3
3.4 View of Measured Quantities and Error Limits
51
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
3.4
View of Measured Quantities and Error Limits
Table 3-3
Measured values and tolerances
Measured Values
Measuring Path
1
Menu
Tolerances
2
Voltage L1-N,
L2-N,
L3-N
±
0.2 %
Voltage
L1-L2, L2-L3, L3-L1,
Σ
3
±
0.2 %
Current
L1, L2, L3, N,
Σ
3
±
0.2 %
Active power P
+ demand, - supply
L1, L2, L3,
Σ
±
0.5 %
Reactive power Q
+ cap, - ind
L1, L2, L3,
Σ
±
0.5 %
Apparent power S
L1, L2, L3,
Σ
±
0.5 %
Power factor |cos
ϕ
|
4
L1, L2, L3,
Σ
±
0.5 %
Active power factor cos
ϕ
4
L1, L2, L3,
Σ
±
0.5 %
Phase angle
4
L1, L2, L3,
Σ
±
2°
System frequency
5
L1-N
±
10 mHz
Active energy demand
L1, L2, L3,
Σ
±
0.5 %
Active energy supply
L1, L2, L3,
Σ
±
0.5 %
Active energy total
L1, L2, L3,
Σ
±
0.5 %
Active energy net demand
Σ
±
0.5 %
Reactive energy cap
L1, L2, L3,
Σ
±
0.5 %
Reactive energy ind
L1, L2, L3,
Σ
±
0.5 %
Reactive energy total
L1, L2, L3,
Σ
±
0.5 %
Apparent energy
L1, L2, L3,
Σ
±
0.5 %
Unbalance voltage
Four-wire system
±
0.5 %
Unbalance current
Four-wire system
±
0.5 %
THD voltage
L1, L2, L3
±
0.5 %
THD current
L1, L2, L3
±
0.5 %
Harmonic voltage
5., 7., 11., 13., 17. and 19. H.
L1, L2, L3
±
0.5 %
Harmonic current
5., 7., 11., 13., 17. and 19. H.
L1, L2, L3
±
0.5 %
Limit violation
Counter 1 to 4
Analog input
6
external
±
0.5 %
Binary input
6
external