14 Operating Parameters
14.5 Administrative
259
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.5.2
Ethernet Communication
1)
After the parameter changes have been enabled, the device resets.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
Parameter
Default Settings
Setting Range
IP Address
1)
192.168.0.55
Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0
Any
Default gateway
1)
192.168.0.1
Any
Enable SNMP
no
no
yes
Bus protocol
Modbus TCP
Modbus TCP
-none-
Bus Protocol Modbus TCP
Use a user-port number
2)
no
no
yes
User-port number
2)
(can only be set when
Use a user-port
number
is parameterized with
yes
)
10000
10000 to 65535
Access rights for user port
(can only be set when
Use a user-port
number
is parameterized with
yes
)
Full
Full
Read only
Access rights for user port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms