Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
127
AUTO US
Time change within the USA
Changeover to daylight saving time: The
internal clock is put forward from 2 a.m.
local time to 3 a.m. on the second
Sunday in March.
Changeover to standard time: The
internal clock is put back from 2 a.m.
local time to 1 a.m. on the first Sunday in
November.
TABLE
Time change can be individually
parameterized. The parameters can be
set in the software.
Default value: AUTO EU
9.2.7
Integrated I/Os
Device settings for using the digital inputs and outputs.
Call: "SETTINGS > INTEGRATED I/O".
DIGITAL OUTPUT
Figure 9-6
"DIGITAL OUTPUT" device settings
DIG.OUTPUT
Digital output
Range:
0.0
Digital output DO0 (terminal labeling)
0.1
Digital output DO1 (terminal labeling)
Default value: 0.0
ACTION
Method of using the digital output:
Range:
OFF
The digital output is switched off.
DEVICE ON
The digital output is switched on.
REMOTE OUTPUT
The digital output is controlled by remote
access, e.g. SEAbus, SEAbus TCP,
PROFIBUS DP, Modbus RTU,
Modbus TCP.
Summary of Contents for SENTRON PAC4200
Page 66: ...Installation 5 4 Deinstalling SENTRON PAC4200 66 Manual 09 2008 A5E02316180B 01 ...
Page 118: ...Operator control 8 3 Special displays SENTRON PAC4200 118 Manual 09 2008 A5E02316180B 01 ...
Page 152: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 152 Manual 09 2008 A5E02316180B 01 ...
Page 168: ...Dimension drawings SENTRON PAC4200 168 Manual 09 2008 A5E02316180B 01 ...
Page 252: ...Index SENTRON PAC4200 252 Manual 09 2008 A5E02316180B 01 ...