Parameter
Default Setting
Setting Range
Tolerance unit
Percentage
Percentage
Numerical
Upper threshold
110.00 % of the primary nominal
voltage
100.0 % to 120.0 % of the primary
nominal voltage
Lower threshold
90.00 % of the primary nominal voltage 0.00 % to 99.99 % of the primary
nominal voltage
Hysteresis
2.00 % of the primary nominal voltage
0.0 % to 50.0 % of the primary nominal
voltage
Current trigger limits
Trigger active
No
No
Yes
Tolerance unit
Percentage
Percentage
Numerical
Upper threshold
110.00 % of nominal current
5.0 % to 200.0 % of the nominal
current
Lower threshold
90.00 % of nominal current
0.00 % to 99.99 % of the nominal
current
Hysteresis
2.00 % of the nominal current
0.0 % to 50.0 % of the nominal current
Waveform capture setting
Total recording duration
2.0 s
0.2 s to 3.0 s, increments of 0.2 s
Pretrigger ratio
10%
0 % to 30 %, increments of 5 %
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to
).
•
Click Activation.
Error Information
If the set value is out of the range, a red error message Note: Please consider the setting ranges! appears
and the value changes back to the default setting.
If the set values do not follow the setting rules, a red error message Note: Consider setting rules: 'upper
threshold > lower threshold' and (upper threshold - lower threshold) > 2 * hysteresis appears and the
value changes back to the previous setting.
Value View of the Waveform Records
You cannot view the waveform records triggered by the other sources via the Web browser, but you can
download them. For more information, refer to chapter
During the download progress, the selected files are stored by the browser. You can use the software SIGRA to
display the transmitted record data. For more information on SIGRA, contact the Siemens Hotline.
Clearing of Waveform Records
To clear waveform records, refer to chapter
6.5.3
Power Quality
6.5 Waveform Records
SICAM, SICAM P850/P855 7KG85X, Manual
137
E50417-H1040-C482-A9, Edition 03.2022
Summary of Contents for SICAM 7KG85X
Page 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...