
Description
3.2 Measuring inputs
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
21
See also
Measured variables (Page 22)
Technical data (Page 153)
Sliding window demand values (Page 28)
3.2
Measuring inputs
Current measurement
CAUTION
AC current measurement only
The device is not suitable for measuring DC current.
SENTRON PAC4200 is designed for:
●
Measuring current of 1 A or 5 A for connecting standard current transformers. Each
current measuring input can take a continuous load of 10 A. Surge withstand capability is
possible for currents up to 100 A and a duration of 1 s.
Voltage measurement
CAUTION
AC voltage measurement only
The device is not suitable for measuring DC voltage.
SENTRON PAC4200 is designed for:
●
Direct measurement on the system or using voltage transformers. The measuring voltage
inputs of the device measure direct via protective impedances. External voltage
transformers are required to measure higher voltages than the permissible rated input
voltages.
●
Measuring voltage up to 400 V / 690 V (max. 347 V / 600 V for Vph) on devices with a
wide-voltage power supply. The device is designed for measuring input voltages up to
400 V (347 V for Vph) phase-to-neutral and 690 V (600 V for Vph) phase-to-phase.
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...