8.3.5.1
Load Profile
Default Settings and Setting Ranges
1)
Number = 1: Fixed Block method: The lengths of the subperiod and of the measuring period are identical.
Number = 2 to 5: Rolling Block method
Length of the subperiod: The length of the subperiod is an integer part of a full hour.
Length of measuring period: The length of the measuring period cannot be configured directly. It is defined
as the product of the length of the subperiod and the number of subperiods:
Length of measuring period = n x length of subperiod; n = number of subperiods
2)
Under 3-wire Network (Delta), the selection of Q1 should not be used.
Parameterizing the Load Profile
To change the
Load profile
settings, proceed as follows:
✧
In the navigation window of the
Energy management
menu click
Load profile
.
Figure 8-41
Configure Tab, Load Profile Input/Output Window
Table 8-10
Load Profile
Parameter
Default Setting
Setting Range
Subperiode time
15 minutes
1 min to 6 min in 1-min steps, 10 min, 12 min,
15 min, 20 min, 30 min, 60 min
Number of subperiods
1)
1
1 to 5
Synchronization source
Internal clock
None
Protocol
Binary input 1
Binary input 2
Internal clock
Kind of used reactive
power
Q1
Q1
2)
Qn
Qtot