Accessories
9.5 Bridging bars
154
Manual, 08/2017, L1V30368969104A-02
Replacing mounting spacers
The following steps are necessary for replacing additional mounting spacers.
1.
Remove the bolts from the existing mounting spacers of the transfer switching equipment.
2.
Remove the existing mounting spacers.
3.
Fit the new mounting spacers with the available bolts.
9.5
Bridging bars
For current ratings 250 A to 1600 A, bridging bars can be mounted for implementing an
upstream or downstream connection point. They serve as a bridge for the load-side
connection and they can be attached either on the top or bottom of the transfer switching
equipment.
The bridging bars for current ratings 250 A to 630 A and 800 A to 1600 A comprise one
bridging bar as well as the bolts, nuts and washers for mounting.
These must be ordered separately for connecting to the connecting terminals. Please note
here the section titled Connecting bridging bars on the load side (Page 42)
To install the device, 3 or 4 bridging bars must be mounted depending on the number of
poles.
Figure 9-11 Bridging bar 250 A to 630 A
Figure 9-12 Bridging bar 800 A to 1600 A
There is only 1 bridging bar per product number pack so 3 or 4 packs must be ordered.
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...