Measured Values
Table 1-4
Mapping for Measured Values
Index
MQTT
Name Q200
(Description)
Name IEC61850 (Name)
Unit
1P
3W1I
3W3I
3W2I
4W1I
4W3I
56
Va
PQA2MMXN1$MX
$Vol
–
–
–
PQA2MMXU1$MX$PhV
$phsA
V
57
Vb
–
–
–
–
–
PQA2MMXU1$MX
$PhV$phsB
V
58
Vc
–
–
–
–
–
PQA2MMXU1$MX
$PhV$phsC
V
59
Vab
–
PQA2MMXU1$MX$PPV
$phsAB
–
PQA2MMXU1$MX
$PPV$phsAB
V
60
Vbc
–
PQA2MMXU1$MX$PPV
$phsBC
–
PQA2MMXU1$MX
$PPV$phsBC
V
61
Vca
–
PQA2MMXU1$MX$PPV
$phsCA
–
PQA2MMXU1$MX
$PPV$phsCA
V
62
Ia
PQA2MMXN1$MX
$Amp
PQA2MMXU1$MX$A$phsA
A
63
Ib
–
–
PQA2MMXU1$
MX$A$phsB
–
PQA2MMXU1$MX
$A$phsB
A
64
Ic
–
–
PQA2MMXU1$
MX$A$phsC
–
PQA2MMXU1$MX
$A$phsC
A
65
VN
–
–
–
–
PQA2MMXU1$MX$PhV
$neut
V
66
Vavg
–
PQA2MMXU1$MX$PhV
$net
–
PQA0MMXU1$MX
$PhV$net
V
67
IN
–
–
–
–
–
PQA2MMXU1$MX
$A$neut
A
68
Iavg
–
–
PQA2MMXU1$
MX$A$net
–
PQA2MMXU1$MX
$A$net
A
69
Pa
PQA2MMXN1$MX
$Watt
PQA2MMXU1$MX$W$phsA
W
70
Pb
–
–
PQA2MMXU1$
MX$W$phsB
–
PQA2MMXU1$MX
$W$phsB
W
71
Pc
–
–
PQA2MMXU1$
MX$W$phsC
–
PQA2MMXU1$MX
$W$phsC
W
72
P
–
PQA2MMXU1$MX$TotW
W
73
Qa
PQA2MMXN1$MX
$VolAmpr
PQA2MMXU1$MX$VAr$phsA
var
74
Qb
–
–
PQA2MMXU1$
MX$VAr$phsB
–
PQA2MMXU1$MX
$VAr$phsB
var
75
Qc
–
–
PQA2MMXU1$
MX$VAr$phsC
–
PQA2MMXU1$MX
$VAr$phsC
var
76
Q
–
PQA2MMXU1$MX$TotVAr
var
77
Sa
PQA2MMXN1$MX
$VolAmp
PQA2MMXU1$MX$VA$phsA
VA
78
Sb
–
–
PQA2MMXU1$
MX$VA$phsB
–
PQA2MMXU1$MX
$VA$phsB
VA
79
Sc
–
–
PQA2MMXU1$
MX$VA$phsC
–
PQA2MMXU1$MX
$VA$phsC
VA
1.5
Data-Points Mapping
1.5 Measured Values
SICAM, Class A Power Quality Instrument and Power Monitoring Device SICAM Q200 7KG97, Manual
15
E50417-H1040-C621-A2, Edition 01.2020