Event Records
Function Description
Using the device you can record the following events:
•
Voltage events
•
Frequency events
•
Voltage unbalance events
Table 6-7
Recording and Evaluation
Measured Quantities
Values
Va
x
Vb
x
Vc
x
Vab
x
Vbc
x
Vca
x
•
Interfaces: protocols IEC 61850 and Modbus TCP, HTML, display determining overvoltage, undervoltage
and voltage interruption according to EN 50160 (only SICAM P855), for example.
Voltage Events
Function Description
The device detects voltage events (dips, swells, interruptions) based on 1/2-cycle RMS values according to
IEC 61000-4-30 Edition 3.0.
The device works as follows:
•
It determines the start of events with the threshold value.
All thresholds are related to the primary nominal voltage.
•
It determines the end of voltage events with the voltage considering the hysteresis of the preset
threshold.
6.4
6.4.1
6.4.2
6.4.2.1
Power Quality
6.4 Event Records
SICAM, SICAM P850/P855 7KG85X, Manual
125
E50417-H1040-C482-A9, Edition 03.2022
Summary of Contents for SICAM 7KG85X
Page 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Page 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...