6 Connection Principle and Applications
6.4 Application Examples SICAM MMU with SICAM I/O Unit 7XV5673
71
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
6.4
Application Examples SICAM MMU with SICAM I/O Unit 7XV5673
6.4.1
Direct Connection of a SICAM MMU to a SICAM I/O Unit 7XV5673 and
Connection to the Control Center
You can use a Y-cable and the internal Ethernet switch of the SICAM I/O Unit 7XV5673 to connect the SICAM
MMU to the SICAM I/O Unit 7XV5673. The second connector of the Y-cable enables you to connect this device
combination to the control center via an external Ethernet switch. The following figure illustrates the cabling of
the devices and the possible transmission protocols.
Fig. 6-13
Direct Connection of a SICAM MMU to a SICAM I/O Unit 7XV5673 via a Y-Cable
SICAM MMU
SICAM I/O Unit
IEC 60870-5-104,
HTTP, NTP
Y-Cable
IEC 60870-5-104,
HTTP, NTP
IEC 60870-5-104
NTP
HTTP
Ethernet
Switch
NTP Server
Diagnosis/
Configuration
Redundant
IEC 60870-5-104
Master
IEC 60870-5-104
Primary
IEC 60870-5-104
Master
3~ V/I Inputs,
2 Binary Outputs
6 Binary Inputs,
6 Binary Outputs
and Modbus UDP
between SICAM MMU
and SICAM I/O Unit
SICAM-MMU_7KG9663_US.book Page 71 Monday, December 7, 2015 12:22 PM