8
8.1 SICAM P 7KG7750
140
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
8.1.2
Test Data
Reference Conditions
8.1.2.1
Electrical Tests
Standards
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Reference cond itio ns
The stated error limits apply for reference
conditions
Input current I
i
I
iN
± 1 %
Input voltage U
i
U
i N
± 1 %
Frequency f
i
45 Hz to
65
Hz
Waveform Sinus,
harmonic
distortion
≤
5 %
Ambient temperature T
A
23 °C ± 1 °C
Auxiliary voltage U
H
U
H N
± 1 %
Warm-up time
≥
15 min
External fields
no
Standards:
IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
Inputs/Outputs
Insulation
Rated
Voltage
ISO Test
Voltage
Category
Current measurement
inputs (E)
Reinforced
150 V
AC 2.21 kV
Cat. III
Voltage measurement
inputs (F)
Reinforced
480 V
Surge voltage
9.76 kV
Cat. III
Supply voltage (H)
Reinforced
300 V
DC 3.125 kV
Cat. III
Binary outputs (G)
Reinforced
300 V
AC 3.51 kV
Cat. III
RS485 interface
SELV
< 50 V
DC 700 V
Input-/Output module (A)
- Binary input
- Binary output
- Relay output
Reinforced
150 V
AC 2210 V
Cat. III
Input-/Output module (A)
- Analog input
- Analog output
SELV
< 50 V
DC 700 V