
8 Operation at Use of a PC
8.3 Configuration of the Device
170
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.3
Recorder Parameter
Default Settings and Setting Ranges
1)
The interval of aggregated values of harmonics and interharmonics will always synchronize with the setting
of Average interval in Measurement recorder.
Table 8-14
Recorder Parameter
Parameter
Default Setting
Setting Range
Measurement Recorder
Average intervals - Frequency
10 s
fixed
Short term flicker
10 min
fixed
Long term flicker
2 h
fixed
Average interval - Voltage,
Unbalance and Harmonics
10 min
30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no
no
yes
Recorder of average - Min
no
no
yes
Recorder of average - Max
no
no
yes
Harmonics parity
Odd
Even
Odd
All
File generation every:
1)
(corresponds to the setting of
the
Average interval
parame-
ter)
The created PQDIF files can be
downloaded via the user inter-
face or with the IEC 61850 pro-
tocol.
24 h
At average interval
File generation
every:
30 s
1 h (fix)
1 min
2 h (fix)
10 min, 15 min,
30 min, 1 h or
2 h
2 h
4 h
6 h
12 h
24 h
Recorded file type
PQDIF
PQDIF (see chapter 8.4.2.5)
CSV
All
Flicker lamp model
230 V
230 V
120 V
Trend Recorder
Tolerance unit
Percentage
Percentage
Numerical
Tolerance number
Percentage: 3 % of primary
nominal voltage,
Numerical: 0.5 V
1 % to 5 % in 1-% steps
0.2 V to 500.0 V
Maximum recording interval
10 min
10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h