Service
SICAM RTUs, SICAM AK 3 User Manual
233
DC2-028-2.03, Edition 07.2016
5.5.2
Errors with Loading of Firmware
For a perfect functioning of the master control element, it is absolutely necessary that the
loading procedure completes without errors.
If the tool "Load Firmware" terminates with an error indication, cancel it. Afterwards start the
loading procedure again and attempt to complete without error. If an error occurs again, check
the record in the diagnosis and the lighted display on the master control element.
The following reasons lead to a malfunction of the master control element:
•
Voltage failure during loading procedure
•
Premature abortion by the user during loading procedure
•
Failure (defect, shutdown) of the engineering PC
•
Abortion due to hardware error
•
Abortion or excessively long fault of the communication connection between engineering
PC and SICAM AK
Further technical information can be found in the manual
SICAM RTUs Common Functions
System and Basic System Elements, chapter "System Services", sections "Loading Opera-
tion" and "Firmware Shutdown"
.
Note
A master control element that is no longer capable of functioning can be recognized by the fact, that after
a restart of the SICAM AK 3 the yellow RDY LED does not light up and the red ER LED and the yellow
HLT LED do not turn off any more. An access with the SICAM TOOLBOX II is no longer possible in this
case.
In this case please consult:
SIEMENS AG
Energy Customer Support Center
Phone: + 49 180 524 70 00
Fax:+ 49 180 524 24 71
mailto:[email protected]
http://www.siemens.com/energy-support/de
Summary of Contents for SICAM AK 3
Page 8: ...Open Source Software 8 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Page 84: ...Installation 84 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Page 166: ...System Components 166 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Page 180: ...Prepare Engineering 180 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...