16 Operating Parameters
16.5 Recording and Reporting
413
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.5.2
Trigger Management
1)
The detection mode will always synchronize with the setting of Record ph-ph voltage.
Parameter
Default Setting
Setting Range
Voltage trigger limits
Trigger active
no
no
yes
Tolerance unit
Percentage
Percentage
Numerical
Lower threshold
90.00 %
of the nominal/declared
supply voltage
0.00 % to 99.99 % of the nominal/declared
supply voltage
0.0 V to 1 000 000.0 V
Upper threshold
110.00 %
of the nominal/declared
supply voltage
100.0 % to 10 000.0 % of the
nominal/de-
clared supply voltage
0.0 V to 1 000 000.0 V
Hysteresis
2.00 %
of the nominal/declared
supply voltage
0.0 % to 50.0 % of the nominal/declared
supply voltage
Detection mode
1)
ph-N
ph-N
ph-ph
Current trigger limits
Trigger active
no
no
yes
Tolerance unit
Percentage
Percentage
Numerical
Lower threshold
90.00 %
of nominal current In
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
Upper threshold
110.00 %
of nominal current In
100.0 % to 10 000.0 % of of nominal
current In
0.0 A to 1 000 000 A
Hysteresis
2.00 %
of nominal current In
0.0 % to 50.0 % of of nominal current In
Configuration binary trigger
Trigger active
no
no
yes
Trigger source
Binary Input 1
Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
Trigger value
OFF
ON
OFF
Waveform capture setting
Total recording duration
2.0 s
0.2 s to 3.0 s in 0.2-s steps
Pretrigger ratio
10 %
0 % to 30 % in 5-% steps
Record ph-ph voltage
no
no
yes