5
5.7 Input / Output Modules
98
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5.7.5
Analog Inputs (optional)
The analog inputs (optional) allow you to measure analog signals in the range of 0 mA to 20 mA.
Proceed as follows:
1. Activate/Deactivate one or both analog inputs by ticking the corresponding check box under
1.
and/or
2.
2. For each input used, set the
Designation
together with the
Dimension
(max. 6 characters).
3. You define the range of values of the signal in the fields
from
and
to
.
4. The device display will be parameterized via screen contents, the supervision of limit values
concerning the analog inputs via limit value groups.
Note
It is possible to save the values (together with the time information) recorded via analog inputs
to the memory for mean values (see chapter 5.9.2).