sound.
The signal base has two volume settings (per component/parameter set).
The FDT241 and FDT221 heat detectors cannot actuate the signal base.
The signal base can be actuated across the whole system.
FDS221 Alarm horn (sounder)
The sounder has 2 output components which can be used to activate a warning or evacuation
sound.
The sounder has three volume settings (per component/parameter set). The sounds are con-
figured in PLAN D100:
The different sounds are differentiated by the tripping criterion (level 1 and level 2). The crite-
ria are listed in order of priority. If both sounds are triggered, the sound with the higher priority
is actuated.
If required, the criteria can be implemented by means of virtual inputs/outputs (VEA). Exam-
ple: With alarm organization, a different sound or volume can be used for the pre-alarm than
for the main alarm.
The sounder can be actuated across the whole system.
12.6.6 Calculating the maximum number of elements and length of lead
Technically, the possible length of line depends on what cable you are using (capacity and
resistance), as well as the load imposed by buzzers and sounders.
Threshold values for FDnet:
Maximum 180 ohms per loop and/or spur and maximum 330 nF for shielded and 500 nF for
unshielded lines.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
89 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Summary of Contents for SIGMASYS C
Page 4: ......
Page 30: ......
Page 38: ......
Page 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 48: ......
Page 62: ......
Page 84: ......
Page 110: ......
Page 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 130: ......
Page 132: ......
Page 134: ......
Page 137: ......