4 Measured Quantities and Recording
4.2 Measured Quantities
68
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
4.2.3
Recording and Evaluation of Measured Quantities
4.2.3.1
Recording and Evaluation of the Operational Measured Quantities
Table 4-15
Recording and Evaluation of the Operational Measured Quantities
Measured
Quantity
Measurement Recorder
1)
Event
Recorder
2)
Fault
Recorder
3)
Trend
Recorder
4)
Mains
Signalling
Voltage
Recorder
6)
AVG
Max.
Value
Min.
Value
Values
PQDIF, CSV
COMTRADE
7)
PQDIF
COMTRADE
7)
Alternating Voltage
Va
x
x
x
x
x
x
-
Vb
x
x
x
x
x
x
-
Vc
x
x
x
x
x
x
-
Vab
x
x
x
x
x
x
-
Vbc
x
x
x
x
x
x
-
Vca
x
x
x
x
x
x
-
V
N
x
x
x
-
x
-
-
Vavg
x
-
-
-
-
-
-
Neg.seq.comp.
V
x
x
x
-
-
-
-
Zero
seq.comp.V
x
x
x
-
-
-
-
Alternating Current
Ia
x
x
x
-
x
-
-
Ib
x
x
x
-
x
-
-
Ic
x
x
x
-
x
-
-
I
N
x
-
-
-
-
-
-
Iavg
x
-
-
-
-
-
-
Neg.seq.comp.
I
x
x
x
-
-
-
-