8 Operation at Use of a PC
8.3 Configuration of the Device
210
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.7.5
SICAM Subdevices
The internal Ethernet switch and a Y cable or an external Ethernet switch can be used to connect up to 2 sub-
devices of the type SICAM I/O Unit 7XV5673 to SICAM Q100. The communication takes place with the Modbus
UDP protocol. For further information and connection examples, refer to the System Manual SICAM Q100,
chapter 2.
8.3.7.5.1
SICAM Subdevice – Parameterization in SICAM Q100
Default Settings and Settings of the SICAM Subdevices
Table 8-30
Settings of the SICAM Subdevices
Parameter/Indications
Default Setting
Setting Range
Subdevice 1
-none-
No further indications are
displayed.
-none-
SICAM IO
Subdevice 2
Subdevice 1
Server IP address
192.168.0.56
any
(different from IP address of subde-
vice 2 and in the same subnet as
SICAM Q100)
Server port
51 000
10 000 to 65 535
Response timeout
3 (* 10 ms)
10 ms to 60 000 ms
0 ms = invalid
Parameter: Source of output 1-N
Indication: Input 1-N
Indication 3 from Remote
Binary inp. 1-N SICAM IO 1
Indication: any, max. 31 characters
Parameter Source of output:
Selection which indication is trans-
mitted from SICAM Q100 to the
binary output of the SICAM I/O Unit
7XV5673.
Indication Input:
Designation of the indication which
shows the status of the binary input
of SICAM I/O Unit 7XV5673.
Parameter: Source of output 2-N
Indication: Input 2-N
Indication 4 from Remote
Binary inp. 2-N SICAM IO 1
Parameter: Source of output 3-N
Indication: Input 3-N
Indication 5 from Remote
Binary inp. 3-N SICAM IO 1
Parameter: Source of output 1-P
Indication: Input 1-P
Indication 6 from Remote
Binary inp. 1-P SICAM IO 1
Parameter: Source of output 2-P
Indication: Input 2-P
Indication 7 from Remote
Binary inp. 2-P SICAM IO 1
Parameter: Source of output 3-P
Indication: Input 3-P
Indication 8 from Remote
Binary inp. 3-P SICAM IO 1