Installation and Wiring
5.1 Overall Dimension
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-
4
, Release Date
06.2018
32
5.1
Overall Dimension
The figure below shows the overall dimension of this product. Panel cut out size: 92 mm×92 mm
Figure 5-1
Overall Dimension of Instrument
5.2
Precautions of Installation
1. Dry and well ventilated environment far away from thermal source and strong electric (magnetic) field is rec-
ommended for installation of this product.
2. Ambient temperature: -25
℃
to +60
℃
, humidity:
≤
95% (no condensation)
3. This product should be firmly mounted to avoid accident arising from vibration.
4. For the reason of convenient installation, maintenance and operation and safety, enough space around this
product should be reserved during installation (especially when one panel for multiple meters).
5. Requirement for electric wiring: Stranded fire-retarded copper wire over 2.5 mm
2
should be used for current
circuit, 1.5 mm
2
stranded fire-retarded copper wire should be used for voltage circuit and power supply circuit,
and 1.0 mm
2
Shielded Twisted Pair should be used for RS485 communication.
6. Requirement for electric connection: In voltage input circuit and operating power supply circuit, appropriate
fuses (such as 0.5 A fuse) should be connected and a CT short-circuit box should be provided to prevent
open circuit of CT wiring.