4 Measurands and Recording
4.3 Display of Measurands
64
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
4.3
Display of Measurands
4.3.1
Measurands and Operational Measurement Uncertainty acc. to IEC 62586-1
Product Standard, Class S, and Standards IEC 61000-4-30, Ed. 2 and
IEC 61000-4-7 and IEC 61000-4-15
Table 4-15 Measurands and their Operational Measurement Uncertainty
Measurands
Unit
Rated Value
Measurement Range
Operat. Measurem.
Uncertainty acc. to
IEC 62586-1, Class S,
IEC 61000-4-30,
IEC 61000-4-7
IEC 61000-4-15
Voltage V
ph-ph
(delta)
Acc. to parameterization
V
AC 110 V
AC 190 V
AC 400 V
AC 690 V
AC 600 V for UL
conditions
0 % to 120 % V
rated
±0.2 %
Voltage V
ph-N
(star)
Acc. to parameterization
V
AC 63.5 V
AC 110 V
AC 230 V
AC 400 V
AC 347 V for UL
conditions
0 % to 120 % V
rated
±0.2 %
Voltage V
N
V
AC 63.5 V
AC 110 V
AC 230 V
AC 400 V
AC 347 V for UL
conditions
0 % to 120 % V
rated
±0.2 %
Voltage unbalance U
2
%
-
0 % to 100 % V
rated
±0.2 %
Frequency f
Hz
50 Hz (±7.5 Hz)
60 Hz (±9 Hz)
42.5 Hz to 57.5 Hz
51.0 Hz to 69.0 Hz
50 mHz
(see Table 4-17)
Flicker Pst, Plt
(only SENTRON PAC5200)
-
-
Pst, Plt: 0,4 to 4
Pinst: 0 to 40
Acc. to class S,
IEC 61000-4-30:
Pst: ±10 %
Plt: ±10 %
Pinst: ±16 %
Harmonics of voltage
H_xV
ph
% or V
-
-
Condition:
V
m
3 % V
rated
Maximum error:
±5 % V
m
-------------------------------
Condition:
U
m
< 3 % V
rated
Maximum error:
±0.15 % V
rated