Description
3.4 Power demands and counters
SENTRON PAC3200
32
Manual, 02/2008, A5E01168664B-04
3.4
Power demands and counters
Acquisition of power demand.
Values that can be read out:
SENTRON PAC3200 supplies the power demand of the last completed demand period:
●
Average values for active power and reactive power, import and export.
●
Minimum and maximum value within the period.
●
Length of the demand period in seconds. The period may be shorter for reasons of
external synchronization.
●
Time in seconds since the last synchronization or since completion of the last period.
Note
The power demand can only be read out via the interface and is not represented on the
display. The average values of the last demand period can only be retrieved during the
active demand period.
Example: Period length and length of the demand period
Period length: 15 minutes; time of day: 13:03; time in seconds: 180 s.
The following can be calculated from this: The last demand period ended at 13:00. The
active demand period will end at 13:15 or in 12 minutes.
Settable parameters:
●
Period length in minutes (adjustable between 1 and 60 mins, default 15 mins).
●
Synchronization via bus or digital input.
Energy counter
SENTRON PAC3200 has energy counters for off-peak and on-peak energy types (total of 10
counters):
●
Active energy import
●
Active energy export
●
Reactive energy positive
●
Reactive energy negative
●
Apparent energy
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...