16 Operating Parameters
16.5 Recording and Reporting
415
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.5.4
Mains Signaling Voltage
16.5.5
Memory Management
Tolerance unit
Percentage
Percentage
Numerical
Tolerance number
Percentage: 3 % of primary
nominal voltage,
Numerical: 0.50 V
1 % to 5 % in 1-% steps
0.2 V to 500.0 V
Maximum recording interval
10 min
10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h
Parameter
Default Setting
Setting Range
Mains signaling voltage measurement
MSV active
no
no
yes
No. of MSV frequencies
1 frequency
1 frequency
2 frequencies
Frequency 1
216.60 Hz
100 Hz to 3 kHz
Frequency 2
1060.00 Hz
100 Hz to 3 kHz
Mains signaling voltage capture setting
Detection threshold
1 % of Udin
From 1 % to 15 % of Udin
Total recording duration
75 s
15 s to 120 s in 15-s steps
Pretrigger ratio
10 %
0 % to 30 % in 5-% steps
Parameter
Default Setting
Setting Range
Memory splitting
Event recorder
1.0 %
1 % to 19 %
Measurement recorder
35.0 %
(the recording time depends on
the aggregation interval)
33 % to 51 %