7 Operation at Use of a PC
7.6 Example of a Parameterization and Measured Value Evaluation for SENTRON PAC5200
184
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.6
Example of a Parameterization and Measured Value Evaluation for
SENTRON PAC5200
7.6.1
Task Definition
✧
Set the parameters via the Ethernet interface using the default IP address set upon delivery of the device.
✧
Configure SENTRON PAC5200 according to the topology.
✧
Parameterize the indication of a measurand limit violation for V
ab
> 11 kV with 10 % hysteresis and name
the indication.
✧
Parameterize a binary output that is switched on for the duration of the measurand limit violation.
✧
Parameterize the Ethernet communication according to the network configuration specified by the system
operator.
✧
Assign any name and specify the time/date format as YYYY-MM-DD and the time in 24-hour format.
✧
Parameterize the Measurement recorder with an averaging time of 2 hours and activate the averaging
recorders for minimum and maximum values. Record all voltage harmonics.
✧
Allocate 50 % storage capacity to the Measurement recorder.
✧
Take over the factory-set report configuration.
✧
Activate the device configuration you have created as the active parameter set.
✧
Perform measurements, acquire the measurand limiting value indication and record the measured values
as defined in the task.
7.6.2
Initial Situation
Topology
•
4-wire system, unbalanced
•
Primary nominal voltage: 400 V
•
Voltage transformer: 10 000 V : 100 V
•
Primary rated current: AC 100 A
•
Current measurement range: 1 A
•
Current transformer: 100 A : 1 A
•
Rated frequency: 50 Hz
•
Communication via Ethernet interface
Network Configuration
•
IP address: 192.168.0.55
•
Subnet mask: 255.255.255.0
•
Default gateway: 192.168.1.1
Summary of Contents for SENTRON PAC5100
Page 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Page 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Page 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...