Appendix
A.3 MODBUS
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
205
A.3.4
Structure - PMD diagnostics and status with the function codes 0x03 and 0x04
Design
Table A- 5
Overview of status and diagnostics bytes
Byte
Meaning
0
System status
1
Device status
2
Device diagnostics
3
Component diagnostics
Table A- 6
Modbus offset 205, tab 2: Structure of PMD diagnostics and status
Byte Bit
Device status
Type
Bit mask
Value range
Access
0
0
No synchronization pulse
Status
0x01000000
R
0
1
Device Configuration menu is active
Status
0x02000000
R
0
2
Voltage out of range
Status
0x04000000
R
0
3
Current out of range
Status
0x08000000
R
1
0
Module slot 1
Status
0x00010000
R
1
1
Maximum pulse rate exceeded
Status
0x00020000
R
1
2
Module slot 2
Status
0x00040000
R
2
0
Basic configuration changed
1) 2)
Status
0x00000100
R
2
1
Upper or lower limit violation
1) 2)
saving
0x00000200
R
2
2
Maximum pulse rate exceeded
1) 2)
saving
0x00000400
R
2
3
Device has rebooted
1) 2)
saving
0x00000800
R
2
4
Energy counters reset
1) 2)
saving
0x00001000
R
3
0
Bit 0 Slot 1 Parameters changed
2)
saving
0x00000001
R
3
1
Bit 1 Slot 1 IMDATA changed
2)
saving
0x00000002
R
3
2
Bit 2 Slot 1 Firmware update active
2)
saving
0x00000004
R
3
3
Bit 3 Firmware data block available
2)
saving
0x00000008
R
3
4
Bit 4 Bootloader update flag
2)
saving
0x00000010
R
3
5
Bit 5 Slot 2 Parameters changed
2)
saving
0x00000020
R
3
6
Bit 6 Slot 2 IMDATA changed
2)
saving
0x00000040
R
3
7
Bit 7 Slot 2 Firmware update active
2)
saving
0x00000080
0 =
Not active
1 =
active
R
1)
Only these device states are to be acknowledged.
2)
You can use the function codes 0x05 and 0x0F here in addition to the function codes 0x01 and 0x02.
See also
Measured variables without a time stamp with the function codes 0x03 and 0x04 (Page 196)
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...