9 Operation at Use of a PC
9.3 Configuration of the Device
263
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.7.8 Syslog
In addition to showing audit logs in the
Maintenance
tab via the user interface, the device supports transmitting
the audit logs to a central log server using Syslog.
Syslog is a well-established internationally implemented standard for message logging.
Syslog allows the separation of the following:
•
The software that generates messages
•
The system that stores messages
•
The software that reports and analyzes messages
Computer system designers can use Syslog for system management and security auditing as well as general
informational, analysis, and debugging messages. Various devices, such as printers, routers, and message
receivers across many platforms use the Syslog standard. For example, a Q100 device works as a device and
a Kiwi Syslog service manager works as a receiver.
9.3.7.8.1
Basic Settings
Default Settings and Setting Ranges of the Syslog
Table 9-42
Settings of the Syslog
Parameter
Default Setting
Setting Range
Syslog active
No
No
Yes
If you set the
Syslog active
parameter to
yes
, the following parameters are visible:
Primary Syslog server
0.0.0.0
Any
Port
514
0 to 65 535
Secondary Syslog server
0.0.0.0
Any
Port
514
0 to 65 535
MAN_SICAM_Q100_US.book Page 263 Wednesday, June 5, 2019 9:31 AM