Trend Records
Function Description
i
i
NOTE
This function is only available in SICAM P855.
The function Trend records ensures the acquisition and long-term monitoring of the voltage V
rms
(1/2-cycle)
values during voltage changes. The function Trend records compares the 1/2-cycle RMS value calculated from
measured value with last recorded 1/2-cycle RMS value in every 1/2 cycle. If the difference exceeds or falls
below the Tolerance number, the new 1/2-cycle RMS value is recorded.
[dw_trend_rec_Vrms, 2, en_US]
Figure 6-25
Example for Voltage Changes
Once the measuring interval ends, the next measuring interval starts automatically. You can set the following
parameters via the Web pages:
•
Tolerance number
•
Maximum recording interval
Table 6-20
Recording and Evaluation
Measured Quantities
PQDIF
Va
x
Vb
x
Vc
x
Vab
x
Vbc
x
Vca
x
•
Interfaces: protocols IEC61850, HTML
•
Conditions: 1/2 cycle, RMS values
6.7
6.7.1
Power Quality
6.7 Trend Records
144
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Summary of Contents for SICAM 7KG85X
Page 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...