
Startup
7.3 Parameterizing the device
SENTRON PAC4200
90
Manual, 09/2008, A5E02316180B-01
7.3.4
Voltage input
7.3.4.1
Set the connection type
Inform the device of the connection type executed. To do so, enter the short code for the
connection type in the device settings.
Note
Connection type
The connection type executed must agree with the connection type entered in the device!
Table 7- 2
Available connection types
Short code
Connection type
3P4W
3 phases, 4 conductors, unbalanced load
3P3W
3 phases, 3 conductors, unbalanced load
3P4WB
3 phases, 4 conductors, balanced load
3P3WB
3 phases, 3 conductors, balanced load
1P2W
Single-phase AC
You can find further information on the possible connection types, and on how the measured
value representation depends on the connection type, in the "Description" chapter.
Procedure
1.
Exit the measured value display and call the "MAIN MENU":
<F4>
2.
In the main menu, go to the "SETTINGS" entry:
<F2>
or <F3>
3.
Call the "SETTINGS" entry:
<F4>
4.
In the "SETTINGS" menu, go to the "BASIC PARAMETERS" entry:
<F2>
or <F3>
5.
Call the "BASIC PARAMETERS" entry:
<F4>
6.
In the "BASIC PARAMETERS" menu, call the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
Figure 7-4
"CONNECTION TYPE" device setting
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...