Appendix
A.3 MODBUS
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
213
A.3.9
Minimum values with a time stamp and the function codes 0x03 and 0x04
Addressing the minimum values with a time stamp
Table A- 14 Available measured variables: Minimum values with time stamp
Offset Number
of
registers
Name
Format
Unit
Value range
Access
6001
6
Minimum Voltage a-n with Time
Float + time stamp V
-
R
6007
6
Minimum Voltage b-n with Time
Float + time stamp V
-
R
6013
6
Minimum Voltage c-n with Time
Float + time stamp V
-
R
6019
6
Minimum Voltage a-b with Time
Float + time stamp V
-
R
6025
6
Minimum Voltage b-c with Time
Float + time stamp V
-
R
6031
6
Minimum Voltage c-a with Time
Float + time stamp V
-
R
6037
6
Minimum Current a with Time
Float + time stamp A
-
R
6043
6
Minimum Current b with Time
Float + time stamp A
-
R
6049
6
Minimum Current c with Time
Float + time stamp A
-
R
6055
6
Minimum Apparent Power a with Time
Float + time stamp VA
-
R
6061
6
Minimum Apparent Power b with Time
Float + time stamp VA
-
R
6067
6
Minimum Apparent Power c with Time
Float + time stamp VA
-
R
6073
6
Minimum Active Power a with Time
Float + time stamp W
-
R
6079
6
Minimum Active Power b with Time
Float + time stamp W
-
R
6085
6
Minimum Active Power c with Time
Float + time stamp W
-
R
6091
6
Minimum Reactive Power a (VARn) with
Time
Float + time stamp VAR
-
R
6097
6
Minimum Reactive Power b (VARn) with
Time
Float + time stamp VAR
-
R
6103
6
Minimum Reactive Power c (VARn) with
Time
Float + time stamp VAR
-
R
6109
6
Minimum Total Reactive Power a (VARtot)
with Time
Float + time stamp VAR
-
R
6115
6
Minimum Total Reactive Power b (VARtot)
with Time
Float + time stamp VAR
-
R
6121
6
Minimum Total Reactive Power c (VARtot)
with Time
Float + time stamp VAR
-
R
6127
6
Minimum Reactive Power a (VAR1) with
Time
Float + time stamp VAR
-
R
6133
6
Minimum Reactive Power b (VAR1) with
Time
Float + time stamp VAR
-
R
6139
6
Minimum Reactive Power c (VAR1) with
Time
Float + time stamp VAR
-
R
6145
6
Minimum Power Factor a with Time
Float + time stamp -
0 ... 1
R
6151
6
Minimum Power Factor b with Time
Float + time stamp -
0 ... 1
R
6157
6
Minimum Power Factor c with Time
Float + time stamp -
0 ... 1
R
6163
6
Minimum cos φ a with Time
Float + time stamp cos φ
a
-
R
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...