12 Failures and LED Indications
12.2 Commissioning during Failures
310
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Starting the User Interface without Uploading a New Firmware
✧
Click
Run Application
. The following message appears:
Figure 12-2
Boot Loader Message of Run Application
✧
Wait for at least 20 s and then click the
home
link.
The user interface opens.
Starting the User Interface with Uploading a New Firmware
✧
Click
Browse...
.
The
Choose file
dialog opens.
✧
Select the desired firmware package in the directory.
✧
Click
Open
.
The selected path appears in the
Browse...
field.
✧
Click
upload
.
If the firmware upload is successful, the following information is displayed in the Boot Loader window:
Figure 12-3
Information in the Boot Loader
✧
Wait for at least 30 s and then click the
home
link.
The user interface opens.
12.2.2
Manual Start of the Boot Loader
If it is necessary to start the Boot Loader manually, proceed as follows:
✧
If the SICAM Q100 is still energized by the supply voltage, switch off the supply voltage.
✧
At the SICAM Q100, press the softkey F4 (see Chapter 6.7.3), keep the softkey F4 pressed, and switch
on the supply voltage.