7 Operation
7.3 Configuration of the Device
122
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
7.3.4.3.2
Parameter Settings of the SICAM I/O Unit (Subdevice)
Settings of the Ethernet Communication of the SICAM I/O Unit
NOTE
A detailed description of all parameter settings of the SICAM I/O Unit 7XV5673 and a description of that device
is given in the Device Manual, order number E50417-H1040-C484.
Table 7-13
Settings of the Ethernet Communication in the SICAM I/O Unit Subdevice
Parameter
Default Setting
Setting Range
IP address
192.168.0.55
At
IP address
, enter the same IP address as in
SICAM MMU
→
I/O Unit subdevice
under
Server
IP address
.
SICAM MMU and SICAM I/O Unit must have differ-
ent IP addresses.
Subnet mask
255.255.255.0
Identical to the subnet mask of the SICAM MMU
Default gateway
192.168.0.1
Any
Ethernet switch on
no
Selection of the second port of the internal Ethernet
switch
Bus protocol/Operating
mode
I/O Mirror server
You must select
I/O Mirror Server
for connection
to the SICAM MMU.
Operating Mode I/O Mirror Server
Port number
51000
Port number for the Ethernet communication
between SICAM MMU and SICAM I/O Unit
Communication super-
vision time
8 *10 ms
-