Data traffic
6.3 Acyclic data traffic
PROFINET Proxy SPP2000
48
Equipment Manual, 03/2022, L1V30814715D-01
6.3.4
DS47 data set for flexible read access
You can flexibly read access the data scope of the SENTRON PAC devices you are using by
means of data set DS47.
This data set only applies to the SENTRON PAC devices. The corresponding slot/subslot
address must therefore be used for writing and reading.
Table 6- 7
Structure of data set DS47 – read request
Byte
Length
(bits)
Format
Data
(examples)
Description
0
16
Unsigned short
0x0001
Register address for value 1 *
2
8
Unsigned char
0x00
Device address 1 **
3
8
Unsigned char
0x02
Register number 1 ***
4
16
Unsigned short
0x0321
Register address for value 2 *
6
8
Unsigned char
0x00
Device address 2 **
7
8
Unsigned char
0x04
Register number 2 ***
...
max. 240
* You can find the register address of the measured variable or the status in the manual for the device
you are using.
** Internal device address.
For SPP2000 = 00.
The lower-level PAC devices are addressed via slot/subslot for the entire data set. For this reason,
always enter the value "0".
*** Enter the number of registers here. One register is the equivalent of 2 bytes; two registers are the
equivalent of 4 bytes, etc.
Table 6- 8
Structure of data set DS47 – read response
Byte
Length
(bits)
Format
Data
(examples)
Description
0
16
Float
65.6
Value 1, e.g. current L1
3
8
Double
123456789.01 Value 2, e.g. active energy
import
11
...
...
max. 240
The Read response supplies the requested values in the order of their request.