13 Technical Data
13.1 General Device Data
325
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
13.1.4
Environmental Conditions and Climatic Stress Tests
Environmental Conditions
Climatic Stress Tests
Temperature data
Operating temperature
Devices with display: the legibility of the display is
impaired at temperatures < 0 °C (+32 °F).
-25 °C to +55 °C
-13 °F to +131 °F
Temperature during transport
-40 °C to +70 °C
-40 °F to +158 °F
Temperature during storage
-40 °C to +70 °C
-40 °F to +158 °F
Maximum temperature gradient
20 K/h
Air humidity data
Mean relative humidity per year
75 %
Maximum relative humidity
95 % 30 days a year
Condensation during operation
Not permitted
Condensation during transport and storage
Permitted
Altitude and operation
site
Max. altitude above sea level
2000 m
Operation site
Only indoors
Standards: IEC 60068
Dry cold:
IEC 60068-2-1 test Ad
Dry heat during operation, storage, and transport:
IEC 60068-2-2 test Bd
Damp heat:
IEC 60068-2-78 test Ca
Change of temperature:
IEC 60068-2-14 test Na and Nb