Operation
7.2 Functions of the inputs and outputs
Manual, 08/2017, L1V30368969104A-02
111
7.2.1.1
Outputs of the motor operator
The outputs of the motor operator are located in the following position:
Figure 7-10 Outputs of the motor operator
Designation
Pin Meaning
Explanation
Properties
Recommended
cable cross-section
Outputs
of motor opera-
tor
04
0
Auxiliary contact position O – nor-
mally open
Floating contacts 2 A
AC1 / 250 V
1.5 - 2.5 mm
2
13
C
Common control terminal for pins
04, 14 and 24
14
I
Auxiliary contact position I – nor-
mally open (NO) contact
24
II
Auxiliary contact position II – nor-
mally open (NO) contact
63A AVAIL.
Availability of the motor operator:
•
Opened if the motor operator of
the transfer switching equip-
ment is not available.
•
Closed if the switch on the
motor operator is at the "Auto"
position and the motor is ready
64A