Register-Type Data – Holding Registers
Modbus Frame Configuration
(Address 1) This register defines the Modbus frame configuration.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
No Parity
0
Even Parity
1
Odd Parity
2
Default
0
Modbus Baud Rate
(Address 2) This register defines the Modbus baud rate.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Range
0 to 6
Baud rate (bps)
0
1
2
3
4
5
6
2400
4800
9600
19200
38400
57600
115200
Default
6
115200 bps
Modbus ID
(Address 4) This register defines the Modbus ID.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Range
1 to 247
Default
247
Date and Time
(Address 5 to 8) The format used for date and time complies with EN60870-5- 4:1993. It consists of 4 succes-
sive registers for writing in one request. It uses the function code 16.
(Address 5)
B.4
Modbus Registers
B.4 Register-Type Data – Holding Registers
110
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019