Technical data
11.1 Technical data
SENTRON PAC4200
158
Manual, 09/2008, A5E02316180B-01
Connection elements
Measuring inputs and supply voltage inputs
Screw-type terminals
Connection designations
IL1(°↑k, l↓), IL2(°↑k, l↓), IL3(°↑k, l↓)
V
1
, V
2
, V
3
, V
N
, L/+, N/-
1-wire or 2-wire connection possible
Conductor cross section
Solid
1 x 0.5 ... 4,0 mm²
AWG 1 x 20 ... 12
2 x 0.5 ... 2,5 mm²
AWG 2 x 20 ... 14
Finely stranded with end
sleeve
1 x 0.5 ... 2,5 mm²
AWG 1 x 20 ... 14
2 x 0.5 ... 1.5 mm²
AWG 2 x 20 ... 16
Stripping length
10 mm
Connection screws
Tightening torque
0.8 ... 1.2 Nm
7 ... 10.3 lbf·in
Tool
Screwdriver PZ2
cal. ISO 6789
Crimping tool in accordance with EN 60947-1
Ring lug terminals
Connection designations
IL1(°↑k, l↓), IL2(°↑k, l↓), IL3(°↑k, l↓)
V
1
, V
2
, V
3
, V
N
, L/+, N/-