SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
67
Connecting
6
6.1
Safety notes
Instructions
DANGER
Dangerous high voltages
Will cause death, serious injury or property damage.
The country-specific standards for setting up power systems must be taken into account
when carrying out the electrical installation.
The following tasks are partly carried out when hazardous voltage is present. For this
reason, they must only be carried out by qualified personnel who are familiar with and
follow the safety regulations and cautionary measures.
Wear the prescribed protective clothing. Observe the general equipment regulations and
safety regulations for working with high-voltage installations (e.g. DIN VDE, NFPA 70E as
well as national or international regulations).
The limits given in the technical data must not be exceeded even at startup or when testing
the device.
The secondary connections of intermediate current transducers must be short-circuited at
the transducers before the current lines to the device are interrupted.
The polarity and phase assignment of the measuring transducer must be tested.
Before connecting the device, you must check that the system voltage agrees with the
voltage specified on the type plate.
Check that all connections are correctly made before startup.
Ensure the polarity is correct when connecting a DC supply voltage.
Before power is applied to the device for the first time, it must have been located in the
operating area for at least two hours in order to reach temperature balance and avoid
humidity and condensation.
Condensation on the device is not permissible during operation.
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...