16 Operating Parameters
16.5 Recording and Reporting
418
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
1)
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and
2-wire connections.
2)
The frequency “YYY” and limit “xxx” are based on the configured frequency.
16.5.7
Recording Control
16.5.8
Transient Detection
Supply voltage interruptions:
1. Short interruption until 1 second duration
2. Short interruption until 3 minute duration
3. Long interruption longer than 3 minute duration
Any setting for user-defined
evaluation mode
Harmonic voltages:
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
Any setting for user-defined
evaluation mode
Mains signaling voltages
2)
Supply voltage should be in -15.0 % to +15.0 % deviation of the nominal/
declared supply voltage
99.0 % of “YYY” Hz mains signaling voltage should be less than “xxx” %
of the nominal/declared supply voltage
Any setting for user-defined
evaluation mode
Parameter
Default Setting
Setting Range
Start record option
Start next 10th minute
Start next minute
Start next 10th minute
Start immediately
Start next hour
Start next day
Start time
-
Display of the start time in:
Depends on the configuration of Date/time
format.
Recording status
-
Not settable
Status display of recorder started or recorder
stopped
Parameter
Default Setting
Setting Range
Transient reference level
110 %
110 % to 240 % of Primary nominal voltage