1.6 Interface and Terminals
26
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
1.6.4
Connection Examples
1.6.4.1
General
The following are examples of current and voltage input connections (according to DIN 43807).
The device can be connected without current or voltage transformers as long as the maximum
voltage and current ratings of the device are not exceeded.
The voltage transformers can be connected in wye or open-delta configurations.
All input and/or output terminals not required for a particular input voltage and current configura-
tion are not used.
1.6.4.2
Single-phase
Note
The single ground connection of the instrument transformers is shown for illustration only. Actual
grounds must be installed directly at each instrument transformer.
a
N
P1
P2
S1
S2
PE
10 A