4 Project planning for control and indicating panels
Peripheral elements
Fixed system event
location
Programmable event
locations
Total event locations
Detectors
-
1
1
Contact coupler *)
2
4
6
Minitransponder *)
2
2
4
Transponder
-
4
4
Indicator panel *)
2
Number of programmed
outputs
2 + programmed outputs
Multiple control facility *)
2
Number of programmed
outputs
2 + programmed outputs
Zone operating panel *)
2
2
Table 4: Allocation of event location numbers
FDnet peripheral element
Fixed system
event loca-
tions
Suppliable event loca-
tions
Total event locations
Detector with output
-
1 + max. 1 outputs
2
Detector without output
-
1
1
Linear smoke detector FDL241
-
1 + max. 1 outputs
2
Infrared flame detector FDF
1 + max. 1 outputs
2
FDCI222 input module *)
2
max. 4 inputs
6
FDCIO222 input/output module *)
2
max. 4 inputs max. 4 out-
puts
10
FDCIO223 FDnet transponder *)
2
2 in- or outputs
4
FDCL221 line disconnector
2
-
2
FDS221 alarm sounder
-
max. 2 outputs
2
FDSB291 signal base
-
1 output
1
Table 5: Allocation of event locations in the peripheral elements in FDnet
*) maximum of 250 peripheral elements per FDC, MPC module or SIGMASYS C can be
connected.
Your marketing representative must be consulted with regard to project planning activities if
the above limitations are exceeded.
4.2
Selecting the installation location
4.2.1
Fire protection system requirements
The fire alarm control and indicating panel or the operating device is to be installed in a room
adjacent to the main entrance, the surveillance area or an access that is always accessible by
the fire brigade in the event of a fire.
The control and indicating panel should be installed as close as possible to the fire brigade
operating panel.
The maximum cable length for the loop/spur peripherals should also be taken into account
when selecting the location of the control and indicating panel.
It may be advisable to install a number of SIGMASYS C control and indicating panels in the
case of large-scale objects.
The alarm system’s operator terminal should be permanently monitored by trained personnel.
If this is not possible for operational reasons, alarm and fault signals must be forwarded to a
responsible service (see DIN VDE 0833).
12 / 128
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Summary of Contents for SIGMASYS C
Page 4: ......
Page 30: ......
Page 38: ......
Page 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 48: ......
Page 62: ......
Page 84: ......
Page 110: ......
Page 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 130: ......
Page 132: ......
Page 134: ......
Page 137: ......