Digital Inputs
Number
1
External operating voltage
DC 24 V to 30 V continuous signal
DC 30 V to 60 V periodic
0.5 s ON time and 4.5 s OFF time
Digital Outputs
Number
2
Type
Dry contact
Maximum switching capacity
2000 VA (AC, resistive)
240 W/30 V DC (DC, resistive)
Permissible current per contact (continuous)
8 A
Permissible current per contact (switching)
8 A
Dimensions
Type of fixing
Panel flush mounting
Cut-out (W x H)
92+0.8 mm x 45+0.8 mm
Overall depth
109.5 mm
Permissible switch panel thickness for installation
2 mm to 4 mm
Mounting position
Horizontal
Weight
≤ 500 g
Environment
Operating temperature range
-40 °C to +70 °C
Storage temperature range
-25 °C to +55 °C
Humidity range
0 % to 95 %, non-condensing
Altitude above sea level
Maximum up to 2000 m
Protection Device Class
Device front
IP 40
Device rear
IP 20
Power Consumption
DC 24 V/AC 230 V
0.8 W
Peak power during power on
6.0 W
i
i
NOTE
When the auxiliary power supply fails, the device is switched on with an internal battery. In this low-power
mode, the device has limited functionality.
In the low-power mode, you can reset a fault, set parameters, and view events/records. In this mode, meas-
urements, fault detection, and communication functions are not available.