Connect the cables of the supply voltage on the terminal side of the device at
terminal block H
as follows:
Supply from the Alternating Voltage System
Terminal N/-:
Neutral conductor of the supply voltage
Terminal L/+:
Phase of the supply voltage
Terminal
:
Protective grounding terminal
Supply from a Direct Voltage Source
Terminal N/-:
Negative supply voltage
Terminal L/+:
Positive supply voltage
Terminal :
Protective
grounding
terminal
Terminals
Terminals for supply voltage (H), inputs for current measurement (E), inputs for voltage measurement (F), bi-
nary outputs (G) on the terminal side:
Conductor cross-section, rigid max.
2.5 mm² (AWG 14)
Conductor cross-section (conductor with ferrule)
1.5 mm² (AWG 16)
Conductor cross-section (conductor with ferrule, terminal F)
2.5 mm² (AWG 14)
Tightening torque
0.4 Nm to 0.5 Nm (3.5 in-lb to 4.5 in-lb)
Ethernet interface (Z) on the top side:
Ethernet patch cable or crossover cable
Voltage measuring inputs:
In the case of a
direct connection
and
transformer connection
, the device has
to be safeguarded with a
listed 10 A backup fuse
or a listed 10 A miniature circuit breaker. When using voltage
transformers, their secondary connections must never be short-circuited!
5.4
System Requirements
To operate SENTRON PAC5100/5200 with a PC or notebook, the following system requirements must be met:
•
PC or notebook with Intel Pentium processor (or compatible type); clock frequency min. 800 MHz
•
Operating system: Microsoft Windows XP Professional and Windows 7 with Internet Explorer 6.0 (or
higher)
•
Minimum 1 GB RAM primary storage
•
VGA display 1024 x 768 with truecolor
NOTE
Always connect the grounding at the SENTRON PAC5100/5200 to the terminal for the protective conductor